Congratulations on your purchase of this product from the Niko dimmer 
range. 

1. LEGAL WARNINGS

- Read the complete manual before attempting installation and activating 

the system.

- The installation has to be carried out by a qualified person and in compli-

ance with the statutory regulations.

- This user manual has to be handed over to the user. It has to be included 

in the electrical installation file and has to be passed on to any new 
owners. Additional copies are available on the Niko website or via the 
support service.

- During installation, the following has to be taken into account (not limited 

to list below):

  - The statutory laws, standards and regulations;
  - The state of the art technique at the moment of installation;
  - This user manual, which must be read within the scope of each specific 

installation, only states general regulations;

  - The rules of proper workmanship
- In case of questions, you can consult Niko’s support service or contact 

a registered control organisation.

  Support Belgium: 

Support Slovakia:

  +32 3 760 14 82 

+421 263 825 155

  website : http://www.niko.be 

e-mail: [email protected]

  e-mail: [email protected]
In case of a defect, you can return your product to a registered Niko 
wholesaler, together with a clear description of your complaint (Conditions 
of use, stated defect…).

2. DESCRIPTION

Controlling the intensity (dimming) of all dimmable loads except for fluo-
rescent lamps.
Resistive loads: incandescent lamps, 230V halogen lamps...
Inductive loads: ferromagnetic transformers
Capacitive loads: electronic transformers...

3. OPERATION AND USE

This dimmer (05-707) operates with power transistors instead of triacs. This 
allows both phase control and reverse phase control dimming.
In phase control, the dimmer is switched off at the zero crossing and 
switched on beforehand. This switch technique is recommended for 
inductive loads (ferromagnetic transformers). In reverse phase control, the 
dimmer is switched on at the zero crossing and switched off afterwards. 
This switch technique is recommended for:
- capacitive loads (dimmable, electronic transformers 230V~);
- resistive loads;
- mixed loads (above-men inductive loads) connected to the 

same dimmer.

Because the interference suppression is full-electronic and no chokes are 
used, these dimmers are completely silent and up to 30% lighter than 
classic dimmers. The technology used enables to electronically protect the 
dimmer against short-circuit, overcurrent and overvoltage.
This dimmer is remote controlled either via an analog signal or via potentialfree 
N.O. contacts (e.g. 07-000). The control is galvanically separated from the 
mains. Both the analog and the push button wiring is carried out under very 
low voltage. A lamp that is connected via dimmers cannot be dimmed to 
the max. light intensity. The light intensity will always be less in comparison 
with an identical lamp that is directly connected to the mains.

3.1 Analog control

 (e.g. via Nikobus 05-007-02)

This dimmer (05-707) can be remote controlled with any device that complies 
to the international 0-10V (voltage control) and the 1-10V (current control) 
standard. Operation is analogue (0V = off, 10V = max. light intensity). Analog 
control and signal cables are galvanically separated from the mains via the 
dimmer. The wiring is carried out in ELV (extra low voltage). 

3.2 Push button control

Any potentialfree N.O. contact can control the dimmer. Press briefly for 
on/off, press long to increase/decrease (fig. 1 & 2). The push buttons are 
galvanically separated from the mains via the dimmer. The wiring is carried 
out in ELV (extra low voltage).

3.3 Warning

- This devices are not suitable for controlling motors, unless the specific 

safety requirements are guaranteed by external systems (in this case, 
automatic restart after power cut is not allowed). 

- This device is exclusively suitable for DIN-rail mounting and must be 

mounted in a closed distribution board. 

- This device can only be connected to the power supply after installation 

of the necessary covers in the distribution board.

4. DIP SWITCH SETTINGS

Number

ON

OFF

1

phase control

reverse phase control

2

push button operation

analog signal

3

0-10V voltage control

1-10V current control

4

automatic selection

manual selection

Dimming mixed loads and activating the dimmer

A mixed load consists of wound transformers (inductive loads) and electronic 
transformers (capacitive loads) that are connected to the same dimmer. 
Lamps without control gear (e.g. incandescent lamps) are resistive and 
form a neutral load. If the load is not mixed, see 4.1 and 4.2.

Attention:

 for dimming mixed loads, the dimmer has to be set in reverse 

phase control. Mixed loads cannot be dimmed in phase control. Induction 
must be compensated in case the overvoltage protection is activated in 
reverse phase control (red LED no. 4 lights). Inductions of wound transformers 
are compensated in the same way as ballasts of fluorescent lamps: place 

a X-2 class capacitor between phase and neutral on the primary side of 
the transformer. Value ± 1micro Farad per 50VA. 
Follow the procedure described below if you are in doubt as to the type 
of load.
Set the dimmer in reverse phase control (dimming electronic transformers 
and/or resistive loads) by switching DIP switch 1 to OFF (4.2). If no red 
LEDs light, this means that the load is predominantly capacitive and that 
the setting is correct.
If one or more red LEDs light and/or the dimmer does not work (dimmer 
in protective mode), this means that the load is predominantly inductive. 
In this case, switch the DIP switch 1 to ON (= phase control for inductive 
loads, see 4.1). Press the reset key or set the analog signal to 0V to restart 
the dimmer. Resistive loads are neutral and have to be dimmed in reverse 
phase control.

4.1 Phase control: 

switch DIP switch 1 to ON

Only inductive loads (ferromagnetic transformers) can be dimmed in this 
mode. All other loads, incl. resistive loads, have to be dimmed in reverse 
phase control (4.2). When this mode is selected, yellow LED 1 lights as a 
check (5.1).

4.2 Reverse phase control: 

switch DIP switch 1 to OFF

Only resistive and capacitive loads can be dimmed in this mode. These 
loads can be mixed. Never connect only inductive loads in this mode (4.1). 
Also use this mode for mixed loads (ind capacitive).
Attention: electronic transformers of over 105VA are not suitable for dim-
ming. These transformers can produce unstable light (blinking). If the load 
is purely capacitive, the dimmer must be at least loaded by:
- 2 or more electronic transformers;
- or 1 electronic trans 1 electronic auxiliary load (09-016-10).
Switch the dimmer to this mode if you are in doubt as to the type of 
load. 

4.3 Push button control: 

switch DIP switch 2 to ON

This setting enables control via N.O. contacts. Press briefly for on/off. Press 
long to increase/decrease. When pressing long, the dim direction is reversed 
after each interruption (increase -> stop -> decrease -> stop -> increase 
-> …). The last level can be stored in a memory (4.9).

4.4 Analog controls: 

switch DIP switch 2 to OFF

This setting enables to control the dimmer via analog control signals (4.8).

4.5 Automatic selection of the type of control signal (0-10 or 1-

10V):

 switch DIP switch 4 to ON

In this mode, the dimmer will automatically discern the type of control 
signal and choose the setting (as opposed to the manual setting described 
in 4.6). This setting is only made when the power supply is switched on. 
Conditions for the use of automatic selection:
Only use the manual setting if several dimmers are connected to the same 
control output. The use of different types of dimmers can affect the detec-
tion. If 05-707 dimmers are distributed over different fuses, all fuses must 
be switched on within 10s. to avoid detection problems.

4.6 Manually setting the control signal: switch DIP switch 4 to 

OFF 

In this mode, the type of control signal (0-10 or 1-10V) is manually selected 
by the setting of DIP switch 3 (4.7 and 4.8).

4.7 Manually setting the control signal to 0-10V: switch DIP switch 

3 to ON

To use this function:
- DIP switch 4 first has to be switched to OFF (manually setting the control 

signal: see 4.6)

- DIP switch 2 has to be switched to OFF (analog control).
When this mode is selected, yellow LED 2 lights as a check. In this posi-
tion, the dimmer will accept a voltage control signal from 0 to 10V in 
accordance with the IEC standard 61131-2. From 0 to 10V it is possible 
to adjust the light intensity from 0.1% to max. The dimmer is switched off 
at 1V (functions as a solid-state relay).

4.8 Manually setting the control signal to 1-10V:

 switch DIP switch 

3 to OFF
To use this function:
- DIP switch 4 first has to be switched to OFF (manually setting the control 

signal: see 4.6). 

- DIP switch 2 has to be switched to OFF (analog control).
In this position, the dimmer operates via a current control signal from 1 to 
10V in accordance with the EN60929 standard (see also 4.7). From 0 to 
1V, there is no adjustment of the light intensity. From 1 to 10V it is possible 
to adjust the light intensity from 0.1% to max. The dimmer is switched off 
at 1V (functions as a solid-state relay).

4.9 Push button operation with memory: 

switch DIP switch 4 to ON

If the dimmer is controlled via a push button (4.3), you can choose operation 
with memory (DIP switch 4 to ON) or without memory (DIP switch 4 to OFF).  
Without memory, the dimmer switches on at max. light intensity. With memory, 
the dimmer switches on at the last set value. After the power voltage has been 
switched on, the dimmer switches on at 20%.

5. OPERATIONAL AND ERROR CONTROL BY MEANS OF LEDS

This dimmer is provided with a visual control function by means of 4 LEDs 
which remain visible on the front of the dimmer after installation.

From left to right (fig.4):

5.1 Indication of operation in phase control:  

LED 1 lights (yellow)

Inductive load symbol above LED 1. This LED lights when DIP switch 1 
is switched to ON.

5.2 Indication of control signal selection in voltage control: 

LED 2 lights (yellow)

Regulated supply symbol above LED 2. This LED lights when DIP switch 3 
is switched to ON and DIP switches 4 and 2 are switched to OFF.

5.3.1 Overcurrent:

 

LED 3 lights (red)

Symbol I above LED 3 and ‘overcurrent’ indication to the left of LED 3. 

This protection is activated if:
- the dimmer is overloaded;
- there is a short-circuit in the load circuit.
If the red LED lights, the protection is activated. This can happen in case 
of switch-on surges or short-circuits.
In case of a short-circuit, the dimmer is automatically switched off.
Note: all protection systems are active when the mains supply is switched 
on. For several seconds, they are deactivated one after the other. The dim-
mer does not react to the remote control signal for as long as this control 
has not been completed successfully.
Once the error has been rectified, the dimmer can be switched back 
on as follows:
- press the reset key;
- adjust the control signal to min. level (0 or 1V resp.).

Attention:

 this protection is not intended for people. An external automatic 

protection (automatic fuse) must always be provided.

5.3.2 First thermal protection:

 

LED 3 blinks (red)

If the temperature of the cooling surface exceeds 105°C, this protection 
is activated and:
- the third LED blinks (red);
- the power of the dimmer is restricted to 20% (the light intensity can be 

adjusted to max. 20%). 

As soon as the temperature has dropped, the LED goes out and the dimmer 
can be operated normally again.

5.4 Overvoltage protection: 

LED 4 lights (red)

Overvoltage protection (symbol U above LED 4 and ‘overvoltage’ indication 
to the left of LED 4).
This protection is activated if an overvoltage (greater than 480V for more 
than 100µs.) occurs. An overvoltage can have several causes:
- a temporary or otherwise fault on the 230V mains;
- magnetic transformer with a too high induction caused by e.g. insufficient 

load (min. load of magnetic transformers 75%);

- magnetic transformer with change in the load (defective lamps not 

replaced in time);

- the dimmer is not set to the correct mode, e.g. dimming inductive loads 

in reverse phase control instead of phase control (see 3).

If the protection is activated, this indicates an abnormal situation. If the 
dimmer stays in protection mode, the error must be found and rectified.
Once the error has been rectified, the dimmer can be switched back 
on as follows:
- press the reset key;
- or adjust the control signal to min. level (0 or 1V resp.).

5.5 Indication of direct current or thermal protection: 

LEDs 3 + 4 light 

Indication of direct current or thermal protection.

5.5.1 Direct-current protection 

If an asymmetry of over 1.5V is measured, the dimmer will enter protec-
tion mode. This is particularly important for dimming inductive loads. If 
the dimmer mistakenly dims inductive loads in reverse phase control, this 
protection will be activated. An too high asymmetry causes humming, 
heating and ultimately burning of transformers and lamps.

5.5.2 Second thermal protection

The second thermal protection is self-restoring. In case of overheating, the 
device is switched off from 115°C on the cooling surface. For as long as 
the thermal protection is activated,  the dimmer will not react to the control 
signal. If the temperature has dropped, the dimmer switches back on.

6. MAINS CONNECTIONS

6.1 top from left to right

L: 230V phase (power supply)
N: 230V neuter (power supply)
N: 230V neuter (load) interconnected

: regulated phase (load)

The neuter of the load must be connected to the dimmer. If the neuter 
is directly connected to the mains, the operation of the dimmer is not 
guaranteed.
Attention: before switching on, check whether all connections are secure. 
During maintenance on the installation, the pressure on the terminals 
must be checked. 

6.2 control connections: analog signal

Control with analog signal (bottom):
'-' terminal: mass of the control signal (0V)
'+' terminal: control signal: analog control from 0 or 1 to 10V  

Attention: 

the same terminals are used both for 0-10V voltage control 

and 1-10V current control and push button control. Take into account 
the polarity. In case several dimmers are connected to one and the same 
control output, never confuse the '-' and '+'.
The control input is galvanically separated. The insulation within the dimmer 
guarantees control at extra low voltage.
The 1-10V current control is described in the European standard EN60929. 
This control technique is mainly used for controlling electronic control gear 
(ECG) by means of so-called electronic potentiometers e.g. 09-011. The 
intensity of the current passing through the control circuit determines the 
light intensity. These so-called “current sink” control signals fundamentally 
differ from the 0-10V control signals, known as “source” signals. The 
0-10V voltage or “source” signals are typically used in professional ap-
plications such as: PLCs, Silicon Controls control systems or the Nikobus 
dim controller 05-007-02.

6.3 Control connections: push button control

Control with N.O. contacts (bottom):
'-' terminal: common for all contacts
'+' terminal: signal 
The push buttons can under no circumstances be connected to the mains.   

Summary of Contents for 05-707

Page 1: ...chtingomgekeerd opdimmen stop neerdimmen stop opdimmen Het laatste niveau wordt al dan niet in een geheugen opgeslagen 4 9 4 4 Analoge sturingen DIP switch 2 instellen op OFF Deze instelling laat toe...

Page 2: ...belasting is hoofdzakelijk afhankelijk van de omge vingstemperatuur g 3 Bijzondere opmerking i v m inductieve lasten ferromagnetische gewikkelde transformatoren moeten voor min 75 belast zijn het ver...

Page 3: ...kelen Voeding inschakelen Voeding inschakelen OK Inductieve lasten Overbelasting ferromagnetische transformatoren Voeding uitschakelen Ga naar stap 2 Belasting verminderen Voeding inschakelen Stap 2 I...

Page 4: ...vous doutez du type de la charge 4 3 Commande par bouton poussoir DIP switch 2 r gl sur ON Cette position autorise la commande au moyen de contacts N O Une pression br ve pour allumer teindre et une p...

Page 5: ...que importante pour charges inductives lestransformateursferromagn tiques bobin s doiventtoujoursfonctionner min 75 de leur charge la consommation de ceux ci est fonction du facteur de puissance cos p...

Page 6: ...tection active surcharge transformateurs ferromagn tiques D branchez l alimentation Proc dure n 2 R duire la charge Branchez l alimentation Proc dure N 2 Choix du type de commande D branchez l aliment...

Page 7: ...immer muss in diesem Modus eingeschaltet werden wenn nicht eindeutig ist welcher Belastungstyp vorliegt 4 3 Drucktastenbedienung Dip Schalter 2 auf ON stellen Diese Einstellung erm glicht eine Bet tig...

Page 8: ...osinus phi erh ht werden bei Verwendung von Ringkerntransformatoren ist die H chstbelastung auf 450W be grenzt 11 WARTUNG Diese Ger te sind f r eine Verwendung unter folgenden Bedingungen ausgelegt ei...

Page 9: ...en OK Induktive lasten berlast gewickelte Transformatoren Netzversorgung ausschalten Weiter mit Schritt 2 Last vermindern Netzversorgung einschalten Schritt 2 Einstellen Steuerung Netzversorgung aussc...

Page 10: ...is only made when the power supply is switched on Conditions for the use of automatic selection Only use the manual setting if several dimmers are connected to the same control output The use of diffe...

Page 11: ...rculation with regard to the total dissipated power If the natural air circulation is limited a fan must be provided in the cabinet or in the room Nominal ambient temperature 20 C 9 INTERFERENCE SUPPR...

Page 12: ...pply on Switch on power supply OK Inductive loads Overload ferromagnetic transformers Switch off power supply Go to step 2 Reduce load Switch on power supply Step 2 Choice of remote control Switch off...

Page 13: ...interrupci n subir parada bajar parada subir etc El ltimo nivel luminoso puede ser me morizado 4 9 4 4 Mando anal gico DIP switch 2 ajustado en OFF Esta posici n admite que se controle el regulador po...

Page 14: ...nte de la temperatura ambiente gura 3 Observaci n importante para cargas inductivas los transformadores ferromagn ticos bobinados deben funcionar siempre como m nimo al 75 de su carga el consumo de st...

Page 15: ...ivas Protecci n activa sobrecarga transformadores ferromagn ticos Desconectar la alimentaci n Procedimiento n 2 Reducir la carga Conectar la alimentaci n Procedimiento N 2 Elecci n del modo de mando D...

Page 16: ...on 600 W ta 35C 230V 50Hz 1 2 3 4 ON DIP 14 CEBEC R L C I U reset L N N 05 707 overcurrent overvoltage DC protection 600 W ta 35C 230V 50Hz 1 2 3 4 ON DIP 14 CEBEC R L C I U reset L N N 05 707 overcur...

Reviews: