Service menus
VVM 240
42
Operating settings
Menu 9.3.0 Operating settings
Settings regarding the electric boiler, floor drying and
a return to the factory settings can be made on the
sub-menus in this menu.
O p e r a t i n g s e t t i n g s
9 . 3 . 0
Menu 9.3.3 Extra Shunt Present
This menu is used to select On or Off depending on
whether you have shunt group 2 (accessories need-
ed).
O f f
E x t r a S h u n t P r e s e n t
9 . 3 . 3
Menu 9.3.4 Room unit
Accessories are needed.
R o o m u n i t
9 . 3 . 4
Menu 9.3.5.0 Floor drying
Settings for the floor drying program are made in the
sub-menus to this menu.
F l o o r d r y i n g
9 . 3 . 5 . 0
Menu 9.3.2 Electric boiler
Electric boiler mode is actuated when Yes is shown on
the display, otherwise No is displayed. When the elec-
tric boiler mode is activated, the immersion heater
respective circulation pump cannot be blocked with
the operating mode button.
N o
E l e c t r i c b o i l e r
9 . 3 . 2
Menu 9.3.1 Max. Boilertemp.
The setting selected on the load monitor card (2) knob
(102) is shown here.
8 0 ° C
M a x . B o i l e r t e m p .
9 . 3 . 1
Menu 9.3.5.1 Floor drying
This sub-menu is used to select whether the floor dry-
ing program should be On or Off. After time period 1
switching to time period 2 then return to normal set-
tings.
O f f
F l o o r d r y i n g
9 . 3 . 5 . 1
Menu 9.3.5.2 Numb. of days per. 1
Selection of the number of days in period 1.
The value is adjustable between 1 to 5 days.
3 D a y s
N u m b . o f d a y s p e r . 1
9 . 3 . 5 . 2
Menu 9.3.5.3 Temp per. 1
Selection of the flow temperature in period 1.
The value is adjustable between 15 and 50 °C.
2 5 ° C
T e m p p e r . 1
9 . 3 . 5 . 3
S
S
S
S
S
S
S
S
S
Menu 9.3.5.4 Numb. of days per. 2
Selection of the number of days in period 2.
The value is adjustable between 1 to 5 days.
1 D a y
N u m b . o f d a y s p e r . 2
9 . 3 . 5 . 4
S