Service menus
39
VVM 240
Menu 9.1.0 Heat pump settings
Settings concerning FIGHTER 2010 are made in the
sub-menus to this.
H e a t p u m p s e t t i n g s
9 . 1 . 0
Menu 9.1.1 Compressor starts at
Degree minute setting for start of FIGHTER 2010. The
value is adjustable between -100 and 0.
- 6 0
C o m p r e s s o r s t a r t s a t
9 . 1 . 1
Menu 9.1.2 Number of F2010
The number of connected FIGHTER 2010s. The value
set can either be 0 or 1.
1
N u m b e r o f F 2 0 1 0
9 . 1 . 2
Menu 9.1.3 Start defrost*
The required start temperature on the evaporator sen-
sor for defrosting of FIGHTER 2010 is set here. The
value is adjustable between -10 and +2 °C.
- 3 ° C
S t a r t d e f r o s t ( 0 6 )
9 . 1 . 3
Menu 9.1.5 Max defrost time*
The longest time for defrosting of FIGHTER 2010 is
selected here. The value is adjustable between 5 and
12 min.
7 m i n
M a x d e f r o s t t i m e ( 0 9 )
9 . 1 . 5
Menu 9.1.7 Powerstepup*
Outdoor air temperature, to change the power step in
FIGHTER 2010. The value is adjustable between 0
and 40 °C.
7 ° C
P o w e r s t e p u p ( 1 4 )
9 . 1 . 7
Menu 9.1.6 Time betw. defr*
Minimum running time, heat production before new
defrosting is permitted in FIGHTER 2010. The value is
adjustable between 10 and 90 minutes.
5 0 m i n
T i m e b e t w . d e f r ( 1 0 )
9 . 1 . 6
Menu 9.1.8 Drip tray heater*
Outdoor air temperature, for start of the drip tray
heater in FIGHTER 2010. The value is adjustable
between -2 and +2 °C.
2 ° C
D r i p t r a y h e a t e r
9 . 1 . 8
Menu 9.1.4 Stop defrost*
The required stop temperature on the evaporator sen-
sor for defrosting of FIGHTER 2010 is set here. The
value is adjustable between 10 and 40 °C.
1 0 ° C
S t o p d e f r o s t ( 0 7 )
9 . 1 . 4
Heat pump settings
S
S
S
S
S
S
S
S
S
*
The numbers in brackets denote the corresponding
channel number in FIGHTER 2010.
Menu 9.1.9 Balancetemp.*
No function
5 ° C
B a l a n c e t e m p . ( 1 7 )
9 . 1 . 9
S