May be due to
Description
Alarm text on the dis-
play
Alarm
■
Open circuit or short circuit on sensor
input
■
Sensor does not work (see section "Dis-
turbances in comfort")
■
Defective control board AA23 in F2040
Sensor fault, Sensor incoming water in
F2040 (BT3).
Sensor fault BT3
3
■
Open circuit or short circuit on sensor
input
■
Sensor does not work (see section "Dis-
turbances in comfort")
■
Defective control board AA23 in F2040
Sensor fault, Sensor outgoing water in
F2040 (BT12).
Sensor fault BT12
12
■
Open circuit or short circuit on sensor
input
■
Sensor does not work (see section "Dis-
turbances in comfort")
■
Defective control board AA23 in F2040
Sensor fault, Sensor fluid pipe in F2040
(BT15).
Sensor fault BT15
15
■
Low flow during heating operation
■
Too high set temperatures
Too high temperature out from the con-
denser. Self-resetting.
High condenser out
162
■
Temperature generated by another
heat source
Too high temperature into the condenser.
Self-resetting.
High condenser in
163
■
Set when the heat pump runs the de-
frosting procedure
Not an alarm, but an operating status.
Defrosting in progress
183
■
Insufficient air circulation or blocked
heat exchanger
■
Open circuit or short circuit on input for
high pressure switch (63H1)
■
Defective high pressure switch
■
Expansion valve not correctly connected
■
Service valve closed
■
Defective control board in F2040
■
Low or no flow during heating opera-
tion
■
Defective circulation pump
■
Defective fuse, F(4A)
The high pressure switch (63H1) deployed
5 times within 60 minutes or for 60
minutes continuously.
HP alarm
220
■
Open circuit or short circuit on input for
low pressure sensor
■
Defective low pressure sensor
■
Defective control board in F2040
■
Open circuit or short circuit on input for
suction gas sensor (Tho-S)
■
Defective suction gas sensor (Tho-S)
Too low value on the low pressure sensor
3 times within 60 minutes.
LP alarm
221
■
Any circuit breakers for F2040 off
■
Incorrect cable routing
Communication between the control
board and the communication board is
interrupted. There must be 22 volt direct
current (DC) at the switch CNW2 on the
control board (PWB1).
OU Com. error
223
51
Chapter 9 |
Alarm list
F2040
9 Alarm list
Summary of Contents for F2040-12
Page 1: ...Installer manual LEK LEK LEK UN F2040 6 8 12 16 Air water heat pump IHB EN 1746 6 231844 ...
Page 2: ......
Page 47: ...Connection to board AA23 BP4 BT15 BT12 BT3 AA23 S3 47 Chapter 8 Disturbances in comfort F2040 ...
Page 74: ...F2040 Chapter 11 Technical data 74 ...
Page 77: ...F2040 12 77 Chapter 11 Technical data F2040 ...