Data for return line temperature sensor (BT3),
condensor supply (BT12) and fluid pipe (BT15)
Voltage (VDC)
Resistance
(kOhm)
Temperature
(°C)
3.256
351.0
-40
3.240
251.6
-35
3.218
182.5
-30
3.189
133.8
-25
3.150
99.22
-20
3.105
74.32
-15
3.047
56.20
-10
2.976
42.89
-5
2.889
33.02
0
2.789
25.61
5
2.673
20.02
10
2.541
15.77
15
2.399
12.51
20
2.245
10.00
25
2.083
8.045
30
1.916
6.514
35
1.752
5.306
40
1.587
4.348
45
1.426
3.583
50
1.278
2.968
55
1.136
2.467
60
1.007
2.068
65
0.891
1.739
70
0.785
1.469
75
0.691
1.246
80
0.607
1.061
85
0.533
0.908
90
0.469
0.779
95
0.414
0.672
100