May be due to
Description
Alarm text on the dis-
play
Alarm
■
Cold weather conditions
■
Sensor fault
Temperature of BT28 below the value that
permits operation
Cold outdoor air
271
■
Warm weather conditions
■
Sensor fault
Temperature of BT28 above the value that
permits operation
Hot outdoor air
272
■
Open circuit or short circuit on sensor
input
■
Sensor does not work (see section "Dis-
turbances in comfort")
■
Defective control board in F2040
Sensor fault, heat exchanger in
F2040(Tho-R).
Sensor fault Tho-R
277
■
Open circuit or short circuit on sensor
input
■
Sensor does not work (see section "Dis-
turbances in comfort")
■
Defective control board in F2040
Sensor fault, outdoor temperature sensor
in F2040 (Tho-A).
Sensor fault Tho-A
278
■
Open circuit or short circuit on sensor
input
■
Sensor does not work (see section "Dis-
turbances in comfort")
■
Defective control board in F2040
Sensor fault, hot gas in F2040 (Tho-D).
Sensor fault Tho-D
279
■
Open circuit or short circuit on sensor
input
■
Sensor does not work (see section "Dis-
turbances in comfort")
■
Defective control board in F2040
Sensor fault, suction gas in F2040 (Tho-S).
Sensor fault Tho-S
280
■
Open circuit or short circuit on sensor
input
■
Sensor does not work (see section "Dis-
turbances in comfort")
■
Defective control board in F2040
■
Fault in the refrigerant circuit
Sensor fault, low pressure transmitter in
F2040.
Sensor fault LPT
281
■
Outdoor module and indoor module
are not compatible.
Heat pump and indoor module do not
work properly together due to technical
parameters.
Non-compatible air/wa-
ter heat pump
294
Open circuit or short circuit on sensor in-
put
Sensor fault, Sensor high pressure heat-
ing/low pressure cooling in F2040 (BP4).
Sensor fault BP4
404
Sensor does not work (see section "Dis-
turbances in comfort")
Defective control board AA23 in F2040
53
Chapter 9 |
Alarm list
F2040
Summary of Contents for F2040-12
Page 1: ...Installer manual LEK LEK LEK UN F2040 6 8 12 16 Air water heat pump IHB EN 1746 6 231844 ...
Page 2: ......
Page 47: ...Connection to board AA23 BP4 BT15 BT12 BT3 AA23 S3 47 Chapter 8 Disturbances in comfort F2040 ...
Page 74: ...F2040 Chapter 11 Technical data 74 ...
Page 77: ...F2040 12 77 Chapter 11 Technical data F2040 ...