Menu 7.5.3 [U] Heating system
The climate system that the vacation set back is to affect
is selected here. If shunt group 2 is present the menu can
be set to “Off”, “System 1”, “System 2” or “System 1+2”.
In other cases only "Off" and "System 1" can be selected.
Setting range: Off, System 1, System 2, System 1+2
Default value: Off
Menu 7.5.4 [U] Offset heating curve
How much the heating curve is to be offset during the
holiday period is set here.
If the relevant climate system has a room temperature
sensor, the change is given in degrees.
Setting range: -10 – 10
Default value: -5
Menu 7.5.5 [U] HW off
If the hot water charge is to be shut off during the holiday
period this is set here.
Setting range: No, Yes
Default value: Yes
Menu 7.5.6 [U] Return
Return to menu 7.5.0.
Menu 7.6.0 [N] Silent mode
The period for silent mode, where the heat pump operates
at a lower noise level by limiting the compressor and fan
speeds, is selected in the sub-menu.
Menu 7.6.1 [N] Silent mode time
The time interval for silent mode is set here. The period is
selectable for a maximum of 23:45 (hh:mm) with incre-
ments of 15 min. If the same time is selected for stop and
start the function is off.
Default values: off
Menu 7.6.2 [N] Return
Return to menu 7.6.0.
Menu 7.7 [N] Return
Return to menu 7.0.
8.0 [N] Other adjustments
Menu 8.1.0 [N] Display settings
Settings concerning language and menu type are set in
the sub-menus to this menu.
Menu 8.1.1 [N] Menu type
The menu type is chosen here.
Normal, covers the normal user's needs.
[N]
Extended, shows all menus except the service menus.
[U]
Service, shows all menus, returns to normal menu level
30 minutes after the last button was pressed.
[S]
NOTE
Incorrect settings in the service menus can damage
the property and/or heat pump.
Setting range: N, U, S
Default value: N
Menu 8.1.2 [N] Language
Language settings are made here.
Menu 8.1.3 [U] Display contrast
The display's contrast is set here.
Setting range: 0 – 31
Default value: 20
Menu 8.1.4 [U] Light intensity
The light intensity in idle mode is set here. Idle mode starts
30 minutes after the last button was pushed.
Setting range: 0=off, 1=low, 2=average.
Default value: 1
Menu 8.1.5 [N] Return
Return to menu 8.1.0.
Menu 8.2.0 [N] Op. mode settings
Settings regarding auto mode can be made in the sub-
menus to this menu.
Menu 8.2.1 [N] Allow add. heat
At which operating mode the electric addition is to be
permitted to produce hot water and heat when needed
is selected here.
Setting range: Off, Heating, H Cooling, Cooling
Default values: Heating
Menu 8.2.2 [N] Add. heat mode
Selected if electric addition is to be used to produce hot
water and heat.
Setting range: Off, On
Default value: Off
Menu 8.2.3 [U] Stop temp. heating
The average outdoor air temperature at which the heat
pump (in auto mode) is to stop heat production.
When the average outdoor air temperature falls below
Stop temp. heating – Hysteresis (menu 8.2.5) heating starts
again.
Setting range: 1 – 43 °C
Default value: 17 °C
NIBE™ SPLIT
56
Miscellaneous
Control
Summary of Contents for AMS 10-16
Page 2: ...HE 30 LEK LEK LEK LEK LEK HEV 300 LEK HEV 500 LEK LEK AMS 10 16 LEK HBS 16 ...
Page 70: ...Electrical circuit diagram HBS 16 NIBE SPLIT 68 Miscellaneous Electrical circuit diagram ...
Page 71: ...69 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Page 72: ...NIBE SPLIT 70 Miscellaneous Electrical circuit diagram ...
Page 73: ...71 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Page 74: ...NIBE SPLIT 72 Miscellaneous Electrical circuit diagram ...
Page 75: ...73 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Page 76: ...AMS 10 16 NIBE SPLIT 74 Miscellaneous Electrical circuit diagram ...
Page 100: ...NIBE SPLIT 98 ...
Page 101: ...99 NIBE SPLIT ...
Page 102: ...NIBE SPLIT 100 ...
Page 103: ......