May be due to
Description
Alarm text on the dis-
play
Alarm
no.
- Low flow in heating operation
Too high temperature out from the condenser.
High KF
6
- Too high set temperatures
Occurs if alarm 71 occurs 3 times within an hour.
- Low flow during defrost
Anti-freeze of heat exchanger.
Anti freeze HX
7
- Abnormally low temperature in the climate
system
Occurs if alarm 72 occurs 3 times within an hour.
- Low flow during defrost
Occurs if the alarm 77 occurs 10 times in succes-
sion.
Defrosting interrupted
14
- Abnormally low temperature in the climate
system
- Lack of refrigerant or leak
- Indoor unit and outdoor unit not compatible
with each other.
Indoor unit and outdoor unit do not communic-
ate with each other.
OU not compatible
15
- Low flow during defrost
Occurs if the alarm 78 occurs 10 times in succes-
sion.
Defrosting interrupted
16
- Open-circuit or short-circuit on sensor input
Sensor fault, high pressure (BP4).
S. fault HP
31
- Sensor does not work
- Open-circuit or short-circuit on sensor input
Sensor fault, cond out (BT12).
Sensor fault KF
32
- Sensor does not work (see "Temperature
sensor" section)
- Open-circuit or short-circuit on sensor input
Sensor fault, liquid line (BT15).
S. fault Liquid line
33
- Sensor does not work (see "Temperature
sensor" section)
AMS 10 alarm
The following alarms block AMS 10. Addition runs at min permitted supply temperature.
May be due to
Description
Alarm text on the dis-
play
Alarm
no.
- Any isolator switches for AMS 10 off
Communication between the outdoor unit and
HBS 16 is broken. There must be 22 volt direct
current (DC) in the switch CNW2 on the control
board (PWB1).
OU Com. error
E5
- Incorrect cable routing
- Sensor does not work (see "Temperature
sensor" section)
Temperature deviation on the hot gas sensor
(Tho-R1/R2) five times within 60 minutes or un-
der 60 minutes.
High HX temp
E35
- Insufficient air circulation or blocked heat ex-
changer
- Defective control board in AMS 10
- Too much refrigerant
- Sensor does not work (see "Temperature
sensor" section)
Temperature deviation on the hot gas sensor
(Tho-D) two times within 60 minutes or under
60 minutes.
Permanent Hotgas
E36
- Insufficient air circulation or blocked heat ex-
changer
- If the fault persists during cooling, there may
be an insufficient amount of refrigerant.
- Defective control board in AMS 10
- Open-circuit or short-circuit on sensor input
Sensor fault, heat exchanger in AMS 10 (Tho-R).
S. fault Tho-R
E37
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
NIBE™ SPLIT
64
Miscellaneous
Alarm list
Summary of Contents for AMS 10-16
Page 2: ...HE 30 LEK LEK LEK LEK LEK HEV 300 LEK HEV 500 LEK LEK AMS 10 16 LEK HBS 16 ...
Page 70: ...Electrical circuit diagram HBS 16 NIBE SPLIT 68 Miscellaneous Electrical circuit diagram ...
Page 71: ...69 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Page 72: ...NIBE SPLIT 70 Miscellaneous Electrical circuit diagram ...
Page 73: ...71 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Page 74: ...NIBE SPLIT 72 Miscellaneous Electrical circuit diagram ...
Page 75: ...73 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Page 76: ...AMS 10 16 NIBE SPLIT 74 Miscellaneous Electrical circuit diagram ...
Page 100: ...NIBE SPLIT 98 ...
Page 101: ...99 NIBE SPLIT ...
Page 102: ...NIBE SPLIT 100 ...
Page 103: ......