May be due to
Description
Alarm text on the dis-
play
Alarm
no.
- Open-circuit or short-circuit on sensor input
Sensor fault, outdoor sensor in AMS 10 (Tho-A).
S. fault Tho-A
E38
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
- Open-circuit or short-circuit on sensor input
Sensor fault, hot gas in AMS 10 (Tho-D).
S. fault Tho-D
E39
- Sensor does not work (see "Temperature
sensor" section)
- Defective control board in AMS 10
- Insufficient air circulation or blocked heat ex-
changer
The high pressure pressostat (63H1) deployed 5
times within 60 minutes or under 60 minutes
continuously.
HP alarm
E40
- Open circuit or short circuit on input for high
pressure pressostat (63H1)
- Defective high pressure pressostat
- Expansion valve not correctly connected
- Service valve closed
- Defective control board in AMS 10
- Low or no flow during heating operation
- Defective circulation pump
- Defective fuse, F(4A)
Can occur when 15V power supply to the inverter
PCB is unstable.
When IPM (Intelligent power module) displays
FO-signal (Fault Output) five times during a 60-
minute period.
Power transistor too hot
E41
- Incoming power supply interference
Voltage from the inverter outside the parameters
four times within 30 minutes.
Inverter error
E42
- Service valve closed
- Insufficient amount of refrigerant
- Compressor fault
- Defective circuit board for inverter in AMS 10
- Open-circuit in connection between boards
Communication between circuit board for invert-
er and control board broken.
Inverter error
E45
- Defective circuit board for inverter in AMS 10
- Defective control board in AMS 10
- Sudden power failure
Overcurrent, Inverter A/F module
Inverter error
E47
- The fan cannot rotate freely
Deviations in the fan speed in AMS 10.
Fan alarm
E48
- Defective control board in AMS 10
- Defective fan motor
- Control board in AMS 10 dirty
- Fuse (F2) blown
- Open circuit or short circuit on input for low
pressure transmitter
Too low value on the low pressure transmitter 3
times within 60 minutes.
LP alarm
E49
- Defective low pressure transmitter
- Defective control board in AMS 10
- Open circuit or short circuit on input for suction
gas sensor (Tho-S)
- Defective suction gas sensor (Tho-S)
- Defective fan motor
Continuous deviation on power transistor for 15
minutes.
Inverter error
E51
- Defective circuit board for inverter in AMS 10
65
NIBE™ SPLIT
Miscellaneous
Alarm list
Summary of Contents for AMS 10-16
Page 2: ...HE 30 LEK LEK LEK LEK LEK HEV 300 LEK HEV 500 LEK LEK AMS 10 16 LEK HBS 16 ...
Page 70: ...Electrical circuit diagram HBS 16 NIBE SPLIT 68 Miscellaneous Electrical circuit diagram ...
Page 71: ...69 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Page 72: ...NIBE SPLIT 70 Miscellaneous Electrical circuit diagram ...
Page 73: ...71 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Page 74: ...NIBE SPLIT 72 Miscellaneous Electrical circuit diagram ...
Page 75: ...73 NIBE SPLIT Miscellaneous Electrical circuit diagram ...
Page 76: ...AMS 10 16 NIBE SPLIT 74 Miscellaneous Electrical circuit diagram ...
Page 100: ...NIBE SPLIT 98 ...
Page 101: ...99 NIBE SPLIT ...
Page 102: ...NIBE SPLIT 100 ...
Page 103: ......