Measurements and settings
56
TemBreak
PRO
P_SE-UM-001-EN
– V1.2.0
Power Related Measurements
The P_SE OCR calculates the electrical power related parameters in real-time by taking discrete instantaneous measurements of voltage and current at
regular sample intervals, with the available data refreshed once every second:
-
Active power (P)
-
Reactive power (Q)
-
Apparent power (S)
-
Power Factor (PF)
-
Fundamental power factor
(Cosφ)
-
Power sign
-
Power quadrant
Active, Reactive, Apparent power
Active (P), Reactive (Q) and Apparent (S) Power related parameters vary in availability according to system topology (3Ph or 3Ph+N), which are provided in
the following table. Individual power values per phase are only available on MCCB variants with a Neutral reference, whereas total 3-phase power values
are available for both system topologies.
Electrical Parameter
Symbol
3Ph
3Ph+N
Active power per phase
P
1
, P
2
, P
3
─
✓
Apparent power per phase
S
1
, S
2
, S
3
─
✓
Reactive power per phase
Q
1
, Q
2
, Q
3
─
✓
Total 3-phase active power
P
tot
✓
✓
Total 3-phase reactive power
Q
tot
✓
✓
Total 3-phase apparent power
S
tot
✓
✓
Notice
: Accuracy and correct polarity of power related measurements are dependent on several calculation,
power flow and sign convention settings. Refer to the respective sections for details on these settings:
Power flow direction and quadrant
Summary of Contents for Terasaki TemBreak PRO P SE Series
Page 106: ...106 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex A Dimensions P160 Dimensions...
Page 107: ...Annex A Dimensions 107 TemBreak PRO P_SE UM 001 EN V1 2 0 P250 Dimensions...
Page 108: ...Annex A Dimensions 108 TemBreak PRO P_SE UM 001 EN V1 2 0 P400 Dimensions...
Page 109: ...Annex A Dimensions 109 TemBreak PRO P_SE UM 001 EN V1 2 0 P630 Dimensions...
Page 111: ...111 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex C I2t Let Through Curves P160_SE...
Page 112: ...Annex C I2t Let Through Curves 112 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Page 113: ...Annex C I2t Let Through Curves 113 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Page 114: ...Annex C I2t Let Through Curves 114 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Page 115: ...115 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex D Peak Let Through Curves P160_SE...
Page 116: ...116 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Page 117: ...117 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Page 118: ...118 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Page 121: ...121 TemBreak PRO P_SE UM 001 EN V1 2 0 This page is intentionally left blank...