Internal Accessories
15
TemBreak
PRO
P_SE-UM-001-EN
– V1.2.0
Shunt Trip
A shunt (normally de-energized) can be installed to trip the MCCB by applying voltage to the shunt coil.
Part Number
Rated voltage
Connection Type
AC (V)
DC (V)
T2SH00LA10T
110
─
Terminal
T2SH00LA20T
230…240
─
Terminal
T2SH00LA40T
400…415
─
Terminal
T2SH00LD01T
─
12 Terminal
T2SH00LD02T
─
24 Terminal
T2SH00LD04T
─
48 Terminal
T2SH00LD10T
─
110 Terminal
T2SH00LD20T
─
230 Terminal
T2SH00LA10WA
110
─
Pre-wired cage clamp
T2SH00LA20WA
230…240
─
Pre-wired cage clamp
T2SH00LA40WA
400…415
─
Pre-wired cage clamp
T2SH00LD01WA
─
12 Pre-wired cage clamp
T2SH00LD02WA
─
24 Pre-wired cage clamp
T2SH00LD04WA
─
48 Pre-wired cage clamp
T2SH00LD10WA
─
110 Pre-wired cage clamp
T2SH00LD20WA
─
230 Pre-wired cage clamp
Rated voltage
AC (V)
DC (V)
100…120
200…240
380...450
12
24
48
100…120
200…240
Excitation current (mA)
16.0
16.0
6.2
160.0
124.0
32.0
14.0
12.0
Under Voltage Trips
A UVT (normally energized) can be installed to trip the MCCB removing voltage from the UVT coil.
Part Number
Rated voltage
Compatible MCCB
Connection Type
Notes
AC (V)
DC (V)
3P
4P
T2UV00LA10NT
110
─
All
P160 / 250
Terminal
Instantaneous
T2UV00LA20NT
230…240
─
All
P160 / 250
Terminal
Instantaneous
T2UV00LA40NT
400…440
─
All
P160 / 250
Terminal
Instantaneous
T2UV00LD02NT
─
24
All
P160 / 250
Terminal
Instantaneous
T2UV00LD10NT
─
110
All
P160 / 250
Terminal
Instantaneous
T2UV00LD20NT
─
230
All
P160 / 250
Terminal
Instantaneous
T2UV00LA10DS
110
─
All
P160 / 250
Terminal
Time Delay 500ms
T2UV00LA24DS
230…240
─
All
P160 / 250
Terminal
Time Delay 500ms
T2UV00LA45DS
440…450
─
All
P160 / 250
Terminal
Time Delay 500ms
T2UV00LD02DS
─
24
All
P160 / 250
Terminal
Time Delay 500ms
T2UV00LD10DS
─
110
All
P160 / 250
Terminal
Time Delay 500ms
T2UV00LD24DS
─
230
All
P160 / 250
Terminal
Time Delay 500ms
T2UV00LA10DL
110
─
─
P400 / 630
Terminal
Time Delay 500ms
T2UV00LA24DL
230…240
─
─
P400 / 630
Terminal
Time Delay 500ms
T2UV00LA40DL
380
…
415
─
─
P400 / 630
Terminal
Time Delay 500ms
T2UV00LA45DL
440…450
─
─
P400 / 630
Terminal
Time Delay 500ms
T2UV00LD02DL
24
─
P400 / 630
Terminal
Time Delay 500ms
T2UV00LD10DL
110
─
P400 / 630
Terminal
Time Delay 500ms
T2UV00LD24DL
230
─
P400 / 630
Terminal
Time Delay 500ms
T2UV00LA10NWA
110
─
All
P160 / 250
Pre-wired cage clamp
Instantaneous
T2UV00LA20NWA
230…240
─
All
P160 / 250
Pre-wired cage clamp
Instantaneous
T2UV00LA40NWA
440…450
─
All
P160 / 250
Pre-wired cage clamp
Instantaneous
T2UV00LD02NWA
─
24
All
P160 / 250
Pre-wired cage clamp
Instantaneous
T2UV00LD10NWA
─
110
All
P160 / 250
Pre-wired cage clamp
Instantaneous
T2UV00LD20NWA
─
230
All
P160 / 250
Pre-wired cage clamp
Instantaneous
Rated Voltage
AC (V)
DC (V)
100…120
200…240
380…450
24
100…120
200…240
Excitation current (mA)
1.3
1.1
2.0
22.0
9.0
3.7
Summary of Contents for Terasaki TemBreak PRO P SE Series
Page 106: ...106 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex A Dimensions P160 Dimensions...
Page 107: ...Annex A Dimensions 107 TemBreak PRO P_SE UM 001 EN V1 2 0 P250 Dimensions...
Page 108: ...Annex A Dimensions 108 TemBreak PRO P_SE UM 001 EN V1 2 0 P400 Dimensions...
Page 109: ...Annex A Dimensions 109 TemBreak PRO P_SE UM 001 EN V1 2 0 P630 Dimensions...
Page 111: ...111 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex C I2t Let Through Curves P160_SE...
Page 112: ...Annex C I2t Let Through Curves 112 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Page 113: ...Annex C I2t Let Through Curves 113 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Page 114: ...Annex C I2t Let Through Curves 114 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Page 115: ...115 TemBreak PRO P_SE UM 001 EN V1 2 0 Annex D Peak Let Through Curves P160_SE...
Page 116: ...116 TemBreak PRO P_SE UM 001 EN V1 2 0 P250_SE...
Page 117: ...117 TemBreak PRO P_SE UM 001 EN V1 2 0 P400_SE...
Page 118: ...118 TemBreak PRO P_SE UM 001 EN V1 2 0 P630_SE...
Page 121: ...121 TemBreak PRO P_SE UM 001 EN V1 2 0 This page is intentionally left blank...