MASTER
TRACE
B.4
Appendix B Display Message
Details - Measured
MESSAGE NO:
M2-05
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 100.0 A
DISPLAY MODE: Advanced
RESTRICTIONS: Single-Phase Modules
The displayed value is the highest Heater Current since the last reset. The
maximum value range for internal switching modules is 30.0 A. If the displayed
value is “O.L.”, a value greater than the maximum range was recorded. To reset the
displayed value press [RESET]. To reset with all statistics use RESET
STATISTICS function.
MESSAGE NO:
M2-06
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 100.0 A
DISPLAY MODE: Advanced
RESTRICTIONS: Three-Phase Modules
The displayed value is the highest Heater Current-A since the last reset. If the
displayed value is “O.L.”, a value greater than the maximum range was recorded.
To reset the displayed value press [RESET]. To reset with all statistics use RESET
STATISTICS function.
MESSAGE NO:
M2-07
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 100.0 A
DISPLAY MODE: Advanced
RESTRICTIONS: Three-Phase Modules
The displayed value is the highest Heater Current-B since the last reset. If the
displayed value is “O.L.”, a value greater than the maximum range was recorded.
To reset the displayed value press [RESET]. To reset with all statistics use RESET
STATISTICS function.
MESSAGE NO:
M2-08
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 100.0 A
DISPLAY MODE: Advanced
RESTRICTIONS: Three-Phase Modules
The displayed value is the highest Heater Current-C since the last reset. If the
displayed value is “O.L.”, a value greater than the maximum range was recorded.
To reset the displayed value press [RESET]. To reset with all statistics use RESET
STATISTICS function.
MESSAGE NO:
M2-09
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 1000 mA
DISPLAY MODE: Advanced
RESTRICTIONS: None
The displayed value is the highest Ground Fault Current since the last reset. If the
displayed value is “O.L.”, a value greater than the maximum range was recorded.
To reset the displayed value press [RESET]. To reset with all statistics use RESET
STATISTICS function.
MESSAGE NO:
M2-10
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 1000 MWh
DISPLAY MODE: Advanced
RESTRICTIONS: None
The displayed value is the energy used in the last day. Energy is calculated from
the Heater Current times the Heater Voltage integrated over time. This value is
automatically updated once every 24 hours. It cannot be reset.
MAX HEATER CURRENT
4.7A
&
A: MAX HEATER CURRENT
4.7A
&
B: MAX HEATER CURRENT
4.7A
&
C: MAX HEATER CURRENT
4.6A
&
MAX GROUND FAULT
CURRENT: 6mA
&
ENERGY USED LAST
DAY: 2.1kWh
&
Summary of Contents for MASTERTRACE
Page 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Page 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Page 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Page 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Page 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Page 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Page 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Page 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...