A.4
MASTER
TRACE
Appendix A Display Message
Details - Setpoints
MESSAGE NO:
S1-15
APPLIES TO:
Selected Heater
DEFAULT VALUE: off
VALUE RANGE: 0.5 to 100.0 A, off
DISPLAY MODE: Advanced
RESTRICTIONS: Single-Phase Modules
This function sets the High Current Trip setpoint. It must be greater than the Low
Current Alarm and the High Current Alarm setpoints. To disable this trip function
set the value to “off”. When the Heater Current is greater than or equal to this
setpoint, the heater circuit is opened, a High Current Trip Alarm is activated and a
“HIGH CURRENT TRIP” message is added to the System Status messages. This
is a latching alarm. When the cause of the alarm has been corrected, locate the
alarm message in the Status Menu and press [RESET]. The value range is in 0.5 A
increments. The maximum value for internal switching Control Modules is 30 A.
MESSAGE NO:
S1-16
APPLIES TO:
Selected Heater
DEFAULT VALUE: off
VALUE RANGE:
0.5 to 100.0 A, off
DISPLAY MODE: Advanced
RESTRICTIONS: Three-Phase Modules
This function sets the phase “A” High Current Trip setpoint. It must be greater
than the Low Current-A Alarm and the High Current-A Alarm setpoints. To
disable this trip function set the value to “off”. When the Heater Current-A is
greater than or equal to this setpoint, the heater circuit is opened, a High Current-A
Trip Alarm is activated and a “HIGH CURRENT-A TRIP” message is added to the
System Status messages. This is a latching alarm. When the cause of the alarm has
been corrected, locate the alarm message in the Status Menu and press [RESET].
The value range is in 0.5 A increments.
MESSAGE NO:
S1-17
APPLIES TO:
Selected Heater
DEFAULT VALUE: off
VALUE RANGE:
0.5 to 100.0 A, off
DISPLAY MODE: Advanced
RESTRICTIONS: Three-Phase Modules
This function sets the phase “B” High Current Trip setpoint. It must be greater
than the Low Current-B Alarm and the High Current-B Alarm setpoints. To
disable this trip function set the value to “off”. When the Heater Current-B is
greater than or equal to this setpoint, the heater circuit is opened, a High Current-B
Trip Alarm is activated and a “HIGH CURRENT-B TRIP” message is added to the
System Status messages. This is a latching alarm. When the cause of the alarm has
been corrected, locate the alarm message in the Status Menu and press [RESET].
The value range is in 0.5 A increments.
MESSAGE NO:
S1-18
APPLIES TO:
Selected Heater
DEFAULT VALUE: off
VALUE RANGE: 0.5 to 100.0 A, off
DISPLAY MODE: Advanced
RESTRICTIONS: Three-Phase Modules Only
This function sets the phase “C” High Current Trip setpoint. It must be greater
than the Low Current-C Alarm and the High Current-C Alarm setpoints. To
disable this trip function set the value to “off”. When the Heater Current-C is
greater than or equal to this setpoint, the heater circuit is opened, a High Current-C
Trip Alarm is activated and a “HIGH CURRENT-C TRIP” message is added to the
System Status messages. This is a latching alarm. When the cause of the alarm has
been corrected, locate the alarm message in the Status Menu and press
[RESET].The value range is in 0.5 A increments.
HIGH CURRENT
TRIP: off
?
A: HIGH CURRENT
TRIP: off
?
B: HIGH CURRENT
TRIP: off
?
C: HIGH CURRENT
TRIP: off
?
Summary of Contents for MASTERTRACE
Page 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Page 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Page 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Page 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Page 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Page 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Page 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Page 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...