MASTERTRACE
Appendix G MR100 for Windows CE
G.9
To perform one of the 3 Module Commissioning/Addressing operations, one must follow these
procedures:
(1) Select the desired operation using the Option drop-down edit box.
(2) If the operation is Set Module Number, select the desired module number using the Module
Number drop-down edit box.
(3) Click on the Start command button.
(4) Start the operation by clicking on the Yes button on the pop-up Confirmation Box.
(5) It takes about 15 seconds for the target control module to accomplish the operation. During this
period, the word “Start” on the Start button will be changed to “Wait ...”
(6) If the operation is successful, word "Done!" will appear on the Start button for a while.
Otherwise, word "Failed!" will appear. For a successful Read Module Number operation, the module
number read from the target control module will appear on the Module Number edit box.
(7) In the end, word "Start" will re-appear and a new operation can be started.
Note
Upon completion of a Module Commissioning/Addressing operation, the target control module
must get out of its listening new address mode. This can be realized by setting the target control
module’s ADRESS dip switch to Disable position.
11. Change Password
Password, if there is one, is required if you want to change Program Enable in System Setup
Function Page. The default password is “no password” after the MR100 is newly installed, which means
that you don't need a password to change Program Enable.
To change the password, follow these procedures:
(1) Start the task by clicking Tools|Change Password from the System pull-up menu.
(2) If currently the MR100 has a password, a Password box will be displayed asking for the old
password. Enter the current password and click the OK button.
(3) At this moment, a Confirm box will be displayed asking if you want a password or not. If you
don't want a password, click on the “No” button and the task is accomplished. If you want a password, click
on the “Yes” button and a Password box will be displayed asking for the new password.
(4) Enter your new password using the keyboard and click on the OK button.
Summary of Contents for MASTERTRACE
Page 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Page 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Page 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Page 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Page 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Page 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Page 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Page 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...