A.12
MASTER
TRACE
Appendix A Display Message
Details - Setpoints
Configures the alarm contacts for normally open (NO) or normally closed (NC).
MECH refers to the mechanical alarm contacts on terminals 6 and 7of the Control
Module and terminals 904 and 905 of the MR100 Interface Module. SS refers to
the solid-state dc alarm contacts on terminals 4 and 5 of the Control Module and
terminals 906 and 907 of the MR100 Interface Module. In NO mode, contact
closes during alarm condition. In NC mode, contacts open during alarm
condition.
MESSAGE NO:
S3-20
APPLIES TO:
Interface Module
DEFAULT VALUE: 1
VALUE RANGE: 1-254
DISPLAY MODE: Advanced
RESTRICTIONS: ML100 Interface Module
This function changes the Module Number of the Control Module connected to
the ML100 Interface.
MESSAGE NO:
S3-21
APPLIES TO:
Address Enabled Control
Module
DEFAULT VALUE: no
VALUE RANGE:yes, no
DISPLAY MODE:
Advanced
RESTRICTIONS: MR100 Interface Module
This function resets all values of the Control Module which has been placed in
Address Enabled mode. Select “yes” to proceed. Select “yes” again to confirm.
This message asks you to confirm that the Control Module Address is “enabled”.
The Control Module Address light must be on. Press [MSSG
ò
] to proceed. Refer
Chapter 5.1.2.
MESSAGE NO:
S3-21a
APPLIES TO:
Address Enabled Control
Module
DEFAULT VALUE: None
VALUE RANGE:
None
DISPLAY MODE: Advanced
RESTRICTIONS: MR100 Interface Module
This message provides a last chance to confirm the Reset Module function. Press
[MSSG
ò
] to continue.
CONT - MSSG DOWN
ABORT - RESET
ô
SET ADDR ENABLE
ADDRESS LED ON
yes [STORE]
ARE YOU SURE?
no
?
yes [STORE]
ABOUT TO RESET
MODULE
CONT - MSSG DOWN
ABORT - RESET
ô
[MSSG
ò
]
MODULE RESET
PRESS MSSG DOWN
TO CONTINUE
ô
[MSSG
ò
]
RESET CONTROL
MODULE? no
?
SET MODULE
NUMBER: 1
?
Summary of Contents for MASTERTRACE
Page 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Page 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Page 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Page 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Page 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Page 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Page 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Page 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...