MASTER
TRACE
B.5
Appendix B Display Message
Details - Measured
MESSAGE NO:
M2-11
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 1000 MWh
DISPLAY MODE: Advanced
RESTRICTIONS: None
The displayed value is the energy used since the last reset. Energy is calculated
from the Heater Current times the Heater Voltage integrated over time. To reset use
RESET STATISTICS function.
MESSAGE NO:
M2-12
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: $0 to $1,000,000.00
DISPLAY MODE: Advanced
RESTRICTIONS: None
The displayed value is the energy cost in the last day. Energy cost is calculated
from the Energy Used times the COST PER kWh. This value is automatically
updated once every 24 hours. It cannot be reset.
MESSAGE NO:
M2-13
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: $0 to $1,000,000.00
DISPLAY MODE: Advanced
RESTRICTIONS: None
The displayed value is the energy cost since the last reset. Energy cost is calculated
from the Energy Used times the COST PER kWh. To reset use RESET
STATISTICS function.
MESSAGE NO:
M2-14
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 1,000,000 hours
DISPLAY MODE: Advanced
RESTRICTIONS: None
The displayed value is the elapsed time since last reset. To reset use RESET
STATISTICS function.
MESSAGE NO:
M2-15
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 999,999 hours
DISPLAY MODE: Advanced
RESTRICTIONS: None
The displayed value is the accumulated time that the heater circuit has been on
since the last reset. It indicates how active the heater circuit is and can be useful
for maintenance. To reset use RESET STATISTICS function.
MESSAGE NO:
M2-16
APPLIES TO:
Selected Heater
DEFAULT VALUE: N/A
VALUE RANGE: 0 to 100%
DISPLAY MODE: Advanced
RESTRICTIONS: None
The displayed value is the percentage of time that the heater circuit has been on
since the last reset. PERCENT ON TIME = HEATER ON TIME ÷ TIME SINCE
RESET x 100%. It indicates how active the heater circuit is and can be useful for
maintenance. Interpretation of this value will depend on the process but large
changes could be an indication of degradation of the heater or the insulation. To
reset use RESET STATISTICS function.
TOTAL ENERGY
USED: 42.2kWh
&
ENERGY COST LAST
DAY: $1.70
&
TOTAL ENERGY
COST: $33.92
&
TIME SINCE RESET
48 hrs
&
HEATER ON TIME
80 hrs
&
HEATER IS ON
&
17% OF THE TIME
Summary of Contents for MASTERTRACE
Page 1: ...MASTERTRACE TM OPERATOR S MANUAL HEAT TRACING CONTROL ...
Page 54: ...MASTERTRACE Chapter 7 Networking Modules 7 2 Figure 7 1 MASTERTRACE System Network ...
Page 87: ...D 2 MASTERTRACE Appendix D Typical Wiring Diagrams MS 2DXH0 MS 2DIN2 MS 5ADXH0 ...
Page 88: ...MASTERTRACE D 3 Appendix D Typical Wiring Diagrams MS 5ADIN2 MS 5ATXH0 ...
Page 89: ...D 4 MASTERTRACE Appendix D Typical Wiring Diagrams MS 10ADIN2 MS 10ADXH0 ...
Page 90: ...MASTERTRACE D 5 Appendix D Typical Wiring Diagrams MS 10ADIN2X MS 10ADIN2T ...
Page 91: ...D 6 MASTERTRACE Appendix D Typical Wiring Diagrams Driving Contactors Serial Communication 1 ...
Page 92: ...MASTERTRACE D 7 Appendix D Typical Wiring Diagrams Serial Communication 2 ...