NTI Secure Remote Power Reboot Switch
75
From the Alert Settings menu, the user can enable/disable alert messages to be sent when the IP Device is not responding and
configure when and how alert messages are sent.
Figure 89- Text Menu-IP Device Alert Settings
Alert Settings
Disable alerts
Change to “Yes” to prevent alerts from being sent when this IP Device’s status changes
Alert Delay
The alert delay is an amount of time the IP Device must be in an alert condition before an alert
is sent. This provides some protection against false alarms. The Alert Delay value can be set
for 0-999 seconds or minutes.
Notify Again Time
Enter the amount of time in seconds, minutes, or hours (1-999) before an alert message will be
repeated
Notify on Return to Normal
The user can also be notified when the IP Device’s state has returned to the normal by
changing to “Yes” for "Notify on return to normal" for a sensor.
Auto Acknowledge
Change to “Yes” to have alert notifications in the summary page return to normal state
automatically when sensor readings return to normal.
Enable Email Alerts
Change to “Yes” to have alert notifications sent via Email
Enable Syslog Alerts
Change to “Yes” to have alert notifications sent via Syslog messages
Enable SNMP traps
Change to “Yes” to have alert notifications sent via SNMP traps (v2c)
Enable SMS Alerts
Change to “Yes” to have alert notifications sent via SMS (requires GSM modem) (IPDU-S4/S8
only)
Email Subject
Enter the subject to be viewed when an email alert message is received
Press <
Tab
> to highlight
Save
and press <
Enter
> to save before pressing <
Esc
> to exit.