60
8. 2
M2M API Protocol – Modbus/ TCP
Available only in PowerCable MODBUS 101x
Fi gur e 41 –Modbus/ TCP pr ot ocol conf i gur at i on
Enable Modbus/ T CP
Enables M2M Modbus/ TCP f unct ions in t he syst em kernel.
Port
Specif ic port f or Modbus/ TCP only, range 1 – 65535. The device alert s
you if you specif y a port number t hat is already occupied. However, t o
be sure, we recommend using port numbers above 1024.
Last access IP
Read-only value indicat ing t he IP address f rom which t he last
Modbus/ TCP command was received. The “ Ref resh” but t on updat es t his
value.
Enable IP f ilt er
To improve securit y, t he IP f ilt er can be used t o specif y a range of IP
addresses f rom which Modbus/ TCP commands are accept ed. Commands
f rom addresses out side of t his range will be ignored.
Save Changes
Saves t he changes.
Function Register Value Description
0x01 101 0/1 1st output state