Universal Wall-Mount Controller 

BACnet Communication Module User Guide

 

 

www.neptronic.com

 

Page | 20 

 

ID 

Name 

Description 

W? 

Notes 

(10) 

Ch Ov Contact Norm Heat

: Cooling mode activates when the contact is closed and heating 

mode activates when the contact is opened. 
(11) 

Occupancy

: Controller activates the Occupancy mode. 

(12) 

Night Set Back

: Controller activates the night set back mode. 

MSV.47  Cfg_BinaryInput2Type 

See MSV.46 

 

 

MSV.55  Cfg_AnalogOutput1Ramp 

Configuration of the ramp used to modulate AO1 based on demand. 
(1) 

OFF

: The controller does not use the output. 

(2) 

Change Over With Fan

: The controller modulates heating and cooling, as appropriate. 

(3) 

Cooling1With Fan

: This ramp is used for cooling. The controller performs cooling based on 

the cooling proportional, integral, and dead band values. 
(4) 

Cooling2With Fan

: This ramp is used for cooling. The controller performs cooling based on 

the cooling proportional, integral, and dead band values. 
(5) 

Heating1With Fan

: This ramp is used for heating. The controller performs heating based on 

the heating proportional, integral, and dead band values. 
(6) 

Heating2With Fan

: This ramp is used for heating. The controller performs heating based on 

the heating proportional, integral, and dead band values. 
(7) 

Heating2

: This ramp is used for heating. The controller performs heating based on the heating 

proportional, integral, and dead band values. 
(8) 

Cooling1Heating1With Fan

: The controller performs cooling regularly. If another output is set 

to heat, it performs heating regularly. 
(9) 

Humidify With Fan

: The controller modulates the output based on the humidify demand. 

(10) 

CO2Alarm

: Carbon dioxide (CO2) alarm. The controller activates or deactivates the output 

based on carbon dioxide levels. 

Present Value 

1 = OFF 
2 = Change Over With Fan 
3 = Cooling1With Fan 
4 = Cooling2With Fan 
5 = Heating1With Fan 
6 = Heating2With Fan 
7 = Heating2 
8 = Cooling1Heating1With Fan 
9 = Humidify With Fan 
10 = CO2Alarm 
 

MSV.57  Cfg_AnalogOutput2Ramp 

See MSV.55 
If BV.95 Cfg_HeatPumpOption is set to Off, AO2 has an additional option: 
(11) Fan: The controller modulates the output according to AV. 60 Fan Demand. 

Present Value 

 

MSV.70  Cfg_BinaryOutput1Ramp 

Configuration of the ramp used to modulate BO1 based on demand. The ramp is fixed if BV.95 
Cfg_HeatPumpOption is set to On. 
(1) 

OFF

: The controller does not use the output. 

(2) 

Change Over With Fan

: The controller modulates heating and cooling, as appropriate. 

(3) 

Cooling1With Fan

: This ramp is used for cooling. The controller performs cooling based on 

the cooling proportional, integral, and dead band values. 
(4) 

Cooling2With Fan

: This ramp is used for cooling. The controller performs cooling based on 

the cooling proportional, integral, and dead band values. 
(5) 

Heating1With Fan

: This ramp is used for heating. The controller performs heating based on 

the heating proportional, integral, and dead band values. 
(6) 

Heating2With Fan

: This ramp is used for heating. The controller performs heating based on 

the heating proportional, integral, and dead band values. 
(7) 

Heating2

: This ramp is used for heating. The controller performs heating based on the heating 

proportional, integral, and dead band values. 
(8) 

Cooling1Heating1With Fan

: The controller performs cooling regularly. If another output is set 

to heat, it performs heating regularly. 
(9) 

Humidify With Fan

: The controller modulates the output based on the humidify demand. 

(10) 

CO2Alarm

: Carbon dioxide (CO2) alarm. The controller activates or deactivates the output 

based on carbon dioxide levels. 

Present Value 

1 = OFF 
2 = Change Over With Fan 
3 = Cooling1With Fan 
4 = Cooling2With Fan 
5 = Heating1With Fan 
6 = Heating2With Fan 
7 = Heating2 
8 = Cooling1Heating1With Fan 
9 = Humidify With Fan 
10 = CO2Alarm 

Summary of Contents for TUCB24C6X2

Page 1: ...versal Wall Mount Controller TUCB TUHB Series BACnet Communication Module User Guide TUCB24C6X2 with Internal Temperature Sensor 6 binary 2 analog outputs TUHB24C6X2 with Internal Temperature and Humi...

Page 2: ...guration 2 Configuration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Copy Config 4 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7...

Page 3: ...nutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to the device...

Page 4: ...ually through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its d...

Page 5: ...t guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing u...

Page 6: ...iguration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for 5...

Page 7: ...Object Name and or device ID change Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 0...

Page 8: ...Property section on page 7 for more information Object will automatically return to Normal after a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Ob...

Page 9: ...5 Out_of_Service property is not writable for MSV Program Description Reliability Program_Change Only LOAD and RESTART are supported for Program Change Use LOAD to apply the new firmware File Descript...

Page 10: ...o Units 0 Open 1 Close AI 2 AnalogInput2 Sensor reading value on analog input 2 Out of Service Cov Increment If a 10k type III sensor is used displays 0V Fault and Out of Service Status Flags are True...

Page 11: ...ocked to prevent the user from changing the setpoint BV 2 This object is commandable relinquish default will be saved to non volatile memory Present Value Relinquish_Default Cov Increment 50 F to 104...

Page 12: ...value must be bigger Present Value Cov Increment 0 to 250 seconds Resolution 5 seconds AV 46 Cfg_CoolingAntiCycleDelay Configuration value in mins to prevent the cooling outputs to cycle on and off Th...

Page 13: ...AV 81 Cfg_HumDeadBand Configuration value that represents the range at which the controller will not take action when below or above the humidity setpoint Present Value Cov Increment 0 RH to 5 RH Res...

Page 14: ...f demand at which the contact closes to energize the controlled element Present Value Cov Increment 15 to 80 Resolution 1 AV 116 Cfg_BinaryOutput1OpenPos Configuration value that indicates the percent...

Page 15: ...15 minutes Resolution 1 minute AV 165 CopyCfgStartAddress Represents the first address in the range of copied controllers while using the Copy Config option Present Value Cov Increment 0 to 254 Resol...

Page 16: ...t4 Contact status of the output 0 Open 1 Close Present Value 0 Open 1 Close BO 5 BinaryOutput5 Contact status of the output 0 Open 1 Close Present Value 0 Open 1 Close BO 6 BinaryOutput6 Contact statu...

Page 17: ...er internal or external Only available on model TUHB24C6X2 Present Value 0 Intern Sensor 1 Extern Sensor BV 26 Cfg_HumSetPointLock Configuration value to prevent the user from changing the relative hu...

Page 18: ...ed When set to 1 Reverse the contact is considered Normally Closed Present Value 0 Direct 1 Reverse BV 61 Cfg_BinaryOutput2Direction See BV 60 Present Value 0 Direct 1 Reverse BV 62 Cfg_BinaryOutput3D...

Page 19: ...at BV 3 BV 21 BV 98 and MSV 20 Auto Controller mode changes automatically between heating and cooling in operation when there is a cooling or heating demand Heating Controller is in heating in operat...

Page 20: ...s in night setback mode 3 Override Zone is in night setback mode but put back to day operation for a maximum pre determined time set at AV 85 Read Only 1 Day 2 Night 3 Override MSV 20 Cfg_Sequence Sel...

Page 21: ...lter Controller activates an alarm to indicate that the filter is dirty 15 Flow Switch Controller activates an alarm to indicate that there is no airflow 16 Overheat Controller activates an alarm to i...

Page 22: ...e 1 OFF 2 Change Over With Fan 3 Cooling1With Fan 4 Cooling2With Fan 5 Heating1With Fan 6 Heating2With Fan 7 Heating2 8 Cooling1Heating1With Fan 9 Humidify With Fan 10 CO2Alarm MSV 57 Cfg_AnalogOutput...

Page 23: ...demand 2 Display Setpoint Demand TUxB will display the actual setpoint and cooling heating demand 3 Display Temp TUxB will display the actual temp but no demand 4 Display Setpoint TUxB will display t...

Page 24: ...beau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm E...

Reviews: