Universal Wall-Mount Controller
BACnet Communication Module User Guide
www.neptronic.com
Page | 20
ID
Name
Description
W?
Notes
(10)
Ch Ov Contact Norm Heat
: Cooling mode activates when the contact is closed and heating
mode activates when the contact is opened.
(11)
Occupancy
: Controller activates the Occupancy mode.
(12)
Night Set Back
: Controller activates the night set back mode.
MSV.47 Cfg_BinaryInput2Type
See MSV.46
MSV.55 Cfg_AnalogOutput1Ramp
Configuration of the ramp used to modulate AO1 based on demand.
(1)
OFF
: The controller does not use the output.
(2)
Change Over With Fan
: The controller modulates heating and cooling, as appropriate.
(3)
Cooling1With Fan
: This ramp is used for cooling. The controller performs cooling based on
the cooling proportional, integral, and dead band values.
(4)
Cooling2With Fan
: This ramp is used for cooling. The controller performs cooling based on
the cooling proportional, integral, and dead band values.
(5)
Heating1With Fan
: This ramp is used for heating. The controller performs heating based on
the heating proportional, integral, and dead band values.
(6)
Heating2With Fan
: This ramp is used for heating. The controller performs heating based on
the heating proportional, integral, and dead band values.
(7)
Heating2
: This ramp is used for heating. The controller performs heating based on the heating
proportional, integral, and dead band values.
(8)
Cooling1Heating1With Fan
: The controller performs cooling regularly. If another output is set
to heat, it performs heating regularly.
(9)
Humidify With Fan
: The controller modulates the output based on the humidify demand.
(10)
CO2Alarm
: Carbon dioxide (CO2) alarm. The controller activates or deactivates the output
based on carbon dioxide levels.
Present Value
1 = OFF
2 = Change Over With Fan
3 = Cooling1With Fan
4 = Cooling2With Fan
5 = Heating1With Fan
6 = Heating2With Fan
7 = Heating2
8 = Cooling1Heating1With Fan
9 = Humidify With Fan
10 = CO2Alarm
MSV.57 Cfg_AnalogOutput2Ramp
See MSV.55
If BV.95 Cfg_HeatPumpOption is set to Off, AO2 has an additional option:
(11) Fan: The controller modulates the output according to AV. 60 Fan Demand.
Present Value
MSV.70 Cfg_BinaryOutput1Ramp
Configuration of the ramp used to modulate BO1 based on demand. The ramp is fixed if BV.95
Cfg_HeatPumpOption is set to On.
(1)
OFF
: The controller does not use the output.
(2)
Change Over With Fan
: The controller modulates heating and cooling, as appropriate.
(3)
Cooling1With Fan
: This ramp is used for cooling. The controller performs cooling based on
the cooling proportional, integral, and dead band values.
(4)
Cooling2With Fan
: This ramp is used for cooling. The controller performs cooling based on
the cooling proportional, integral, and dead band values.
(5)
Heating1With Fan
: This ramp is used for heating. The controller performs heating based on
the heating proportional, integral, and dead band values.
(6)
Heating2With Fan
: This ramp is used for heating. The controller performs heating based on
the heating proportional, integral, and dead band values.
(7)
Heating2
: This ramp is used for heating. The controller performs heating based on the heating
proportional, integral, and dead band values.
(8)
Cooling1Heating1With Fan
: The controller performs cooling regularly. If another output is set
to heat, it performs heating regularly.
(9)
Humidify With Fan
: The controller modulates the output based on the humidify demand.
(10)
CO2Alarm
: Carbon dioxide (CO2) alarm. The controller activates or deactivates the output
based on carbon dioxide levels.
Present Value
1 = OFF
2 = Change Over With Fan
3 = Cooling1With Fan
4 = Cooling2With Fan
5 = Heating1With Fan
6 = Heating2With Fan
7 = Heating2
8 = Cooling1Heating1With Fan
9 = Humidify With Fan
10 = CO2Alarm