Universal Wall-Mount Controller
BACnet Communication Module User Guide
www.neptronic.com
Page | 19
ID
Name
Description
W?
Notes
MSV.28 Cfg_FanModeDoorOpened
Configuration value to set the fan speed mode when the door is open.
(1)
Low
: Fan is limited to low speed.
(2)
Medium
: Fan is limited to medium speed.
(3)
High
: Fan is limited to high speed.
(4)
Auto
: Fan automatically changes speed, based on demand.
Present Value
1= Low
2= Medium
3= High
4 = Auto
MSV.35 Cfg_AnalogInput1Type
Configuration value to select the input signal type for Analog Input 1 (AI1).
(1)
OFF
: Controller does not use the input.
(2)
Extern Sensor 10k
: Controller uses a 10kΩ type III external temperature sensor.
(3)
Change Over Sensor
: Heating mode activates when the temperature read by the external
sensor is above the Changeover Setpoint and cooling mode activates when the temperature read
by the external sensor is below the Changeover Setpoint.
(4)
Ch Ov Contact Norm Cool
: Heating mode activates when the contact is closed and cooling
mode activates when the contact is opened.
(5)
Ch Ov Contact Norm Heat
: Cooling mode activates when the contact is closed and heating
mode activates when the contact is opened.
(6)
Outside Air Sensor
: Controller uses a 10kΩ type III outside air sensor.
(7)
Extern Sensor0_10V
: Controller uses a 0 to 10 Vdc external temperature sensor.
(8)
CO2_0_10V
: Controller uses a 0 to 10 Vdc CO2 sensor.
(9)
Occupancy
: Controller activates the Occupancy mode.
(10)
Night Set Back
: Controller activates the night set back mode.
(11)
Override
: Controller activates an alarm to indicate that there has been an override and the
controller is forced into OFF mode.
(12)
Window
: Controller activates an alarm to indicate that the window is open.
(13)
Door
: Controller activates an alarm to indicate that the door is open.
(14)
Dirty Filter
: Controller activates an alarm to indicate that the filter is dirty.
(15)
Flow Switch
: Controller activates an alarm to indicate that there is no airflow.
(16)
Overheat
: Controller activates an alarm to indicate that the heating equipment has
overheated. The controller shuts off the heating outputs.
(17)
Selector Switch
: Controller activates the Local mode. The controller shuts off fan outputs.
(18)
Humidity Sensor0_10V
: Controller modulates the output based on the humidify demand.
Present Value
1 = OFF
2 = Extern Sensor 10k
3 = Change Over Sensor
4 = Ch Ov Contact Norm Cool
5 = Ch Ov Contact Norm Heat
6 = Outside Air Sensor
7 = Extern Sensor0_10V
8 = CO2_0_10V
9 = Occupancy
10 = Night Set Back
11 = Override
12 = Window
13 = Door
14 = Dirty Filter
15 = Flow Switch
16 = Overheat
17 = Selector Switch
18 = Humidity Sensor0_10V
MSV.36 Cfg_AnalogInput2Type
See MSV.35
MSV.46 Cfg_BinaryInput1Type
Configuration value to select the input signal type for Binary Input 1 (BI1).
(1)
OFF
: Controller does not use the input
(2)
Override
: Controller activates an alarm to indicate that there has been an override and the
controller is forced into OFF mode.
(3)
Window
: Controller activates an alarm to indicate that the window is open.
(4)
Door
: Controller activates an alarm to indicate that the door is open.
(5)
Dirty Filter
: Controller activates an alarm to indicate that the filter is dirty.
(6)
Flow Switch
: Controller activates an alarm to indicate that there is no airflow.
(7)
Overheat
: Controller activates an alarm to indicate that the heating equipment has overheated.
The controller shuts off the heating outputs.
(8)
Selector Switch
: Controller activates the Local mode. The controller shuts off fan outputs.
(9)
Ch Ov Contact Norm Cool
: Heating mode activates when the contact is closed and cooling
mode activates when the contact is opened.
Present Value
(1) = OFF
(2) = Override
(3) = Window
(4) = Door
(5) = Dirty Filter
(6) = Flow Switch
(7) = Overheat
(8) = Selector Switch
(9) = Ch Ov Contact Norm Cool
(10) = Ch Ov Contact Norm Heat
(11) = Occupancy
(12) = Night Set Back