Universal Wall-Mount Controller 

BACnet Communication Module User Guide

 

 

www.neptronic.com

 

Page | 9 

 

Analog Value (AV) 

Table 6 - Object Table Information: Analog Value (AV) 

ID 

Name 

Description 

W? 

Notes 

AV.1  ControlTemp 

Temperature value that is used to calculate demand. This object is commandable. The relinquish 
default value will be equal to the Setpoint (AV.9) if MSV.21 is set to 

Network

. Otherwise, it will be 

equal to the internal or external temperature depending on MSV.21 setting. 

Present Value 

Cov Increment 

-40°F to 212°F or -40°C to 100°C 
Resolution 0.02ºF/0.01ºC 

AV.2

 

Cfg_NetworkTimeOut 

Configuration time value. If MSV.21 is set to 

Network

 and no value has been sent via BMS for 

more than AV.2 time, the controller goes to 

OFF

 mode. AV.1 displays 999°C and object in Fault. If 

time is set to 

0

 mins, AV.1 is reset to AV.9 value.

 

Present Value 

Cov Increment

 

0 to 60 Minutes, Resolution 1 minute

 

AV.3

 

ExternTemp 

Status of the extern temperature sensor (ETS). This temperature is the value read by the external 
temperature sensor when MSV.35 or MSV.36 is set to t10.0 or t10.V. 

 

Out of Service 

Cov Increment

 

-40°F to 212°F or -40°C to 100°C 
Resolution 0.02°F/0.01°C 

AV.4

 

ChangeOverTemp 

Status of the changeover temperature sensor (SENs). This is the value read by the changeover 
sensor when MSV.35 or MSV.36 is set to Changeover Sensor.

 

Out of Service 

Cov Increment

 

-40°F to 212°F or -40°C to 100°C 
Resolution 0.02°F/0.01°C

 

AV.5

 

Cfg_InternTempOffset 

Configuration value used to calibrate the integrated temp sensor of the controller (ITS).

 

Present Value 

Cov Increment

 

±9°F/±5°C, Resolution 0.2ºF/0.1ºC

 

AV.6

 

Cfg_ExternTempOffset 

Configuration value used to calibrate the external temp sensor (ETS).

 

Present Value 

Cov Increment

 

±9°F/±5°C, Resolution 0.2ºF/0.1ºC

 

AV.7

 

Cfg_ExternTempMin 

Configuration value that represents the minimum temp read by the sensor (minimum range value).

Present Value 

Cov Increment

 

-40ºF to 32ºF or -40ºC to 0ºC 
 Resolution 1ºF/0.5ºC

 

AV.8

 

Cfg_ExternTempMax 

Configuration value that represents the maximum temp read by the sensor (maximum range 
value).

 

Present Value 

Cov Increment

 

122°F to 212°F or 50°C to 100°C 
 Resolution 1ºF/0.5ºC

 

AV.9

 

TempSetPoint 

Configuration value used to set the actual user setpoint of the zone in occupied/day operation 
mode. This value may be locked to prevent the user from changing the setpoint (BV.2). This object 
is commandable, relinquish default will be saved to non-volatile memory.

 

Present Value 

Relinquish_Default

Cov Increment

 

50°F to 104°F or 10°C to 40°C (AV.10 to AV.11) 
Resolution 1ºF/0.5ºC

 

AV.10

 

Cfg_MinSetPoint 

Configuration value used to set the minimum temp setpoint of the zone in occupied/day operation 
mode, allowed by the user.

 

Present Value 

Cov Increment

 

50ºF to 104ºF or 10ºC to 40ºC (50ºF/10ºC to AV.11) 
Resolution 1ºF/0.5ºC

 

AV.11

 

Cfg_MaxSetPoint 

Configuration value used to set the maximum temp setpoint of the zone in occupied/day operation 
mode, allowed by the user.

 

Present Value 

Cov Increment

 

50ºF to 104ºF or 10ºC to 40ºC (AV.10 to 104ºF or 
40ºC), Resolution 1ºF/0.5ºC

 

AV.12

 

SetPointCoolNoOccNSB 

Configuration value of the cooling setpoint when in night setback or unoccupied mode. Set BV.35 
value to setpoint for the value to be active.

 

Present Value 

Cov Increment

 

50ºF to 104ºF or 10ºC to 40ºC (AV.13 to 104ºF or 
40ºC), Resolution 1ºF/0.5ºC

 

AV.13

 

SetPointHeatNoOccNSB 

Configuration value of the heating setpoint when in night setback or unoccupied mode. Set BV.35 
value to setpoint for the value to be active.

 

Present Value 

Cov Increment

 

50ºF to 104ºF or 10ºC to 40ºC (50ºF/10ºC to AV.12) 
Resolution 1ºF/0.5ºC

 

AV.20

 

Heating1Demand 

Status value that represents the heating demand for the Heating Ramp 1. This value is based on 
zone temp, zone setpoint and values set for the actual ramp.

 

Cov Increment

 

0 to 100%, Resolution 0.5%

 

AV.21

 

Cfg_Heating1PropBand 

Configuration value that represents the range through which the controller will modulate the 
heating output from 0 to 100% for Heating Ramp 1.

 

Present Value 

Cov Increment

 

1ºF to 9ºF or 0.5ºC to 5.0ºC 
 Resolution 1ºF/0.5ºC

 

AV.22

 

Cfg_Heating1DeadBand 

Configuration value that represents the range at which the controller will not take action when 
temp is below the zone setpoint for Heating Ramp 1.

 

Present Value 

Cov Increment

 

0ºF to 9ºF or 0.0ºC to 5.0ºC 
 Resolution 0.2ºF/0.1ºC

 

AV.24

 

Heating2Demand 

Status value that represents the heating demand for the Heating Ramp 2. This value is based on 
zone temp, zone setpoint and values set for the actual ramp.

 

Cov Increment

 

0 to 100%, Resolution 0.5%

 

AV.25

 

Cfg_Heating2PropBand 

Configuration value that represents the range through which the controller will modulate the 
heating output from 0 to 100% for Heating Ramp 2.

 

Present Value 

Cov Increment

 

1ºF to 9ºF or 0.5ºC to 5.0ºC 
 Resolution 1ºF/0.5ºC

 

Summary of Contents for TUCB24C6X2

Page 1: ...versal Wall Mount Controller TUCB TUHB Series BACnet Communication Module User Guide TUCB24C6X2 with Internal Temperature Sensor 6 binary 2 analog outputs TUHB24C6X2 with Internal Temperature and Humi...

Page 2: ...guration 2 Configuration Options 3 Quick Setup 3 Manual Setup 3 MAC Address and Max_Master 3 Copy Config 4 Network Reset 4 Device Object Properties 5 Object Types Supported 6 Out of Service Property 7...

Page 3: ...nutes to ensure a Tusage_timeout value within 20 minutes MS TP Support The controller supports a Full Master Node state machine for MS TP The Max_Master and the instances are configured to the device...

Page 4: ...ually through the WriteProperty service to Device Object Object_Identifier The device s Object_Identifier is a combination of the Device Object_Type 8 and the Device_Instance 0 4194302 therefore its d...

Page 5: ...t guarantee efficient operation of the controller and other MS TP units on the MS TP network Some MAC address and Max_Master combinations are more efficient than others BACnet requires token passing u...

Page 6: ...iguration of a controller over the network to controllers of the same type using the Copy Config feature 1 Access Operation Mode jumper set to RUN position 2 Press and hold both function buttons for 5...

Page 7: ...Object Name and or device ID change Max_APDU_Length_Accepted Always 480 Segmentation_Supported 3 No Segmentation APDU_Timeout 6000 W Number_of_APDU_Retries Always 3 Local_Time 00 00 00 W Local_Date 0...

Page 8: ...Property section on page 7 for more information Object will automatically return to Normal after a programmable period of time Refer to Proprietary property 1002 of Device Object in Table 2 Device Ob...

Page 9: ...5 Out_of_Service property is not writable for MSV Program Description Reliability Program_Change Only LOAD and RESTART are supported for Program Change Use LOAD to apply the new firmware File Descript...

Page 10: ...o Units 0 Open 1 Close AI 2 AnalogInput2 Sensor reading value on analog input 2 Out of Service Cov Increment If a 10k type III sensor is used displays 0V Fault and Out of Service Status Flags are True...

Page 11: ...ocked to prevent the user from changing the setpoint BV 2 This object is commandable relinquish default will be saved to non volatile memory Present Value Relinquish_Default Cov Increment 50 F to 104...

Page 12: ...value must be bigger Present Value Cov Increment 0 to 250 seconds Resolution 5 seconds AV 46 Cfg_CoolingAntiCycleDelay Configuration value in mins to prevent the cooling outputs to cycle on and off Th...

Page 13: ...AV 81 Cfg_HumDeadBand Configuration value that represents the range at which the controller will not take action when below or above the humidity setpoint Present Value Cov Increment 0 RH to 5 RH Res...

Page 14: ...f demand at which the contact closes to energize the controlled element Present Value Cov Increment 15 to 80 Resolution 1 AV 116 Cfg_BinaryOutput1OpenPos Configuration value that indicates the percent...

Page 15: ...15 minutes Resolution 1 minute AV 165 CopyCfgStartAddress Represents the first address in the range of copied controllers while using the Copy Config option Present Value Cov Increment 0 to 254 Resol...

Page 16: ...t4 Contact status of the output 0 Open 1 Close Present Value 0 Open 1 Close BO 5 BinaryOutput5 Contact status of the output 0 Open 1 Close Present Value 0 Open 1 Close BO 6 BinaryOutput6 Contact statu...

Page 17: ...er internal or external Only available on model TUHB24C6X2 Present Value 0 Intern Sensor 1 Extern Sensor BV 26 Cfg_HumSetPointLock Configuration value to prevent the user from changing the relative hu...

Page 18: ...ed When set to 1 Reverse the contact is considered Normally Closed Present Value 0 Direct 1 Reverse BV 61 Cfg_BinaryOutput2Direction See BV 60 Present Value 0 Direct 1 Reverse BV 62 Cfg_BinaryOutput3D...

Page 19: ...at BV 3 BV 21 BV 98 and MSV 20 Auto Controller mode changes automatically between heating and cooling in operation when there is a cooling or heating demand Heating Controller is in heating in operat...

Page 20: ...s in night setback mode 3 Override Zone is in night setback mode but put back to day operation for a maximum pre determined time set at AV 85 Read Only 1 Day 2 Night 3 Override MSV 20 Cfg_Sequence Sel...

Page 21: ...lter Controller activates an alarm to indicate that the filter is dirty 15 Flow Switch Controller activates an alarm to indicate that there is no airflow 16 Overheat Controller activates an alarm to i...

Page 22: ...e 1 OFF 2 Change Over With Fan 3 Cooling1With Fan 4 Cooling2With Fan 5 Heating1With Fan 6 Heating2With Fan 7 Heating2 8 Cooling1Heating1With Fan 9 Humidify With Fan 10 CO2Alarm MSV 57 Cfg_AnalogOutput...

Page 23: ...demand 2 Display Setpoint Demand TUxB will display the actual setpoint and cooling heating demand 3 Display Temp TUxB will display the actual temp but no demand 4 Display Setpoint TUxB will display t...

Page 24: ...beau blvd Montreal Qc H4N 1R6 Canada www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service fax 514 333 1091 Monday to Friday 8 00am to 5 00pm E...

Reviews: