Universal Wall-Mount Controller
BACnet Communication Module User Guide
www.neptronic.com
Page | 9
Analog Value (AV)
Table 6 - Object Table Information: Analog Value (AV)
ID
Name
Description
W?
Notes
AV.1 ControlTemp
Temperature value that is used to calculate demand. This object is commandable. The relinquish
default value will be equal to the Setpoint (AV.9) if MSV.21 is set to
Network
. Otherwise, it will be
equal to the internal or external temperature depending on MSV.21 setting.
Present Value
Cov Increment
-40°F to 212°F or -40°C to 100°C
Resolution 0.02ºF/0.01ºC
AV.2
Cfg_NetworkTimeOut
Configuration time value. If MSV.21 is set to
Network
and no value has been sent via BMS for
more than AV.2 time, the controller goes to
OFF
mode. AV.1 displays 999°C and object in Fault. If
time is set to
0
mins, AV.1 is reset to AV.9 value.
Present Value
Cov Increment
0 to 60 Minutes, Resolution 1 minute
AV.3
ExternTemp
Status of the extern temperature sensor (ETS). This temperature is the value read by the external
temperature sensor when MSV.35 or MSV.36 is set to t10.0 or t10.V.
Out of Service
Cov Increment
-40°F to 212°F or -40°C to 100°C
Resolution 0.02°F/0.01°C
AV.4
ChangeOverTemp
Status of the changeover temperature sensor (SENs). This is the value read by the changeover
sensor when MSV.35 or MSV.36 is set to Changeover Sensor.
Out of Service
Cov Increment
-40°F to 212°F or -40°C to 100°C
Resolution 0.02°F/0.01°C
AV.5
Cfg_InternTempOffset
Configuration value used to calibrate the integrated temp sensor of the controller (ITS).
Present Value
Cov Increment
±9°F/±5°C, Resolution 0.2ºF/0.1ºC
AV.6
Cfg_ExternTempOffset
Configuration value used to calibrate the external temp sensor (ETS).
Present Value
Cov Increment
±9°F/±5°C, Resolution 0.2ºF/0.1ºC
AV.7
Cfg_ExternTempMin
Configuration value that represents the minimum temp read by the sensor (minimum range value).
Present Value
Cov Increment
-40ºF to 32ºF or -40ºC to 0ºC
Resolution 1ºF/0.5ºC
AV.8
Cfg_ExternTempMax
Configuration value that represents the maximum temp read by the sensor (maximum range
value).
Present Value
Cov Increment
122°F to 212°F or 50°C to 100°C
Resolution 1ºF/0.5ºC
AV.9
TempSetPoint
Configuration value used to set the actual user setpoint of the zone in occupied/day operation
mode. This value may be locked to prevent the user from changing the setpoint (BV.2). This object
is commandable, relinquish default will be saved to non-volatile memory.
Present Value
Relinquish_Default
Cov Increment
50°F to 104°F or 10°C to 40°C (AV.10 to AV.11)
Resolution 1ºF/0.5ºC
AV.10
Cfg_MinSetPoint
Configuration value used to set the minimum temp setpoint of the zone in occupied/day operation
mode, allowed by the user.
Present Value
Cov Increment
50ºF to 104ºF or 10ºC to 40ºC (50ºF/10ºC to AV.11)
Resolution 1ºF/0.5ºC
AV.11
Cfg_MaxSetPoint
Configuration value used to set the maximum temp setpoint of the zone in occupied/day operation
mode, allowed by the user.
Present Value
Cov Increment
50ºF to 104ºF or 10ºC to 40ºC (AV.10 to 104ºF or
40ºC), Resolution 1ºF/0.5ºC
AV.12
SetPointCoolNoOccNSB
Configuration value of the cooling setpoint when in night setback or unoccupied mode. Set BV.35
value to setpoint for the value to be active.
Present Value
Cov Increment
50ºF to 104ºF or 10ºC to 40ºC (AV.13 to 104ºF or
40ºC), Resolution 1ºF/0.5ºC
AV.13
SetPointHeatNoOccNSB
Configuration value of the heating setpoint when in night setback or unoccupied mode. Set BV.35
value to setpoint for the value to be active.
Present Value
Cov Increment
50ºF to 104ºF or 10ºC to 40ºC (50ºF/10ºC to AV.12)
Resolution 1ºF/0.5ºC
AV.20
Heating1Demand
Status value that represents the heating demand for the Heating Ramp 1. This value is based on
zone temp, zone setpoint and values set for the actual ramp.
Cov Increment
0 to 100%, Resolution 0.5%
AV.21
Cfg_Heating1PropBand
Configuration value that represents the range through which the controller will modulate the
heating output from 0 to 100% for Heating Ramp 1.
Present Value
Cov Increment
1ºF to 9ºF or 0.5ºC to 5.0ºC
Resolution 1ºF/0.5ºC
AV.22
Cfg_Heating1DeadBand
Configuration value that represents the range at which the controller will not take action when
temp is below the zone setpoint for Heating Ramp 1.
Present Value
Cov Increment
0ºF to 9ºF or 0.0ºC to 5.0ºC
Resolution 0.2ºF/0.1ºC
AV.24
Heating2Demand
Status value that represents the heating demand for the Heating Ramp 2. This value is based on
zone temp, zone setpoint and values set for the actual ramp.
Cov Increment
0 to 100%, Resolution 0.5%
AV.25
Cfg_Heating2PropBand
Configuration value that represents the range through which the controller will modulate the
heating output from 0 to 100% for Heating Ramp 2.
Present Value
Cov Increment
1ºF to 9ºF or 0.5ºC to 5.0ºC
Resolution 1ºF/0.5ºC