Universal Wall-Mount Controller
BACnet Communication Module User Guide
www.neptronic.com
Page | 18
ID
Name
Description
W?
Notes
MSV.10 Cfg_ChangeOverControlMode
Configuration that indicates the source of the changeover value.
(1)
Locally
: Analog or binary input is configured in the TUxB and will execute the changeover with
the set parameters.
(2)
Cooling
: Changeover is sent and controlled by the BMS. No changeover will occur unless the
BMS sends the signal to do so.
(3)
Heating
: Changeover is sent and controlled by the BMS. No changeover will occur unless the
BMS sends the signal to do so.
Present Value
1= Locally
2= Cooling
3= Heating
MSV.13 NsbOccCommand
Configuration to set the occupancy or night setback mode. This object is commandable, relinquish
default will be saved to non-volatile memory.
(1)
Locally
: Occupancy or Night setback is activated via a configured input wired to a timer or an
occupancy sensor.
(2)
OFF
: Forces the TUxB Off. Signal sent via BMS.
(3)
Occupancy
: Forces the TUxB to occupied or day mode. Signal sent via BMS.
(4)
No Occupancy
: Forces the TUxB to unoccupied or night setback mode. Signal sent via BMS.
Present Value
Relinquish_Default
1 = Locally
2 = Off
3 = Occupancy/Day
4 = No Occupancy/Night
MSV.14 OccupancyStatus
Status that indicates the actual occupancy.
(1)
Unoccupied
: Zone is not occupied.
(2)
Occupied
: Zone is occupied.
(3)
Override
: Zone is unoccupied but put back to occupied mode for a maximum pre-determined
time set at AV.86.
Read Only
1 = NoOccupancy
2 = Occupancy
3 = Override
MSV.15 NightSetBackStatus
Status that indicates the actual mode of the zone.
(1)
Day
: Zone is in day operation mode.
(2)
Night
: Zone is in night setback mode.
(3)
Override
: Zone is in night setback mode but put back to day operation for a maximum pre-
determined time set at AV.85.
Read Only
1 = Day
2 = Night
3 = Override
MSV.20 Cfg_Sequence Select
Configuration value to limit available options at MSV.1.
(1)
Auto
: All modes available.
(2)
Heating
: Only Heating.
(3)
Cooling
: Only Cooling.
(4)
ON
: Heating or Cooling.
(5)
Auto Lock
: Only Auto.
Present Value
1 = Auto
2 = Heating
3 = Cooling
4 = HeatingOrCooling
5 = Auto Lock
MSV.21 Cfg_ TempControlSource
Configuration value to set the control temp to be used by the controller.
(1)
Network Sensor
: AV.1 will use temp value sent via the BMS. See AV.2 for timeout safety
feature (Net).
(2)
Intern Sensor
: AV.1 will use the integrated temp sensor of the controller (ITS).
(3)
Extern Sensor
: AV.1 will use the external temp sensor configured (ETS).
Present Value
1 = Network (Net)
2 = Internal (ItS)
3 = External (EtS)
MSV.25 Cfg_FanOperationType
Configuration value to set the number of fan speed available on the fan coil.
(1)
1 Speed
: Fan coil has a one speed fan (wired to Low).
(2)
2 Speed
: Fan coil has a two speed fan (wired to Medium).
(3)
3 Speed
: Fan coil has a three speed fan (wired to High).
Present Value
1= 1Speed
2= 2Speeds
3= 3Speeds
MSV.26 Cfg_FanModeNoOccNight
Configuration value to set the fan speed for no occupancy or night setback mode.
(1)
Low
: Fan is limited to low speed.
(2)
Medium
: Fan is limited to medium speed.
(3)
High
: Fan is limited to high speed.
(4)
Auto
: Fan automatically changes speed, based on demand.
Present Value
1= Low
2= Medium
3= High
4 = Auto
MSV.27 Cfg_FanModeWindowOpened
Configuration value to set the fan speed mode when the window is open.
(1)
Low
: Fan is limited to low speed.
(2)
Medium
: Fan is limited to medium speed.
(3)
High
: Fan is limited to high speed.
(4)
Auto
: Fan automatically changes speed, based on demand.
Present Value
1= Low
2= Medium
3= High
4 = Auto