Universal Wall-Mount Controller
BACnet Communication Module User Guide
www.neptronic.com
Page | 16
ID
Name
Description
W?
Notes
BV.45 Cfg_BinaryInput1Contact
Configuration to change the contact's normal position. Input can be set to (0) Normally Opened or
(1) Normally Closed.
Present Value 0 = Norm Open, 1 = Norm Close
BV.46 Cfg_BinaryInput2Contact
See BV.45
Present Value 0 = Norm Open, 1 = Norm Close
BV.47 Cfg_AnalogInput1Contact
See BV.45
Present Value 0 = Norm Open, 1 = Norm Close
BV.48 Cfg_AnalogInput2Contact
See BV.45
Present Value 0 = Norm Open, 1 = Norm Close
BV.49 Cfg_WindowOpenedMode
Configuration to determine the action of the controller when the window is open. When set to (0)
setpoint, the controller will maintain the setpoint values of AV.12 & AV.13. If set to (1) OFF, the
controller will turn off and will not consider any setpoints.
Present Value 0 = Setpoint, 1 = OFF
BV.50 Cfg_DoorOpenedMode
Configuration to determine the action of the controller when the door is open. When set to (0)
setpoint, the controller will maintain the setpoint values of AV.12 & AV.13. If set to (1) OFF, the
controller will turn off and will not consider any setpoints.
Present Value 0 = Setpoint, 1 = OFF
BV.55 Cfg_AnalogOutput1Direction
Configuration of the analog output direction. When set to (0) Direct, the signal ramp is configured
from 0-10Vdc. When set to (1) Reverse, the signal ramp is configured from 10-0Vdc.
Present Value 0 = Direct, 1 = Reverse
BV.56 Cfg_AnalogOutput2Direction
See BV.55
Present Value 0 = Direct, 1 = Reverse
BV.60 Cfg_BinaryOutput1Direction
Configuration of the binary output direction. When set to (0) Direct, the contact is considered
Normally Opened. When set to (1) Reverse, the contact is considered Normally Closed.
Present Value 0 = Direct, 1 = Reverse
BV.61 Cfg_BinaryOutput2Direction
See BV.60
Present Value 0 = Direct, 1 = Reverse
BV.62 Cfg_BinaryOutput3Direction
See BV.60
Present Value 0 = Direct, 1 = Reverse
BV.63 Cfg_BinaryOutput4Direction
See BV.60
Present Value 0 = Direct, 1 = Reverse
BV.64 Cfg_BinaryOutput5Direction
See BV.60
Present Value 0 = Direct, 1 = Reverse
BV.65 Cfg_BinaryOutput6Direction
See BV.60
Present Value 0 = Direct, 1 = Reverse
BV.85 Cfg_ServiceDisplayAddress
When activated, the controller lights up and displays the MSTP address. It remains active until
deactivated via BACnet or upon cycling power to the controller. Useful when troubleshooting and/or
servicing the controller.
Present Value 0 = Off, 1 = On
BV.86 Cfg_KeyPadUpperLeftLock
If object is ON, the button is inactive in RUN mode but is active in the PRG mode via the controller.
Button is used to change the fan speed.
Present Value
0 = Off, 1 = On
If set to “On”, functionality of these buttons will not be
available.
BV.87 Cfg_KeyPadBottomLeftLock
If object is ON, the button is inactive in RUN mode but is active in the PRG mode via the controller.
Button is used to change temp control modes.
Present Value
0 = Off, 1 = On
If set to “On”, functionality of these buttons will not be
available.
BV.88 Cfg_KeyPadArrowsLock
If object is ON, the button is inactive in RUN mode but is active in the PRG mode via the controller.
Buttons are used to change the setpoint.
Present Value
0 = Off, 1 = On
If set to “On”, functionality of these buttons will not be
available.
BV.89 Cfg_ProgramModeLock
If object is ON, all buttons are inactive and PRG mode is not accessible via the controller.
Present Value 0 = Off, 1 = On
BV.90 CopyCfgExecute
When using Copy Config, this value is used to start the copy to other controllers.
Present Value 0 = No, 1 = Yes