TROB24 Series Thermostat 

 

BACnet

®

 Communication Module  

User Guide 

 
 
 
 

 

 

 
 
 
 
 

 
 
 
 
 
 
 
 
 

 

TROB24 SERIES-BACNET-USER GUIDE 

TROB24-120926-EUL.doc 

 

Summary of Contents for TROB24 Series

Page 1: ...TROB24 Series Thermostat BACnet Communication Module User Guide TROB24 SERIES BACNET USER GUIDE TROB24 120926 EUL doc...

Page 2: ...ries Thermostat 1 Table of Contents 1 Introduction 2 BACnet Overview 2 Getting Started 3 Quick Setup 3 Manual Setup 3 Copy Config 4 MAC address and Max_Master 4 Device Object Properties 5 Object Types...

Page 3: ...e refer to the Getting Started section on page 3 For more information on the thermostat menu please refer to the thermostat s Specification Installation Manual for more details BIBB Support The thermo...

Page 4: ...x_Master value can be configured through WriteProperty service to the Device Object Max_Master For more information refer to the MAC address and Max_Master section on page 4 Device Object Object_Name...

Page 5: ...ess and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not present Unless there are 126 other units on the MS...

Page 6: ...ays 0x00 0x09 0x40 0x02 0x60 i e a bitstring in BACnet order writeProperty readProperty deviceCommunicationControl unconfirmedPrivateTransfer who Is who Has Protocol_Object_Types_Supported Always 0x00...

Page 7: ...Multi State Value 5 Description Reliability States_Text Present_Value6 N A Out of Service Neptronic thermostats offer the use of the Out of Service writable property When set to true this property di...

Page 8: ...nds AV 42 CoolingDemand2 N A 0 100 Resolution 0 1 AV 43 CoolingPropBand2 Present Value 0 5 5 C or 1 10 F Resolution 0 5 C 1 F AV 44 CoolingDeadBand2 Present Value 0 3 5 C or 0 6 10 F Resolution 0 1 C...

Page 9: ...ng 4 Off only if BV 3 is set to Enable States available if MSV 4 is set to Cool 1 Cooling 2 Off only if BV 3 is set to Enable States available if MSV 4 is set to Heat 1 Heating 2 Off only if BV 3 is s...

Page 10: ...Value 1 ChangeOverDemand 2 CoolingDemand1 3 CoolingDemand2 4 HeatingDemand1 5 HeatingDemand2 States available if MSV 23 is set to Pulsing 1 HeatingDemand1 2 HeatingDemand2 MSV 20 TO3Source Present Va...

Page 11: ...n_Off 1 20 2 40 3 60 4 80 MSV 29 TO4ClosePos Present Value Ignored if MSV 25 is other than On_Off 1 20 2 40 3 60 4 80 MSV 31 PressureIndOutput Present Value if MSV 22 and MSV 24 are set to Floating 1...