Q539A, H and J Subbases 

Installation Instruction for the Trained Service Technician. 

Application 

Q539 Subbases provide cooling anticipators, and mounting for T87F Thermostats. Q539 Subbases also provide system 

and fan switching for heating, cooling, and heating-cooling thermostats. For subbase specifications, refer to Tables 1 and 2.

 TABLE 1—SUBBASE SPECIFICATIONS. 

Model Description 

System 

Switch 

Fan 

Switch 

Terminals 

See 

Fig. 

Q539A provides system and fan switching and cooling 
anticipator for heating cooling systems. Includes indicator 
LOCKOUT LED for use in oil burner systems. 

HEAT -
OFF-
COOL 

AUTO-ON  RH

-

RC-W-Y-G-X 

Q539H provides fan switching with Z terminal for low voltage 
fan switch to control fan in AUTO position. 

NONE 

AUTO-ON  R-W-Y-G-X-Z 

Q539J provides system switching for control of heating and 
cooling for heat pump and electric heating. Auto fan operates 
through fan relay on both heating and cooling. 

HEAT -
OFF-
COOL 

AUTO-ON  R-W-Y-G-X-P-O-B 

5

 TABLE 2—TERMINAL DESIGNATIONS. 

Terminal 

Connection 

Transformer. 

RC

Cooling Transformer. 

RH

Heating Transformer. 

Heating Relay or Valve Coil. 

Cooling Contactor Coil. 

B

Heating Damper Motor or Changeover 
Valve (if used). 

O

Cooling Damper Motor or Changeover 
Valve (if used). 

Fan Relay Coil. 

X

Clogged Filter Switch or Lockout Switch 
(primary control). 

Heat Pump Contactor Coil. 

Q539H low voltage fan switch for control 
of fan relay in AUTO position for both 
heating and cooling control. 

Cooling transformer in systems with separate heating and 
cooling circuits.

Heating transformer in systems with isolated heating and 
cooling circuits. 

Circuit only completed between R and B with system 
switch in HEAT position.

Circuit only completed between R and O with system 
switch in COOL position. 

Only available on subbases with indicator LEDs. 

M3375

 

Mercury Notice 

This control contains mercury in a sealed tube. Do n

ot 

place control in the trash at the end of its useful life. 

If this control is replacing a control that contains mer­

cury in a sealed tube, do 

not 

place your old control in the 

trash. 

Contact your local waste management authority for 

instructions regarding recycling and the proper disposal of 
this control, or of an old control containing mercury in a 
sealed tube. 

Installation 

WHEN INSTALLING THIS PRODUCT… 

1. Read these instructions carefully. Failure to follow 

instructions can damage product or cause a hazardous 

condition. 
2.  Check ratings given in instructions and on product to 

make sure product is suitable for your application. 

3.  Make sure installer is a trained, experienced service 

technician. 

4.  After completing installation check out product opera­

tion as provided in these instructions. 

LOCATION 

Locate the subbase about 5 ft (1.5m) above the floor in 

an area with good air circulation at average temperature. 

®U.S. Registered Trademark 
Copyright © 2002 Honeywell  • 

•  All Rights Reserved 

95-6486-9 

Summary of Contents for Q539

Page 1: ...l Z Q539H low voltage fan switch for control of fan relay in AUTO position for both heating and cooling control a Cooling transformer in systems with separate heating and cooling circuits b Heating transformer in systems with isolated heating and cooling circuits c Circuit only completed between R and B with system switch in HEAT position d Circuit only completed between R and O with system switch...

Page 2: ...er instructions for Q539 wiring diagrams If not available refer to Fig 1 through 5 4 Push excess wire back through the hole and plug any opening with insulation to prevent drafts that can affect performance 5 Loosely fasten the thermostat subbase to the wall with ascrewthroughtheleftmountinghole Adjustthesubbaseso it is approximately level and start the second screw through the right mounting slot...

Page 3: ... HOT M8833 Fig 5 Typical hookup for Q539J in heating cooling applications Fan relay operates automatically on heat or cool with fan in AUTO position Q539J T87F INTERNAL SCHEMATIC HEAT OFF COOL HEAT OFF COOL AUTO FAN ON W B R G P T87F TEMP FALL R1 ADJUST ABLE HEAT ANTICIPATOR FILTER LIGHT X Y CLOGGED FILTER SWITCH OR COOLING PANEL CONNECTION COMPRESSOR RELAY COOLING DAMPER MOTOR FAN RELAY O L1 HOT ...

Page 4: ...ch to ON The fan should run continuously Move the fan switch to AUTO In this position fan operation is controlled by the heating or cooling system control circuit Operate the entire system one complete cycle with switches in each position before leaving installation Turn thermostat dial to the desired setting and set the system and fan switches Automation and Control Solutions Honeywell Honeywell ...

Reviews: