TROB24 Series Thermostat
Page | 9
ID
7
Name
Writable
Property
Notes
MSV.12
UniversalInput2Function
22
Present
Value
1= Off
2= Extern.Sensor
3= ChangeOverSensor
4= Ch.Ov.ContactNorm.Cool
5= Ch.Ov.ContactNorm.Heat
6= NightSetBack
7= Pressure0-10V
8= AirFlow0-10V
MSV.13
NightSetBackMode
23
Present
Value
1= Locally
2= Day
3= Night
MSV.15
UniversalInput3Function
24
Present
Value
1= Off
2= Extern.Sensor
3= ChangeOverSensor
4= Ch.Ov.ContactNorm.Cool
5= Ch.Ov.ContactNorm.Heat
6= NightSetBack
7= Pressure0-10V
8= AirFlow0-10V
MSV.16
AnalogOutput1Source Present
Value
1= Off
2= ChangeOverDemand
3= CoolingDemand1
4= CoolingDemand2
5= HeatingDemand1
6= HeatingDemand2
MSV.17
AnalogOutput2Source Present
Value
1 = Off
2= ChangeOverDemand
3= CoolingDemand1
4= CoolingDemand2
5= HeatingDemand1
6= HeatingDemand2
MSV.18
TO1Source Present
Value
1= ChangeOverDemand
2= CoolingDemand1
3= CoolingDemand2
4= HeatingDemand1
5= HeatingDemand2
States available if MSV.22 is set to “Pulsing”:
1= HeatingDemand1
2= HeatingDemand2
MSV.19
TO2Source Present
Value
1= ChangeOverDemand
2= CoolingDemand1
3= CoolingDemand2
4= HeatingDemand1
5= HeatingDemand2
States available if MSV.23 is set to “Pulsing”:
1= HeatingDemand1
2= HeatingDemand2
MSV.20
TO3Source Present
Value
1= Off
2= ChangeOverDemand
3= CoolingDemand1
4= CoolingDemand2
5= HeatingDemand1
6= HeatingDemand2
States available if MSV.24 is set to “Pulsing”:
1= HeatingDemand1
2= HeatingDemand2
MSV.21
TO4Source Present
Value
1= Off
2= ChangeOverDemand
3= CoolingDemand1
4= CoolingDemand2
5= HeatingDemand1
6= HeatingDemand2
States available if MSV.25 is set to “Pulsing”:
1= HeatingDemand1
2= HeatingDemand2
22
Activating external temperature does not automatically modify the control source; it is necessary to also modify BV.6 to control external
temperature. Pressure0-10V and AirFlow0-10V are available on version 1.03 and above.
23
Selecting “Locally” enables the thermostat to manage the day or night status for energy conservation. The other 2 statuses force the
thermostat into a specific state.
24
Activating external temperature does not automatically modify the control source; it is necessary to also modify BV.6 to control external
temperature. Pressure0-10V and AirFlow0-10V are available on version 1.03 and above.