Neptronic TROB24 Series User Manual Download Page 5

 

TROB24 Series Thermostat 

 

Page  | 4  

2)  Enter the password (637). 
3)  In this mode you can manually configure the MAC address, Device Instance and Baud Rate. 
4)  Power down the thermostat, connect the thermostat to the network and then power up the thermostat. 
5)  Repeat steps 1 to 4 for each. 
6)  To increase network efficiency or if there are less than 127 devices on the network, the Max_Master 

value can be configured through WriteProperty service to the 

Device Object.Max_Master

. For more 

information, refer to the 

MAC address and Max_Master

 section on page 4. 

Copy Config 

Copy the thermostat’s entire configuration and broadcast it to other devices of the same type on the same 
network. 

1)  With the thermostat in Operation Mode (jumper = RUN), go to the Quick Access Menu by pressing and 

holding both function buttons on the thermostat for 5 seconds. Refer to the thermostat’s

 Specification & 

Installation Manual

 for more details. 

2)  Enter the password (637). 
3)  Scroll to “Copy Config” and select yes. Follow onscreen instructions. 

MAC address and Max_Master 

The MAC address must be unique on the entire MS/TP network. However, having a unique MAC address and a 
high baud rate does not guarantee efficient operation of the thermostat and other MS/TP units on the MS/TP 
network. Some MAC address and Max_Master combinations are more efficient than others. BACnet

®

 requires 

token-passing units to occasionally “poll” for other masters based on the MAC address and Max_Master. A 
“poor” combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for 
masters that are not present. Unless there are 126 other units on the MS/TP network, the default Max_Master 
of 127 is not the most efficient choice for the thermostat. The Max_Master default of 127 was selected to ensure 
that any master, specifically a BACnet

®

 client, can be found when the thermostat is first started. 

 

Example 1: 

This example is slow and inefficient because every time either unit is required to find another master unit it has 
to poll 126 units until it finds the right one to pass the token. 

 MAC=0. 

Max_Master=127 

 MAC=1, 

Max_Master=127 

 

Example 2: 

This example is better but it’s still slower. The Max_Master is set to the most efficient value; however because 
of the gap between the two MAC addresses, each unit must poll 4 units until it finds the right one to pass the 
token. 

 MAC=0. 

Max_Master=5 

 

MAC=1 to MAC=4 are not used 

 MAC=5, 

Max_Master=5 

 

Example 3: 

This example is an incorrect configuration. The MAC=0 will never find MAC=2 because it will never poll for the 
master MAC address=2. 

 MAC=0. 

Max_Master=1 

 MAC=2, 

Max_Master=2 

 

Example 4: 

As a general guideline, the most efficient set up for an MS/TP network is one in which the units are 
consecutively numbered starting at MAC address 0 and all have Max_Master=the maximum MAC address in 
the system. If consecutive numbering is not possible, then the next most efficient set up is one in which all units 
have Max_Master=the maximum MAC address in the system. 

 MAC=0. 

Max_Master=3 

 MAC=1, 

Max_Master=3 

 MAC=2, 

Max_Master=3 

 MAC=3, 

Max_Master=3 

Summary of Contents for TROB24 Series

Page 1: ...TROB24 Series Thermostat BACnet Communication Module User Guide TROB24 SERIES BACNET USER GUIDE TROB24 120926 EUL doc...

Page 2: ...ries Thermostat 1 Table of Contents 1 Introduction 2 BACnet Overview 2 Getting Started 3 Quick Setup 3 Manual Setup 3 Copy Config 4 MAC address and Max_Master 4 Device Object Properties 5 Object Types...

Page 3: ...e refer to the Getting Started section on page 3 For more information on the thermostat menu please refer to the thermostat s Specification Installation Manual for more details BIBB Support The thermo...

Page 4: ...x_Master value can be configured through WriteProperty service to the Device Object Max_Master For more information refer to the MAC address and Max_Master section on page 4 Device Object Object_Name...

Page 5: ...ess and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not present Unless there are 126 other units on the MS...

Page 6: ...ays 0x00 0x09 0x40 0x02 0x60 i e a bitstring in BACnet order writeProperty readProperty deviceCommunicationControl unconfirmedPrivateTransfer who Is who Has Protocol_Object_Types_Supported Always 0x00...

Page 7: ...Multi State Value 5 Description Reliability States_Text Present_Value6 N A Out of Service Neptronic thermostats offer the use of the Out of Service writable property When set to true this property di...

Page 8: ...nds AV 42 CoolingDemand2 N A 0 100 Resolution 0 1 AV 43 CoolingPropBand2 Present Value 0 5 5 C or 1 10 F Resolution 0 5 C 1 F AV 44 CoolingDeadBand2 Present Value 0 3 5 C or 0 6 10 F Resolution 0 1 C...

Page 9: ...ng 4 Off only if BV 3 is set to Enable States available if MSV 4 is set to Cool 1 Cooling 2 Off only if BV 3 is set to Enable States available if MSV 4 is set to Heat 1 Heating 2 Off only if BV 3 is s...

Page 10: ...Value 1 ChangeOverDemand 2 CoolingDemand1 3 CoolingDemand2 4 HeatingDemand1 5 HeatingDemand2 States available if MSV 23 is set to Pulsing 1 HeatingDemand1 2 HeatingDemand2 MSV 20 TO3Source Present Va...

Page 11: ...n_Off 1 20 2 40 3 60 4 80 MSV 29 TO4ClosePos Present Value Ignored if MSV 25 is other than On_Off 1 20 2 40 3 60 4 80 MSV 31 PressureIndOutput Present Value if MSV 22 and MSV 24 are set to Floating 1...

Page 12: ...treal Qc H4N 1R6 CANADA www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service Fax 514 333 1091 Business hours from Monday to Friday 8 00am to 5...

Reviews: