TROB24 Series Thermostat
Page | 8
ID
7
Name
Writable
Property
Notes
BV.1
TempUnit Present
Value
0= Celsius
1= Fahrenheit
BV.2
TempSetPointLock Present
Value
0= Disable
1= Enable
BV.3
UserControlOffMode
13
Present
Value
0= Enable
1= Disable
BV.6
ControlTempSource Present
Value
0= Intern.Sensor
1= Extern.Sensor
14
BV.7
ChangeOverMode Out
of
service
0= Cooling
1= Heating
BV.14
AirFlowBalancing Present
Value
0= Disable
1= Enable
BV.15
AirFlowBalMode Present
Value
0= Minimum
1= Maximum
BV.16
AntiFreezeProtection
15
Present
Value
0= Off
1= On
BV.17
FloatingMotor1Direction Present
Value
0= Direct
1= Reverse
BV.18
FloatingMotor2Direction Present
Value
0= Direct
1= Reverse
BV.29
OnOffOutput1
16
Present
Value
0= Off
1= On
BV.30
OnOffOutput2
17
Present Value
0= Off
1= On
BV.31
OnOffOutput3
18
Present Value
0= Off
1= On
BV.32
OnOffOutput4
19
Present Value
0= Off
1= On
MSV.1
UniversalInput1Function
20
Present
Value
1= Off
2= Extern.Sensor
3= ChangeOverSensor
4= Ch.Ov.ContactNorm.Cool
5= Ch.Ov.ContactNorm.Heat
6= NightSetBack
7= Pressure0-10V
8= AirFlow0-10V
MSV.3
UserControlMode Present
Value
States available if MSV.4 is set to “Auto”
1=
Auto,
2=
Heating
3=
Cooling
4= Off (only if BV.3 is set to “Enable”)
States available if MSV.4 is set to “Cool”
1=
Cooling
2= Off (only if BV.3 is set to “Enable”)
States available if MSV.4 is set to “Heat”
1=
Heating
2= Off (only if BV.3 is set to “Enable”)
States available if MSV.4 is set to “HeatingOrCooling”
1=
Heating
2=
Cooling
3= Off (only if BV.3 is set to “Enable”)
MSV.4
ControlMode
21
Present
Value
1= Auto
2= Heating
3= Cooling
4= HeatingOrCooling
MSV.9
NightSetBack Out
of
service
1= Day
2= Night
3= Override
13
Enable or Disable “off” state of UserControlMode (MSV.3).
14
It can be set to “Use Extern.Sensor” only if one object MSV.1, MSV.12 or MSV.15 is set to “Extern.Sensor”
15
Available on version 1.03 and above.
16
Writable if MSV.18 is set OFF. Off means no internal process affected to this output.
17
Writable if MSV.19 is set OFF. Off means no internal process affected to this output.
18
Writable if MSV.20 is set OFF. Off means no internal process affected to this output.
19
Writable if MSV.21 is set OFF. Off means no internal process affected to this output.
20
Activating external temperature does not automatically modify the control source; it is necessary to also modify BV.6 to control by external
temperature. Pressure0-10V and AirFlow0-10V are available on version 1.03 and above.
21
Locks user options. MSV.3, UserControlMode, will be affected or even locked in one state.