Neptronic TROB24 Series User Manual Download Page 9

TROB24 Series Thermostat

 

Page  | 8  

ID

7

 Name 

Writable  
Property 

Notes 

BV.1 

TempUnit Present 

Value 

0= Celsius 
1= Fahrenheit 

BV.2 

TempSetPointLock Present 

Value 

0= Disable  
1= Enable 

BV.3 

UserControlOffMode

13

 Present 

Value 

0= Enable  
1= Disable 

BV.6 

ControlTempSource Present 

Value 

0= Intern.Sensor 
1= Extern.Sensor

14

 

BV.7 

ChangeOverMode Out 

of 

service 

0= Cooling  
1= Heating 

BV.14 

AirFlowBalancing Present 

Value 

0= Disable 
1= Enable 

BV.15 

AirFlowBalMode Present 

Value 

0= Minimum 
1= Maximum 

BV.16 

AntiFreezeProtection

15

 Present 

Value 

0= Off 
1= On 

BV.17 

FloatingMotor1Direction Present 

Value 

0= Direct 
1= Reverse 

BV.18 

FloatingMotor2Direction Present 

Value 

0= Direct 
1= Reverse 

BV.29 

OnOffOutput1

16

 Present 

Value

 

0= Off 
1= On 

BV.30 

OnOffOutput2

17

 

Present Value

 

0= Off 
1= On 

BV.31 

OnOffOutput3

18

 

Present Value

 

0= Off 
1= On 

BV.32 

OnOffOutput4

19

 

Present Value

 

0= Off 
1= On 

MSV.1 

UniversalInput1Function

20

 Present 

Value 

1= Off  
2= Extern.Sensor 
3= ChangeOverSensor 
4= Ch.Ov.ContactNorm.Cool 
5= Ch.Ov.ContactNorm.Heat 
6= NightSetBack  
7= Pressure0-10V  
8= AirFlow0-10V 

MSV.3 

UserControlMode Present 

Value 

States available if MSV.4 is set to “Auto” 
1=

 

Auto,  

2=

 

Heating  

3=

 

Cooling  

4= Off (only if BV.3 is set to “Enable”) 

States available if MSV.4 is set to “Cool” 
1=

 

Cooling  

2= Off (only if BV.3 is set to “Enable”) 

States available if MSV.4 is set to “Heat” 
1=

 

Heating  

2= Off (only if BV.3 is set to “Enable”) 
States available if MSV.4 is set to “HeatingOrCooling” 
1=

 

Heating  

2=

 

Cooling  

3= Off (only if BV.3 is set to “Enable”) 

MSV.4 

ControlMode

21

 Present 

Value 

1= Auto  
2= Heating  
3= Cooling  
4= HeatingOrCooling 

MSV.9 

NightSetBack Out 

of 

service 

1= Day  
2= Night  
3= Override 

                                                      

13

 Enable or Disable “off” state of UserControlMode (MSV.3). 

14

 It can be set to “Use Extern.Sensor” only if one object MSV.1, MSV.12 or MSV.15 is set to “Extern.Sensor” 

15

 Available on version 1.03 and above. 

16

 Writable if MSV.18 is set OFF. Off means no internal process affected to this output. 

17

 Writable if MSV.19 is set OFF. Off means no internal process affected to this output. 

18

 Writable if MSV.20 is set OFF. Off means no internal process affected to this output. 

19

 Writable if MSV.21 is set OFF. Off means no internal process affected to this output. 

20

 Activating external temperature does not automatically modify the control source; it is necessary to also modify BV.6 to control by external 

temperature. Pressure0-10V and AirFlow0-10V are available on version 1.03 and above. 

21 

Locks user options. MSV.3, UserControlMode, will be affected or even locked in one state.

 

Summary of Contents for TROB24 Series

Page 1: ...TROB24 Series Thermostat BACnet Communication Module User Guide TROB24 SERIES BACNET USER GUIDE TROB24 120926 EUL doc...

Page 2: ...ries Thermostat 1 Table of Contents 1 Introduction 2 BACnet Overview 2 Getting Started 3 Quick Setup 3 Manual Setup 3 Copy Config 4 MAC address and Max_Master 4 Device Object Properties 5 Object Types...

Page 3: ...e refer to the Getting Started section on page 3 For more information on the thermostat menu please refer to the thermostat s Specification Installation Manual for more details BIBB Support The thermo...

Page 4: ...x_Master value can be configured through WriteProperty service to the Device Object Max_Master For more information refer to the MAC address and Max_Master section on page 4 Device Object Object_Name...

Page 5: ...ess and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not present Unless there are 126 other units on the MS...

Page 6: ...ays 0x00 0x09 0x40 0x02 0x60 i e a bitstring in BACnet order writeProperty readProperty deviceCommunicationControl unconfirmedPrivateTransfer who Is who Has Protocol_Object_Types_Supported Always 0x00...

Page 7: ...Multi State Value 5 Description Reliability States_Text Present_Value6 N A Out of Service Neptronic thermostats offer the use of the Out of Service writable property When set to true this property di...

Page 8: ...nds AV 42 CoolingDemand2 N A 0 100 Resolution 0 1 AV 43 CoolingPropBand2 Present Value 0 5 5 C or 1 10 F Resolution 0 5 C 1 F AV 44 CoolingDeadBand2 Present Value 0 3 5 C or 0 6 10 F Resolution 0 1 C...

Page 9: ...ng 4 Off only if BV 3 is set to Enable States available if MSV 4 is set to Cool 1 Cooling 2 Off only if BV 3 is set to Enable States available if MSV 4 is set to Heat 1 Heating 2 Off only if BV 3 is s...

Page 10: ...Value 1 ChangeOverDemand 2 CoolingDemand1 3 CoolingDemand2 4 HeatingDemand1 5 HeatingDemand2 States available if MSV 23 is set to Pulsing 1 HeatingDemand1 2 HeatingDemand2 MSV 20 TO3Source Present Va...

Page 11: ...n_Off 1 20 2 40 3 60 4 80 MSV 29 TO4ClosePos Present Value Ignored if MSV 25 is other than On_Off 1 20 2 40 3 60 4 80 MSV 31 PressureIndOutput Present Value if MSV 22 and MSV 24 are set to Floating 1...

Page 12: ...treal Qc H4N 1R6 CANADA www neptronic com Toll free in North America 1 800 361 2308 Tel 514 333 1433 Fax 514 333 3163 Customer service Fax 514 333 1091 Business hours from Monday to Friday 8 00am to 5...

Reviews: