Neptronic TROB24 Series User Manual Download Page 8

TROB24 Series Thermostat

 

Page  | 7  

TROB24 Series Objects Table 

The TROB24 thermostat series of controllers use the following BACnet

®

 object table. The 

type

 is the BACnet

®

 

Object type, the 

instance

 is the BACnet

®

 Object. Together the 

type

 and 

instance

 form the BACnet

®

 

Object_Identifier for an object according to the following C-language algorithm: 
 

 

object_identifier=(unsigned long)((unsigned long)

type

<<22)+

instance

 

 

ID

7

 Name 

Writable  
Property 

Notes 

AI.1 

InternTemp 

Out of service 

0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF 

AI.2 

ExternTemp Out 

of 

service

 

-40-100ºC or -40-212ºF, Resolution 0.01ºC/0.02ºF 

AI.3 

ChangeOverTemp Out 

of 

service

 

-40-100ºC or -40-212ºF, Resolution 0.01ºC/0.02ºF 

AI.10 

PressureSensor Out 

of 

service

0-10.00 Volt, Resolution 0.01 Volt 

AV.1 

ControlTemp Out 

of 

service

 

-40-100ºC or -40-212ºF, Resolution 0.01ºC/0.02ºF 

AV.2 

HeatingDemand1 N/A

0-100%, Resolution 0.1% 

AV.3 

CoolingDemand1 N/A

 

0-100%, Resolution 0.1% 

AV.5 

InternTempOffset 

Present Value 

±5.0ºC, Resolution 0.1ºC 

AV.6 

ExternTempOffset Present 

Value

 

±5.0ºC, Resolution 0.1ºC 

AV.7 

TempSetPointDay Present 

Value

AV.8 to AV.9, Resolution 0.5ºC/1ºF 

AV.8 

MinSetPointDay Present 

Value

 

0 to AV.9 , Resolution 0.5ºC/1ºF 

AV.9 

MaxSetPointDay Present 

Value

AV.8 to 40ºC or 104ºF, Resolution 0.5ºC/1ºF 

AV.10 

TempSetPointCoolNight Present 

Value

 

AV.11 to 40ºC or 104ºF, Resolution 0.5ºC/1ºF 

AV.11 

TempSetPointHeatNight Present 

Value

10.0ºC or 50ºF to AV.10, Resolution 0.5ºC/1ºF 

AV.12 

CoolingPropBand1 Present 

Value

0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF 

AV.13 

HeatingPropBand1 Present 

Value

 

0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF 

AV.14 

CoolingDeadBand1 Present 

Value

0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF 

AV.15 

HeatingDeadBand1 Present 

Value

 

0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF 

AV.23 

ChangeOverSetPoint Present 

Value

 

10-40ºC or 50-104ºF, Resolution 0.5ºC/1ºF 

AV.24 

NightSetBackDelay 

Present Value 

0-180 minutes, Resolution 15 minutes 

AV.26 

IntTimeFactor Present 

Value

0-250 seconds, Resolution 5 seconds 

AV.27 

CoolingAntiCycleDelay Present 

Value

 

0-15 minutes, Resolution 1 minute 

AV.31 

FloatingMotorTiming1

8

 Present 

Value

 

15-250 seconds, Resolution 5 seconds 

AV.42 

CoolingDemand2 N/A

0-100%, Resolution 0.1% 

AV.43 

CoolingPropBand2 Present 

Value

 

0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF 

AV.44 

CoolingDeadBand2 Present 

Value

0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF 

AV.46 

HeatingDemand2 

N/A 

0-100%, Resolution 0.1% 

AV.47 

HeatingPropBand2 

Present Value 

0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF 

AV.48 

HeatingDeadBand2 

Present Value 

0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF 

AV.49 

ChangeOverDemand 

N/A 

0-100%, Resolution 0.1% 

AV.50 

ChangeOverPropBand 

Present Value 

0.5-5ºC or 1-10ºF, Resolution 0.5ºC/1ºF 

AV.51 

ChangeOverDeadBand 

Present Value 

0.3-5ºC or 0.6-10ºF, Resolution 0.1ºC/0.2ºF 

AV.52 

AnalogOutput1Min 

Present Value 

0 Volt to AV.54, Resolution 0.1 Volt 

AV.53 

AnalogOutput2Min 

Present Value 

0 Volt to AV.55, Resolution 0.1 Volt 

AV.54 

AnalogOutput1Max 

Present Value 

AV.52 to 10.0 Volt, Resolution 0.1 Volt 

AV.55 

AnalogOutput2Max 

Present Value 

AV.53 to 10.0 Volt, Resolution 0.1 Volt 

AV.56 

AnalogOutput1MinPos 

Present Value 

0-100%, Resolution 5% 

AV.57 

AnalogOutput2MinPos 

Present Value 

0-100%, Resolution 5% 

AV.58 

FloatingMotorTiming2 

9

 

Present Value 

15-250 seconds, Resolution 5 seconds 

AV.61 

PressureNumFilter 

Present Value 

1-10 seconds, Resolution 1 second 

AV.62 

AirFlowVnomOrKFactor 

Present Value 

100-9995, Resolution 5  

AV.63 

AirFlowCoolMin 

Present Value 

0 to AV.64, Resolution 5 

AV.64 

AirFlowCoolMax 

Present Value 

AV.63 to AV.62, Resolution 5 

AV.65 

AirFlowHeatMin 

Present Value 

0 to AV.66, Resolution 5 

AV.66 

AirFlowHeatMax 

Present Value 

AV.65 to AV.62, Resolution 5 

AV.67 

AirFlowIntFactor 

Present Value 

0-60 minutes, Resolution 1 minute 

AV.68 

ActualAirFlow 

OutOfService 

0 to AV.62, Resolution 1 

AV.69 

AirFlowSetPoint 

OutOfService 

0-9999, Resolution 1 

AV.71 

AdjustAirFlowKFactor

10

 

Present Value 

0-9999, Resolution 1 

AV.72 

AnalogOutput1

11

 N/A 

0-10V 

AV.73 

AnalogOutput2

12

 N/A 

0-10V 

AV.160 

AirFlowOffset Present 

Value 

±500 

BI.1 

UIxContactInput Out 

of 

service 

0= Open  
1= Close 

                                                      

7

 ID is equal to ObjectType.Instance 

8

 Used if MSV.22 and MSV.23 are in Floating mode.  

9

 Used if MSV.24 and MSV.25 are in Floating mode. 

10

 Writable only if system is in balancing, BV.14 is set to “Enable” and BV.15 is set to “Maximum” 

11

 Writable if MSV.16 is set OFF. Off means no internal process affected to this output. 

12

 Writable if MSV.17 is set OFF. Off means no internal process affected to this output. 

Summary of Contents for TROB24 Series

Page 1: ...TROB24 Series Thermostat BACnet Communication Module User Guide TROB24 SERIES BACNET USER GUIDE TROB24 120926 EUL doc...

Page 2: ...ries Thermostat 1 Table of Contents 1 Introduction 2 BACnet Overview 2 Getting Started 3 Quick Setup 3 Manual Setup 3 Copy Config 4 MAC address and Max_Master 4 Device Object Properties 5 Object Types...

Page 3: ...e refer to the Getting Started section on page 3 For more information on the thermostat menu please refer to the thermostat s Specification Installation Manual for more details BIBB Support The thermo...

Page 4: ...x_Master value can be configured through WriteProperty service to the Device Object Max_Master For more information refer to the MAC address and Max_Master section on page 4 Device Object Object_Name...

Page 5: ...ess and Max_Master A poor combination of MAC addresses and Max_Master can lead to a slower network due to lost time polling for masters that are not present Unless there are 126 other units on the MS...

Page 6: ...ays 0x00 0x09 0x40 0x02 0x60 i e a bitstring in BACnet order writeProperty readProperty deviceCommunicationControl unconfirmedPrivateTransfer who Is who Has Protocol_Object_Types_Supported Always 0x00...

Page 7: ...Multi State Value 5 Description Reliability States_Text Present_Value6 N A Out of Service Neptronic thermostats offer the use of the Out of Service writable property When set to true this property di...

Page 8: ...nds AV 42 CoolingDemand2 N A 0 100 Resolution 0 1 AV 43 CoolingPropBand2 Present Value 0 5 5 C or 1 10 F Resolution 0 5 C 1 F AV 44 CoolingDeadBand2 Present Value 0 3 5 C or 0 6 10 F Resolution 0 1 C...

Page 9: ...ng 4 Off only if BV 3 is set to Enable States available if MSV 4 is set to Cool 1 Cooling 2 Off only if BV 3 is set to Enable States available if MSV 4 is set to Heat 1 Heating 2 Off only if BV 3 is s...