SKG Steam Humidifier
BACnet® Communication Module User Guide
15
SKG Humidifier Object Table
For tank 3:
type inst Object_Name
Description
range of Present_Value
W?
AI
301
Water_Temp3
Water Temperature 3
0-260 °C or 32-500 °F
AI
302
Chimney_Temp3
Chimney Temperature 3
0-260 °C or 32-500 °F
AI
303
Water_Level3
Water level 3
0-120%
AI
304
Burner_Demand3
Burner Demand 3
0.0 - 100.0%
AI
305
Op_Timer_Total3
Operation Timer 3 (Total
time)
1-1677215Hrs
AI
306
Op_Timer3
Operation Timer 3
1-5000Hrs
AI
307
Delay_Autodrain3
Delay until Auto-drain 3
1-100Hrs
AI
308
Foam_Probe_Sensr3
Foam Probe Sensor 3
0-255
AI
309
Burner_Fan_Speed3
Burner Fan Speed 3
0-1000Hz
type inst Object_Name
Description
range of Present_Value
W?
AV
301
Water_Temp_Off3
Water Temperature offset
3
±0-20 °C or ±0-40 °F
W
AV 302 Chimney_Temp_Off3 Chimney
Temperature
offset 3
±0-20 °C or ±0-40 °F
W
AV
303
Water_Level_Off3
Water Level offset 3
±0-20%
W
type inst Object_Name
Description
range of Present_Value
W?
-- -- --
Alarm
1:
-
BV
301
OverTemp_Cont_ON3
Over temperature contact
ON 3
0=Normal, 1=Alarm
W
BV
302
Bad_Fill_Tank3
Defective filling tank 3
0=Normal, 1=Alarm
W
BV 303 Bad_Refill_Tank3
Defective refill tank 3(too
long)
0=Normal, 1=Alarm
W
BV
304
Bad_Drain_Tank3
Defective draining tank 3
0=Normal, 1=Alarm
W
BV
305
Bad_Burner_Fan3
Defective Burner Fan 3
0=Normal, 1=Alarm
W
BV
306
Bad_Burner_Gas3
Defective Burner Gas
3(Locked)
0=Normal, 1=Alarm
W
BV
307
Input_Volt_Low3
Input voltage 3 too low
0=Normal, 1=Alarm
W
BV
308
Power_Fuse_Open3
Power Fuse 3 open
(34VAC)
0=Normal, 1=Alarm
W
-- -- --
Alarm
3:
-
BV
309
Tank_Sens_Bad3
Tank sensor 3 defective
0=Normal, 1=Alarm
W
BV
310
Chim_Sens_Bad3
Chimney sensor 3
defective
0=Normal, 1=Alarm
W
BV
311
H3OLvl_Prb_Bad3
Water level probe 3 defect
0=Normal, 1=Alarm
W
BV
312
Foam_Sens_ON3
Foam Sensor 3 ON
0=Normal, 1=Alarm
W
BV
313
OverFlow_DripPan3
Over Flow, Drip Pan 3
0=Normal, 1=Alarm
W
BV
314
Tank_Temp_Low3
Tank temper. 3 Too low
(freeze)
0=Normal, 1=Alarm
W
BV
315
Tank_Temp_Hi3
Tank temperature 3 too
high
0=Normal, 1=Alarm
W
BV
316
Chimney_Temp_Hi3
Chimney temperature 3
too high
0=Normal, 1=Alarm
W