SKG Steam Humidifier
BACnet® Communication Module User Guide
22
Configuration
Example 4:
•
MAC=0.
Max_Master=1
•
MAC=1,
Max_Master=1
This example is the most efficient, since each unit must poll only 1 other unit until it finds the right one to pass
the token to.
As a general guideline, the most efficient set up for an MS/TP network is one in which the units are
consecutively numbered starting at MAC address 0 and all have Max_Master=the maximum MAC address in
the system. If consecutive numbering is not possible, then the next most efficient set up is one in which all units
have have Max_Master=the maximum MAC address in the system.