SKG Steam Humidifier
BACnet® Communication Module User Guide
10
SKG Humidifier Object Table
Common for all SKG Models:
type inst
Object_Name
Description
range of Present_Value
W?
MSV
1
Ctl_Mode
Control Mode
1=Demand from analog
input 1 (default)
2=Internal PID loop
calculation
3=Demand from remote
communication port (e.g.
BACnet)
W
MSV
2
Operation_Mode
Operation Mode
1=Set unit Off
2=Set unit On
3=Set unit in drain mode
W
MSV 3 Unit_Display_Lang Unit
Display Language
1=English (Default)
2=French
3=Spanish
W
MSV
4
SP_Source
Setpoint Source
1=Local analog input 1
2=Local Internal digital
value
3=Remote from
communication port (e.g.
BACnet)
W
MSV
5
Room_Hum_Source
Room Humidity Source
1=Local analog input 2
(default)
2=Remote from
communication port (e.g.
BACnet)
MSV 6 Duct_Hum_Source Duct
Humidity Source
1=Not used
2=Local analog input 3
3=Remote from
communication port (e.g.
BACnet)
W