SKG Steam Humidifier 

BACnet® Communication Module User Guide

 

 

SKG Humidifier Object Table 

The SKG Humidifier use the following BACnet object table. The 

type

 is the BACnet Object type, the 

instance

 is 

the BACnet Object instance. 

W?

 indicates whether the Present_Value property is writable. Together the 

type

 

and 

instance

 form the BACnet Object_Identifier for an object according to the following C-language algorithm: 

 object_identifier=(unsigned 

long)((unsigned long)type<<22)+instance 

 
Object instances are assigned according to the following scheme: 

 

The Object instance for the Device Object is 153000 by default. This value can be reprogrammed from 
between 0 and 4194302 as needed to insure uniqueness system-wide 

 

For the Properties that are Common for all SKG Models, the Object instances range from 1 to 99 as 
needed. 

 

For the Tank Properties, the Object instances range from 101 to 199 for Tank 1, 201 to 299 for Tank 2, 
301 to 399 for Tank 3 and 401 to 499 for Tank 4 as needed. 

Common for all SKG Models: 

type inst  Object_Name 

Description 

range of Present_Value 

W? 

AI 

Humidity_Out 

Humidity Output 

0-100 %RH 

 

 
type inst  Object_Name 

Description 

range of Present_Value 

W? 

AV 

Humidity_Demand 

Humidity Demand 

0-100 %RH 

AV 2  Room_Humidity 

Room 

Humidity 

0-100 

%RH 

AV 

Room_Humidity_Off 

Room Humidity offset 

±0-10.0 %RH 

AV 

Duct_Humidity 

Duct Humidity 

0-100 %RH 

AV 

Duct_Humidity_Off 

Duct Humidity offset 

±0-10.0 %RH 

AV 

Outside_Temp 

Outside Temperature 

-40 - 40 °C or -40 - 104 
°F 

AV 7  Lock_On_Capacity 

Lock 

On 

capacity 

10-100% 

AV 

Max_Output_Limit 

Maximum output limit 

10-100% 

AV 

Drain_Delay    

Drain Delay 

1-100Hrs 

AV 10  Service_Delay 

Service 

Delay 

1-5000Hrs 

AV 

11 

End_Season_Delay 

End of season delay 

1-250Hrs 

AV 

12 

PID_Loop_KP 

PID Loop gain KP 

0-255 

AV 

13 

PID_Loop_KI 

PID Loop gain KI 

0-255 

AV 

14 

PID_Loop_KD 

PID Loop gain KD 

0-255 

AV 15  Ctl_Band 

Control 

band  

 

 

 

0-20.0% (0..200) 

AV 

16 

Ctl_SP 

Control set point 

0-100%RH 

AV 

17 

Extern_SP_Min 

External setpoint minimum 

0-100%RH 

AV 18  Extern_SP_Max 

External 

setpoint 

maximum 

0-100%RH W 

AV 

19 

Duct_Hum_HiLim_SP 

Duct hum. high limit set 
point 

50-100%RH W 

AV 

20 

Min_ON_Time_Fan 

Minimum ON time for fan 

2-20 minutes 

AV 

21 

Min_H2O_Temp 

Min. water temp. in ON 
mode 

50-90 °C or 122-194 °F 
(0 -> Mode is Off) 

AV 22  Antifreeze_Temp 

Anti-freeze 

mode 

temperature 

7-12 °C or 44-54 °F (0 -> 
Mode is Off) 

AV 

23 

Analog_Ctl_In_Lo 

Analog Control input Lo 
Limit 

0-10.00VDC W 

AV 

24 

Analog_Ctl_In_Hi 

Analog Control input Hi 
Limit 

0-10.00VDC W 

AV 

25 

Analog_Hum_In_Lo 

Analog Humidity input Lo 
Limit 

0-10.00VDC W 

AV 

26 

Analog_Hum_In_Hi 

Analog Humidity input Hi 
Limit 

0-10.00VDC W 

AV 27  Analog_Duct_In_Lo  Analog 

Duct input Lo Limit 

0-10.00VDC 

AV 28  Analog_Duct_In_Hi 

Analog 

Duct input Hi Limit 

0-10.00VDC 

Summary of Contents for SKG Series

Page 1: ...Gas Fired Humidifier SKG Series BACnet Communication Module User Guide SKG BACNET Rev 060803...

Page 2: ......

Page 3: ...t 1 Introduction BACnet Requirements 2 Introduction 2 BACnet Requirements 2 Device Object 3 Objects 4 SKG Humidifier Object Table 8 Configuration 19 Personal notes 23 Other related documents 1 Install...

Page 4: ...hrough WriteProperty service to the device object A default MAC address of 254 shall be recognized when a configuration dip switch is set to configure mode Two other dip switches shall determine MS TP...

Page 5: ...s unavailable and is unreliable Firmware_Revision currently 1 00 Application_Software_Version currently 1 00 Protocol_Version always 1 Protocol_Revision always 2 Max_APDU_Length_Accepted always 107 Se...

Page 6: ...puts AI Analog Values AV 6 Binary Inputs BI 16 Binary Values BV 1 Multistate Input MSI So the number of objects vs the number of Tanks are listed in the following table Number of Tanks Number of Objec...

Page 7: ...is set this property s value is unreliable_other otherwise it s no_fault_detected Out_of_Service Always false Units see Object Table Analog Values property value W Object_Identifier see Object Table...

Page 8: ...no_fault_detected Out_of_Service Always normal Polarity see Object Table Active_Text see Object Table Inactive_Text see Object Table Binary Values property value W Object_Identifier see Object Table...

Page 9: ...property s value is unreliable_other otherwise it s no_fault_detected Out_of_Service Always normal Number_of_States see Object Table Multistate Values property value W Object_Identifier see Object Ta...

Page 10: ...dity_Off Room Humidity offset 0 10 0 RH W AV 4 Duct_Humidity Duct Humidity 0 100 RH W AV 5 Duct_Humidity_Off Duct Humidity offset 0 10 0 RH W AV 6 Outside_Temp Outside Temperature 40 40 C or 40 104 F...

Page 11: ...VDC 0 OFF 1 ON Alarm main board BI 12 Interlock_In_Open Interlock input open 0 Normal 1 Alarm BI 13 High_Hum_In_Duct High humidity level in the duct 0 Normal 1 Alarm BI 14 Input_Voltage_Low Input volt...

Page 12: ...ion_Mode Operation Mode 1 Set unit Off 2 Set unit On 3 Set unit in drain mode W MSV 3 Unit_Display_Lang Unit Display Language 1 English Default 2 French 3 Spanish W MSV 4 SP_Source Setpoint Source 1 L...

Page 13: ...range of Present_Value W Alarm 1 BV 101 OverTemp_Cont_ON1 Over temperature contact ON 1 0 Normal 1 Alarm W BV 102 Bad_Fill_Tank1 Defective filling tank 1 0 Normal 1 Alarm W BV 103 Bad_Refill_Tank1 Def...

Page 14: ...1 Burner Valve 1 0 OFF 1 ON BI 102 Burner_Fan1 Burner Fan 1 0 OFF 1 ON BI 103 Fill_Tank1 Fill Tank 1 0 OFF 1 ON BI 104 Drain_Tank1 Drain Tank 1 0 OFF 1 ON BI 105 Water_Level_OK1 Water Level 1 Okay 0 O...

Page 15: ...range of Present_Value W Alarm 1 BV 201 OverTemp_Cont_ON2 Over temperature contact ON 2 0 Normal 1 Alarm W BV 202 Bad_Fill_Tank2 Defective filling tank 2 0 Normal 1 Alarm W BV 203 Bad_Refill_Tank2 Def...

Page 16: ...2 Burner Valve 2 0 OFF 1 ON BI 202 Burner_Fan2 Burner Fan 2 0 OFF 1 ON BI 203 Fill_Tank2 Fill Tank 2 0 OFF 1 ON BI 204 Drain_Tank2 Drain Tank 2 0 OFF 1 ON BI 205 Water_Level_OK2 Water Level 2 Okay 0 O...

Page 17: ...range of Present_Value W Alarm 1 BV 301 OverTemp_Cont_ON3 Over temperature contact ON 3 0 Normal 1 Alarm W BV 302 Bad_Fill_Tank3 Defective filling tank 3 0 Normal 1 Alarm W BV 303 Bad_Refill_Tank3 Def...

Page 18: ...3 Burner Valve 3 0 OFF 1 ON BI 302 Burner_Fan3 Burner Fan 3 0 OFF 1 ON BI 303 Fill_Tank3 Fill Tank 3 0 OFF 1 ON BI 304 Drain_Tank3 Drain Tank 3 0 OFF 1 ON BI 305 Water_Level_OK3 Water Level 3 Okay 0 O...

Page 19: ...range of Present_Value W Alarm 1 BV 401 OverTemp_Cont_ON4 Over temperature contact ON 4 0 Normal 1 Alarm W BV 402 Bad_Fill_Tank4 Defective filling tank 4 0 Normal 1 Alarm W BV 403 Bad_Refill_Tank4 Def...

Page 20: ...4 Burner Valve 4 0 OFF 1 ON BI 402 Burner_Fan4 Burner Fan 4 0 OFF 1 ON BI 403 Fill_Tank4 Fill Tank 4 0 OFF 1 ON BI 404 Drain_Tank4 Drain Tank 4 0 OFF 1 ON BI 405 Water_Level_OK4 Water Level 4 Okay 0 O...

Page 21: ...F 38400 OFF ON 76800 ON ON Please note that you must restart the unit in order for a change of baud rate to take effect Configurable BACnet Properties The following four BACnet properties are configur...

Page 22: ...gly If the answer to Question 2 is no there is no MS TP MAC address 0 then you can start up the NEPICSKG with the dip switch 1 in the OFF operational position In this mode the factory settings are in...

Page 23: ...e care must be taken in setting the MS TP MAC address and Max_Master property First the MAC address must be unique on the entire MS TP network However having a unique MAC address and a high baud rate...

Page 24: ...finds the right one to pass the token to As a general guideline the most efficient set up for an MS TP network is one in which the units are consecutively numbered starting at MAC address 0 and all ha...

Page 25: ...SKG Steam Humidifier BACnet Communication Module User Guide 23 Personal notes...

Page 26: ...nal Environmental Products Ltd 400 Bd Lebeau Montreal Qc H4N 1R6 CANADA www neptronic com Toll free in North America 1 800 361 2308 Tel 1 514 333 1433 Fax 1 514 333 3163 Customer service Fax 514 333 1...

Reviews: