SKG Steam Humidifier
BACnet® Communication Module User Guide
13
SKG Humidifier Object Table
For tank 2:
type inst Object_Name
Description
range of Present_Value
W?
AI
201
Water_Temp2
Water Temperature 2
0-260 °C or 32-500 °F
AI
202
Chimney_Temp2
Chimney Temperature 2
0-260 °C or 32-500 °F
AI
203
Water_Level2
Water level 2
0-120%
AI
204
Burner_Demand2
Burner Demand 2
0.0 - 100.0%
AI
205
Op_Timer_Total2
Operation Timer 2 (Total
time)
1-1677215Hrs
AI
206
Op_Timer2
Operation Timer 2
1-5000Hrs
AI
207
Delay_Autodrain2
Delay until Auto-drain 2
1-100Hrs
AI
208
Foam_Probe_Sensr2
Foam Probe Sensor 2
0-255
AI
209
Burner_Fan_Speed2
Burner Fan Speed 2
0-1000Hz
type inst Object_Name
Description
range of Present_Value
W?
AV
201
Water_Temp_Off2
Water Temperature offset
2
±0-20 °C or ±0-40 °F
W
AV 202 Chimney_Temp_Off2 Chimney
Temperature
offset 2
±0-20 °C or ±0-40 °F
W
AV
203
Water_Level_Off2
Water Level offset 2
±0-20%
W
type inst Object_Name
Description
range of Present_Value
W?
-- -- --
Alarm
1:
-
BV
201
OverTemp_Cont_ON2
Over temperature contact
ON 2
0=Normal, 1=Alarm
W
BV
202
Bad_Fill_Tank2
Defective filling tank 2
0=Normal, 1=Alarm
W
BV 203 Bad_Refill_Tank2
Defective refill tank 2(too
long)
0=Normal, 1=Alarm
W
BV
204
Bad_Drain_Tank2
Defective draining tank 2
0=Normal, 1=Alarm
W
BV
205
Bad_Burner_Fan2
Defective Burner Fan 2
0=Normal, 1=Alarm
W
BV
206
Bad_Burner_Gas2
Defective Burner Gas
2(Locked)
0=Normal, 1=Alarm
W
BV
207
Input_Volt_Low2
Input voltage 2 too low
0=Normal, 1=Alarm
W
BV
208
Power_Fuse_Open2
Power Fuse 2 open
(24VAC)
0=Normal, 1=Alarm
W
-- -- --
Alarm
2:
-
BV
209
Tank_Sens_Bad2
Tank sensor 2 defective
0=Normal, 1=Alarm
W
BV
210
Chim_Sens_Bad2
Chimney sensor 2
defective
0=Normal, 1=Alarm
W
BV
211
H2OLvl_Prb_Bad2
Water level probe 2 defect
0=Normal, 1=Alarm
W
BV
212
Foam_Sens_ON2
Foam Sensor 2 ON
0=Normal, 1=Alarm
W
BV
213
OverFlow_DripPan2
Over Flow, Drip Pan 2
0=Normal, 1=Alarm
W
BV
214
Tank_Temp_Low2
Tank temper. 2 Too low
(freeze)
0=Normal, 1=Alarm
W
BV
215
Tank_Temp_Hi2
Tank temperature 2 too
high
0=Normal, 1=Alarm
W
BV
216
Chimney_Temp_Hi2
Chimney temperature 2
too high
0=Normal, 1=Alarm
W