SKG Steam Humidifier
BACnet® Communication Module User Guide
6
Objects
Binary Inputs
property
value
W?
Object_Identifier see
Object Table
Object_Name see
Object Table
Object_Type 3
Present_Value see
Object Table
Description see
Object Table
Status_Flags If
the
fault
bit is set, it indicates that the Present_Value is
unavailable and is unreliable
Event_State If
the
fault
bit of the Status_Flags is set, this property’s value is
fault
, otherwise it’s
normal
Reliability If
the
fault
bit of the Status_Flags is set, this property’s value is
unreliable_other
, otherwise it’s
no_fault_detected
Out_of_Service Always
normal
Polarity see
Object Table
Active_Text see
Object Table
Inactive_Text see
Object Table
Binary Values
property
value
W?
Object_Identifier see
Object Table
Object_Name see
Object Table
Object_Type 5
Present_Value see
Object Table
W
Description see
Object Table
Status_Flags If
the
fault
bit is set, it indicates that the Present_Value is
unavailable and is unreliable
Event_State If
the
fault
bit of the Status_Flags is set, this property’s value is
fault
, otherwise it’s
normal
Reliability If
the
fault
bit of the Status_Flags is set, this property’s value is
unreliable_other
, otherwise it’s
no_fault_detected
Out_of_Service Always
normal
Polarity see
Object Table
Active_Text see
Object Table
Inactive_Text see
Object Table