4.2.42 Clean cycle
The time duration for a cleaning cycle.
ESC
OK
CleanCycle
1/1
Tch = 03:00s
Tpu = 02:00s
On = 1
Cnt = 0
Tch: Vacuum building time (Charge time). Default is 3 seconds.
Tpu: Clean pulse time. Default is 2 seconds.
On: Number of cleaning pulses. Default is 1 pulse. Note! Minimum
value = 1.
Cnt = 0. Elapsed cleaning cycles.
Note! If On is set to 0, no filter cleaning is performed.
5
Automatic bin emptying function
5.1
AEB-Flap Valve settings
5.1.1
Hardware
•
The AEB-Flap Valve controlled by the V11 TVFD (SLV) Solenoid Lower Valve.
•
The duct isolation valve controlled by the V12 TVFD (SUV) Solenoid Upper Valve.
5.1.2
PLC Settings
1.
Presep Switch = Off (standard setting).
2.
AEB-TVFD Switch = On (standard setting).
3.
TVFDAdv Switch = Off (standard setting).
NOTE!
Presep overrides 2 above.
NOTE!
If TVFDAdv is activated (Switch = On), TVFDAdv overrides 1 and 2 above.
5.1.3
Timer Settings
BinOpnTm
TL = Delay time to let the motor decrease speed and the TVFD Solenoid Upper Valve to
close a duct isolation valve before bin emptying starts. The default is 5 seconds.
TH = Emptying Time. The default is 5 seconds.
PresepTm
TL = Delay to let the bin lid to close before the motor increases speed and the TVFD
Solenoid Upper Valve to open a duct isolation valve. The default is 5 seconds.
TH = Time delay to the next possible emptying sequence. The default is 5 seconds.
5.2
Simple TVFD Valve Settings
5.2.1
Hardware
Simple TVFD Valve controlled by the V11 TVFD (SLV) Solenoid Lower Valve and the V12
TVFD (SUV) Solenoid Upper Valve.
5.2.2
PLC Settings
1.
Presep (Softkey) = Off (standard setting).
2.
AEB-TVFD (Softkey) =Off (standard setting=On).
3.
TVFDAdv (Softkey) = Off (standard setting).