FlexPAK 800/1000
25
EN
4.2.9
Presep
Menu for activating automatic emptying of two preseparators. This cannot be used
together with TVFD. Presep activates PresepTm to control the TVFD Solenoid Upper Valve
(SUV). It uses BinOpnTm to control the TVFD Solenoid Lower Valve (SLV).
ESC
OK
Presep
1/1
Switch = Off
Switch=Off is the default setting; Presep is deactivated and TFVD is
activated.
To activate Presep, set Switch=On.
4.2.10 MFDPS-Wr
Menu for setting the Main Filter Differential Pressure Sensor Warning (MFDPS-Wr) delay
timer. When the Main Filter Differential Pressure Sensor signal disappears, MFDPS-Wr is
activated, and the delay timer has expired, the Main Filter Clogged warning message is
activated. See Section
‘3.2.2 Warning! Main Filter Clogged’.
ESC
OK
MFDPS-Wr
1/1
T = 00:08m
Ta = 00:00m
T=10:00m Time before MFDPS-Wr is activated. The default is 10
minute.
Ta=00:00 The elapsed time since the MFDPS signal disappeared.
4.2.11 MFDPS-FC
Menu for setting the Main Filter Differential Pressure Sensor Filter Cleaning (MFDPS-FC)
delay timer. When the Main Filter Differential Pressure Sensor signal disappears, MFDPS-
FC is activated, and the delay timer for MFDPS-FC has expired, it activates automatic filter
cleaning if DPFClean is activated, see Section
‘4.2.40 DPFClean’
. If PSIFC is set to ‘On’, the
filter cleaning sequence will not be activated
ESC
OK
MFDPS-FC
1/1
T = 01:00m
Ta = 00:00m
T=01:00m: Time before MFDPS-FC is activated. The default setting is 1
minute.
Ta=00:00: The elapsed time since the MFDPS signal disappeared.
4.2.12 BLI-Empt
Menu for setting the BLI emptying delay time for the bin level indicator. This function is
only available when LiAuto is set to ‘On’, see section
‘4.2.20 LiAuto’
.
When the BLI signal disappears, the BLI-Empt delay timer is activated, when the timer
elapses, the timer activates the dust bin emptying sequence with either the AEB - Flap
Valve, simple TVFD, Advance TVFD or Preseparator.
If AEB-TVFD is set to ‘On’ , in other words, the AEB-Flap Valve is chosen, the bin emptying
sequence is interlocked when PSIFC is set to ‘On’. See Section
‘4.2.32 PSIFC’
.
ESC
OK
BLI-Empt
1/1
T = 10:00s
Ta = 00:00s
T=10:00m: Time before BLI-Empt is activated. The default is 30 minutes.
Ta=00:00: The elapsed time since the BLI-Wr warning message was
activated.