FlexPAK 800/1000
EN
26
4.2.13 BLI-Wr
Menu for setting the delay time for the Bin Level Indicator warning message. When the
BLI signal disappears, the BLI-Wr timer is activated. When the timer elapses, the message
‘Warning! Dustbin Full’ is activated, see Section
‘3.2.3 Dustbin Full’
.
ESC
OK
BLI-Wr
1/1
T = 12:00m
Ta = 00:00m
T=12:00m: Time before message “Warning! Dustbin Full’ is activated.
Default is 12 minutes.
Ta=00:00: Elapsed time since the BLI-sensor was activated.
4.2.14 AEBTme
Menu for Automatic Emptying of the collector Bin, interval Timer settings. This function
is only available when BinAuto is set to ‘On’, see Section
‘4.2.19 BinAuto’
. When AEBTme
elapses, it activates the dust bin emptying sequence with either the AEB - Flap Valve,
simple TVFD, Advance TVFD or Preseparator.
ESC
OK
AEBTmr
1/1
TH = 01:00s
TL = 60:00m
Ta = 00:00m
TH=01:00s: Do not change the default setting of 1 second.
TL=60:00m: The amount of time between emptying cycles. The default
setting is 60 minutes.
Ta=00:00: The elapsed time since the last AEB was activated.
4.2.15 BinOpnTm
Menu for AEB-Flap Valve, simple TVFD and Preseparator opening cycle settings. The values
for ‘TL’ and ‘TH’ depend on which function is being used. See Section
‘5 Automatic bin
emptying function’.
ESC
OK
BinOpnTm 1/1
TH = 05:00s
TL = 03:00s
Ta = 00:00s
TH= See Section
‘5 Automatic bin emptying function’
.
TL= See Section
‘5 Automatic bin emptying function’
.
4.2.16 CFDPS-Al
Menu for setting the delay time for the Control Filter DP Sensor Alarm (CFDPS-Al). When
the Control Filter DP Sensor signal disappears, the CFDPS-Al timer is activated. When this
timer has elapsed, the unit goes into Off mode and an alarm is displayed in the PLC. See
Section
‘3.3.8 Alarm! Control Filter Clogged’
.
ESC
OK
CFDPS-Al
1/1
T = 5:00s
Ta = 00:00s
T=05:00s: Time before CFDPS-Al is activated. The default setting is 5
seconds.
Ta=00:00: The elapsed time since the CF-DPS signal disappeared.
4.2.17 TVFDAdv
Menu for activating the advanced TVFD where an upper and lower position sensor are used
to detect TVFD valve position.
ESC
OK
TVFDAdv
1/1
Switch = Off
Switch=Off is the default setting; advanced TVFD is deactivated. Simple
TVFD, AEB or Preseparator is activated.
To activate advanced TVFD, set Switch=On.