NCB Service Manual 73
Version 1.0
4.9.14
Circulation Pump
Item
Description
Function
1.
Provides internal or external water circulation.
2.
Internal circulation minimises the effects of temperature fluctuations. External circulation
quickly delivers hot water to taps and results in water conservation.
Fault
Unable to detect or measure water flow.
Symptoms
1.
Water inside the boiler system freezes.
2.
Water temperature fluctuations when the boiler is set to internal recirculation.
3.
Hot water takes a long time to be available at taps when the boiler is set to external
recirculation.
Error codes
-
Diagnostics
1.
Visual inspection: Check the circulation pump connection wire.
2.
Check the water filter for obstructions.
3.
Voltage test: Test the voltage meets the specifications shown below.
Testing/inspection
information
YELLOW-WHITE
ON: AC 230 V
OFF: 0 V