50 NCB Service Manual
Version 1.0
Item
Description
Display
(N)
CH burner
OFF temp
During heating, the boiler turns off the burner when the supply
temperature meets or exceeds the burner OFF temperature.
Range
Default
0 to 30
℃
2
℃
Eg.) at 2
℃
(O)
CH burner
ON temp
During heating, the boiler turns on the burner when the supply
temperature is below the burner ON temperature.
Range
Default
1-30
℃
3
℃
Eg.) at 6
℃
(P)
Supply
absolute
MAX set
point
This menu changes the maximum supply temperature range when
Supply Control mode is used. When configuring Custom mode in
Outdoor Reset Control mode, the supply temperature changes based on
the supply absolute MAX temperature range.
Range
Default
(Minimum set point + 20
℃
) to 90
℃
90
℃
Eg.) at 82
℃
(in Supply
control mode)
(Q)
Supply
absolute
MIN set
point
This menu changes the minimum supply temperature range when
Supply Control mode is used. When configuring Custom mode in
Outdoor Reset Control mode, the supply temperature changes based on
the supply absolute MIN temperature range.
Range
Default
25
℃
to (Maximum point - 20
℃
) 40
℃
Eg.) at 40
℃
(R)
Return
absolute
MAX set
point
This menu changes the maximum return temperature range when the
Return Control mode is used. When configuring Custom mode in
Outdoor Reset Control mode, the return temperature changes based on
the return absolute MAX temperature range.
Range
Default
(Minimum set point + 10
℃
] to 70
℃
65
℃
Eg.) at 65
℃
(S)
Return
absolute
MIN set
point
This menu changes the maximum return temperature range when the
Return Control mode is used. When configuring Custom mode in
Outdoor Reset Control mode, the return temperature changes based on
the return absolute MIN temperature range.
Range
Default
20
℃
to (Maximum set point - 10
℃
) 30
℃
Eg.) at 30
℃
Summary of Contents for NCB-24LSWE
Page 16: ...14 NCB Service Manual Version 1 0 NCB 24 28 34LSWE...
Page 17: ...NCB Service Manual 15 Version 1 0 NCB 40LSWE...
Page 18: ...16 NCB Service Manual Version 1 0 NCB 40LSWE...
Page 60: ...58 NCB Service Manual Version 1 0 4 8 Electrical Diagnostic Contacts and Wiring Diagram...
Page 87: ...NCB Service Manual 85 Version 1 0 Scenario2...
Page 120: ...118 NCB Service Manual Version 1 0 5 2 24 782Error Error occurrence conditions and check items...
Page 140: ...138 NCB Service Manual Version 1 0 Memo...
Page 141: ...NCB Service Manual 139 Version 1 0 Memo...
Page 142: ...140 NCB Service Manual Version 1 0 Memo...