NCB Service Manual 103
Version 1.0
5.2.11
Error 110
Error Conditions and Checklist
Error
Description
E110
Air pressure error
The system detects the air pressure and the fan speed and displays 110E on the front panel in the
following cases:
1.
When the initial fan auto-adjustment is not performed.
2.
When boiler reaches 95% of maximum heating capacity during combustion and the APS is not rated
at the standard value.
Checklist
1.
Check the venturi (burner) hole for obstruction.
2.
Check the condensation drain line and drain for obstruction.
3.
Check the flue and exhaust are installed correctly and have adequate clearance. (The circulation of
exhaust gas generates noise.)
4.
Check if the air supply/exhaust flue is obstructed (rainwater may accumulate inside incorrectly
installed air supply/exhaust pipes).
5.
Check for a faulty air pressure sensor or PCB.
6.
Ensure that the vents slope downwards towards the unit for proper condensate drainage.
7.
Ensure the internal damper moves freely and is not obstructed.
Summary of Contents for NCB-24LSWE
Page 16: ...14 NCB Service Manual Version 1 0 NCB 24 28 34LSWE...
Page 17: ...NCB Service Manual 15 Version 1 0 NCB 40LSWE...
Page 18: ...16 NCB Service Manual Version 1 0 NCB 40LSWE...
Page 60: ...58 NCB Service Manual Version 1 0 4 8 Electrical Diagnostic Contacts and Wiring Diagram...
Page 87: ...NCB Service Manual 85 Version 1 0 Scenario2...
Page 120: ...118 NCB Service Manual Version 1 0 5 2 24 782Error Error occurrence conditions and check items...
Page 140: ...138 NCB Service Manual Version 1 0 Memo...
Page 141: ...NCB Service Manual 139 Version 1 0 Memo...
Page 142: ...140 NCB Service Manual Version 1 0 Memo...