NX25/NX15 Troubleshooting Manual
Responding to alarms
Page 1-26
Issue 5.0 2016-05-06
Module #: External
Disable Active
This alarm indicates the PDM cable has been disconnected from
the front of the RF power module, which causes the power
module to be immediately disabled. If this alarm occurs, reconnect
the PDM drive cable associated with that RF power module. If the
problem persists, swap the affected RF power module with an
operational RF power module’s position. If the fault follows the RF
power module, replace the RF power module (see
reinstalling RF power modules” on page 1-45
). If the fault remains
with the position, try replacing the PDM drive cable. If the alarm
persists, replace the source of the
PDM signal (see
Distribution PWB replacement” on page 1-62
).
Module #: High B+
Voltage
This alarm indicates the RF power module's B+ meter has
exceeded
450 V
.
If high B+ voltage alarms are present for other
system components, see the troubleshooting action for those
alarms. If the alarm persists, replace the RF power module (see
“Removing and reinstalling RF power modules” on page 1-45
).
Module #: High DC
Current
This alarm indicates that the RF power module's DC Current
meter has exceeded 22 A, or the RF power module's peak DC
current has exceeded the threshold applied to the
microcontroller's comparator. This alarm will immediately disable
the RF power module, and latch it off. If this alarm occurred in
conjunction with an Overmodulation alarm, follow the
troubleshooting action for that alarm. Otherwise, try resetting the
alarms using the AUI. If the alarm persists, replace the RF power
module. If the alarm clears, troubleshoot the suspect RF power
module for RF FET failures (see
If the alarm persists, suspect that the
associated RF relay is not opening, or the associated gas
discharge tube has activated.
Module #: High PA
Voltage
This alarm occurs because of one of two conditions: (1) the PA
voltage is at least 10% above the product of the B+ level and the
PDM duty cycle; or (2) the PA voltage has exceeded 95% of the
B+ value for more than 50 ms. The alarm is latching and will
cause the associated RF power module to disable itself. This
alarm generally indicates that a modulator FET has failed. See
“Troubleshooting RF power modules” on page 1-48
to determine
whether to replace the affected RF power module or to repair
damaged parts.
Alarm (with Prefix)
Description and Troubleshooting Action
Summary of Contents for NX15
Page 2: ......
Page 4: ......
Page 8: ...NX25 NX15 Troubleshooting Manual Page viii Issue 5 0 2016 05 06...
Page 78: ...NX25 NX15 Troubleshooting Manual Responding to alarms Page 1 70 Issue 5 0 2016 05 06...
Page 96: ...NX25 NX15 Troubleshooting Manual Detailed Circuit Descriptions Page 2 18 Issue 5 0 2016 05 06...
Page 104: ...NX25 NX15 Troubleshooting Manual Parts Lists Page 3 8 Issue 5 0 2016 05 06...
Page 216: ...NX25 NX15 Troubleshooting Manual Wiring connector lists Page 4 12 Issue 5 0 2016 05 06...
Page 222: ...NX25 NX15 Troubleshooting Manual Reading Electrical Schematics Page 5 6 Issue 5 0 2016 05 06...
Page 250: ...Issue 5 0 2016 05 06 MD 1 Figure MD 1 NX15 NX25 Transmitter Front View...
Page 251: ...Issue 5 0 2016 05 06 MD 2 Figure MD 2 NX15 NX25 Transmitter Rear View...
Page 254: ...Issue 5 0 2016 05 06 MD 5 Figure MD 5 NAE96C 01 Control Exciter Panel...
Page 257: ...Issue 5 0 2016 05 06 MD 8 Figure MD 8 NAPI106 Remote Interface PWB...
Page 261: ...Issue 5 0 2016 05 06 MD 12 Figure MD 12 NAPI98 RF Drive Distribution PWB...
Page 263: ...Issue 5 0 2016 05 06 MD 14 Figure MD 14 NAX243A B Distribution Assembly...
Page 265: ...Issue 5 0 2016 05 06 MD 16 Figure MD 16 NAPA34A Modulator Power Amplifier PWB Front View...
Page 267: ...Issue 5 0 2016 05 06 MD 18 Figure MD 18 Fan Tray Assembly 207 8133...
Page 268: ...Issue 5 0 2016 05 06 MD 19 Figure MD 19 Voltage Probe 207 6111...
Page 269: ...Issue 5 0 2016 05 06 MD 20 Figure MD 20 Current Probe 207 6213 04...
Page 270: ...Issue 5 0 2016 05 06 MD 21 Figure MD 21 NAFP106B 02 Directional Coupler A1 DETAIL...
Page 273: ......