NX25/NX15 Troubleshooting Manual
Responding to alarms
Issue 5.0 2016-05-06
Page 1-31
Rack #: High B+ Voltage
If the B+ voltage is more than 10 V above the B+ voltage set point,
the rack interface will attempt to decrease the rectifier’s output. If
the rack interface reaches the bottom of its adjustment range and
the B+ voltage remains 10 V or more above the B+ voltage
setpoint for more than 15 seconds, this alarm will occur. The
alarm will clear when the B+ voltage changes to within 10 V of the
B+ voltage setpoint, or the B+ power supply is inhibited (by turning
RF Off, for example). If the alarm persists while the transmitter is
producing RF power, check the ac mains voltages and verify they
are within ±10% of the nominal voltage for which the transformer
is tapped. Verify the mains transformer is tapped correctly (see
“Installing the power transformer” on page 3-1
in the Installation
Manual). If the alarm persists, replace the rectifier assembly (see
“SCR Rectifier Inspection/Replacement” on page 1-66
) or the rack
interface PWB
“Rack Interface PWB replacement” on
Rack #: High Rectifier
Temperature
This alarm indicates that the rectifier heatsink temperature has
exceeded 100 degrees Celsius. The exciter should reduce the
transmitter’s output power before this alarm occurs (see “Exciter:
High Temperature Foldback” alarm). The alarm will clear once the
rectifier heatsink temperature drops below 99.5 degrees Celsius.
The alarm indicates that there is excessive dissipation in the
rectifier, likely due to high current draw. This may be due to the
secondary voltage of the power transformer being lower than
specified. Verify the mains transformer is tapped correctly (see
“Installing the power transformer” on page 3-1
in the Installation
Manual). If the alarm persists, replace the rectifier assembly (see
“SCR Rectifier Inspection/Replacement” on page 1-66
).
Rack #: Low AC Voltage
This alarm indicates the rack interface’s Ac Sample meter is
below 256 V. The alarm clears when the sample rises above this
voltage. It is caused by an improperly tapped transformer, or a
transient on the ac mains. Verify the mains transformer is tapped
correctly (see
“Installing the power transformer” on page 3-1
in the
Installation Manual). If so, monitor the ac mains for transient
conditions when this alarm occurs. See
Alarm (with Prefix)
Description and Troubleshooting Action
Summary of Contents for NX15
Page 2: ......
Page 4: ......
Page 8: ...NX25 NX15 Troubleshooting Manual Page viii Issue 5 0 2016 05 06...
Page 78: ...NX25 NX15 Troubleshooting Manual Responding to alarms Page 1 70 Issue 5 0 2016 05 06...
Page 96: ...NX25 NX15 Troubleshooting Manual Detailed Circuit Descriptions Page 2 18 Issue 5 0 2016 05 06...
Page 104: ...NX25 NX15 Troubleshooting Manual Parts Lists Page 3 8 Issue 5 0 2016 05 06...
Page 216: ...NX25 NX15 Troubleshooting Manual Wiring connector lists Page 4 12 Issue 5 0 2016 05 06...
Page 222: ...NX25 NX15 Troubleshooting Manual Reading Electrical Schematics Page 5 6 Issue 5 0 2016 05 06...
Page 250: ...Issue 5 0 2016 05 06 MD 1 Figure MD 1 NX15 NX25 Transmitter Front View...
Page 251: ...Issue 5 0 2016 05 06 MD 2 Figure MD 2 NX15 NX25 Transmitter Rear View...
Page 254: ...Issue 5 0 2016 05 06 MD 5 Figure MD 5 NAE96C 01 Control Exciter Panel...
Page 257: ...Issue 5 0 2016 05 06 MD 8 Figure MD 8 NAPI106 Remote Interface PWB...
Page 261: ...Issue 5 0 2016 05 06 MD 12 Figure MD 12 NAPI98 RF Drive Distribution PWB...
Page 263: ...Issue 5 0 2016 05 06 MD 14 Figure MD 14 NAX243A B Distribution Assembly...
Page 265: ...Issue 5 0 2016 05 06 MD 16 Figure MD 16 NAPA34A Modulator Power Amplifier PWB Front View...
Page 267: ...Issue 5 0 2016 05 06 MD 18 Figure MD 18 Fan Tray Assembly 207 8133...
Page 268: ...Issue 5 0 2016 05 06 MD 19 Figure MD 19 Voltage Probe 207 6111...
Page 269: ...Issue 5 0 2016 05 06 MD 20 Figure MD 20 Current Probe 207 6213 04...
Page 270: ...Issue 5 0 2016 05 06 MD 21 Figure MD 21 NAFP106B 02 Directional Coupler A1 DETAIL...
Page 273: ......