NX25/NX15 Troubleshooting Manual
Responding to alarms
Page 1-32
Issue 5.0 2016-05-06
Rack #: Low B+ Voltage
If the B+ voltage falls to more than 15% below the B+ voltage set
point, the rack interface will attempt to turn up the rectifier output
voltage. If the rack interface reaches the top of its adjustment
range and the B+ voltage remains 25% or more below the B+
voltage setpoint for more than two (2) seconds, this alarm will
occur. The alarm will clear when the B+ voltage changes to within
25% of the B+ voltage setpoint, or the B+ power supply is inhibited
(by turning RF Off, for example). If the alarm persists while the
transmitter is producing RF power, check the main B+ fuse and
replace as necessary. If the fuse is OK or the alarm persists,
check the ac mains voltages and verify they are within ±10% of
the nominal voltage for which the transformer is tapped. Verify the
mains transformer is tapped correctly (see
in the Installation Manual).
If the alarm
persists, replace the rectifier assembly (see
Inspection/Replacement” on page 1-66
) or the rack interface PWB
“Rack Interface PWB replacement” on page 1-64
).
Rack #: Power Module #
Not Responding
This alarm indicates that the rack interface PWB is not receiving a
response from the associated RF power module. Try swapping
the affected RF power module with an RF power module in
another location. If the alarm follows the RF power module,
replace the RF power module
).
Rack #: Rectifier Fan 1
(or 2) Fail
This alarm occurs if the speed of one of the SCR rectifier’s cooling
fans is below 3000 RPM for longer than 15 seconds. Inspect the
affected fan and, if necessary, replace it (see
Inspection/Replacement” on page 1-66
).
Rack #: +15 V Fail
This alarm occurs if the +15 V rail is outside the acceptable range
(12 V to 18 V). Disconnect the DC output of both +15 V power
supplies, and measure the voltage of each. If the output voltage of
either power supply measures outside of the acceptable range,
replace the affected power supply. If both power supplies measure
within the acceptable range, replace the rack interface PWB (see
“Rack Interface PWB replacement” on page 1-64
Alarm (with Prefix)
Description and Troubleshooting Action
Summary of Contents for NX15
Page 2: ......
Page 4: ......
Page 8: ...NX25 NX15 Troubleshooting Manual Page viii Issue 5 0 2016 05 06...
Page 78: ...NX25 NX15 Troubleshooting Manual Responding to alarms Page 1 70 Issue 5 0 2016 05 06...
Page 96: ...NX25 NX15 Troubleshooting Manual Detailed Circuit Descriptions Page 2 18 Issue 5 0 2016 05 06...
Page 104: ...NX25 NX15 Troubleshooting Manual Parts Lists Page 3 8 Issue 5 0 2016 05 06...
Page 216: ...NX25 NX15 Troubleshooting Manual Wiring connector lists Page 4 12 Issue 5 0 2016 05 06...
Page 222: ...NX25 NX15 Troubleshooting Manual Reading Electrical Schematics Page 5 6 Issue 5 0 2016 05 06...
Page 250: ...Issue 5 0 2016 05 06 MD 1 Figure MD 1 NX15 NX25 Transmitter Front View...
Page 251: ...Issue 5 0 2016 05 06 MD 2 Figure MD 2 NX15 NX25 Transmitter Rear View...
Page 254: ...Issue 5 0 2016 05 06 MD 5 Figure MD 5 NAE96C 01 Control Exciter Panel...
Page 257: ...Issue 5 0 2016 05 06 MD 8 Figure MD 8 NAPI106 Remote Interface PWB...
Page 261: ...Issue 5 0 2016 05 06 MD 12 Figure MD 12 NAPI98 RF Drive Distribution PWB...
Page 263: ...Issue 5 0 2016 05 06 MD 14 Figure MD 14 NAX243A B Distribution Assembly...
Page 265: ...Issue 5 0 2016 05 06 MD 16 Figure MD 16 NAPA34A Modulator Power Amplifier PWB Front View...
Page 267: ...Issue 5 0 2016 05 06 MD 18 Figure MD 18 Fan Tray Assembly 207 8133...
Page 268: ...Issue 5 0 2016 05 06 MD 19 Figure MD 19 Voltage Probe 207 6111...
Page 269: ...Issue 5 0 2016 05 06 MD 20 Figure MD 20 Current Probe 207 6213 04...
Page 270: ...Issue 5 0 2016 05 06 MD 21 Figure MD 21 NAFP106B 02 Directional Coupler A1 DETAIL...
Page 273: ......