NX25/NX15 Troubleshooting Manual
Responding to alarms
Issue 5.0 2016-05-06
Page 1-15
Controller: Low RF Drive
This alarm indicates the controller's RF Drive Duty Cycle meter
has fallen below 40% for longer than 10 seconds. This alarm will
cause an exciter changeover, if automatic changeover is enabled
and the transmitter is operating on the main exciter. If there are
two exciters in the transmitter, swap exciter positions. If the alarm
follows the exciter, or there is only one exciter in the system,
replace the digital AM exciter PWB (see
). If the alarm persists, or the alarm
remains with the position, replace the control/interface PWB (see
“Control/interface PWB replacement” on page 1-60
).
Controller: Out of
Memory Reset
This alarm is only visible in the transmitter logs, and indicates the
controller automatically reset because it ran out of the memory
required to continue normal operation. If the alarm persists,
replace the control/interface PWB
).
Controller: PDM Latch
This alarm indicates that the PDM latch circuitry on the control/
interface PWB has tripped, causing the transmitter to shut down
and latch off. If automatic changeovers are enabled and the
transmitter is operating on the main exciter, an automatic
changeover will occur, and the latch will be cleared, allowing the
transmitter to return to the current preset settings. If automatic
changeovers are disabled, or if the transmitter
was
already
operating on the standby exciter when this event
occurred,
try
resetting the transmitter alarms. If the alarm persists,
press
RF
Off
, press the
Reset
button (S1) on the digital AM exciter PWB,
then press
RF On
.
If the alarm persists, check modulation levels
being applied to the selected input and verify they are as
expected. If the alarm persists, replace the digital AM exciter PWB
(see
“Digital AM exciter PWB replacement” on page 1-55
).
Controller: Power Loss
This alarm indicates that the controller lost power at the time the
event was logged. The alarm should occur concurrently with other
alarms. Follow the troubleshooting action for the associated
alarm(s). Otherwise, if the alarm persists without the presence of
other alarms, replace the control/interface PWB
interface PWB replacement” on page 1-60
).
Alarm (with Prefix)
Description and Troubleshooting Action
Summary of Contents for NX15
Page 2: ......
Page 4: ......
Page 8: ...NX25 NX15 Troubleshooting Manual Page viii Issue 5 0 2016 05 06...
Page 78: ...NX25 NX15 Troubleshooting Manual Responding to alarms Page 1 70 Issue 5 0 2016 05 06...
Page 96: ...NX25 NX15 Troubleshooting Manual Detailed Circuit Descriptions Page 2 18 Issue 5 0 2016 05 06...
Page 104: ...NX25 NX15 Troubleshooting Manual Parts Lists Page 3 8 Issue 5 0 2016 05 06...
Page 216: ...NX25 NX15 Troubleshooting Manual Wiring connector lists Page 4 12 Issue 5 0 2016 05 06...
Page 222: ...NX25 NX15 Troubleshooting Manual Reading Electrical Schematics Page 5 6 Issue 5 0 2016 05 06...
Page 250: ...Issue 5 0 2016 05 06 MD 1 Figure MD 1 NX15 NX25 Transmitter Front View...
Page 251: ...Issue 5 0 2016 05 06 MD 2 Figure MD 2 NX15 NX25 Transmitter Rear View...
Page 254: ...Issue 5 0 2016 05 06 MD 5 Figure MD 5 NAE96C 01 Control Exciter Panel...
Page 257: ...Issue 5 0 2016 05 06 MD 8 Figure MD 8 NAPI106 Remote Interface PWB...
Page 261: ...Issue 5 0 2016 05 06 MD 12 Figure MD 12 NAPI98 RF Drive Distribution PWB...
Page 263: ...Issue 5 0 2016 05 06 MD 14 Figure MD 14 NAX243A B Distribution Assembly...
Page 265: ...Issue 5 0 2016 05 06 MD 16 Figure MD 16 NAPA34A Modulator Power Amplifier PWB Front View...
Page 267: ...Issue 5 0 2016 05 06 MD 18 Figure MD 18 Fan Tray Assembly 207 8133...
Page 268: ...Issue 5 0 2016 05 06 MD 19 Figure MD 19 Voltage Probe 207 6111...
Page 269: ...Issue 5 0 2016 05 06 MD 20 Figure MD 20 Current Probe 207 6213 04...
Page 270: ...Issue 5 0 2016 05 06 MD 21 Figure MD 21 NAFP106B 02 Directional Coupler A1 DETAIL...
Page 273: ......