NX25/NX15 Troubleshooting Manual
Responding to alarms
Issue 5.0 2016-05-06
Page 1-41
Responding to alarms
Controller: External PDM Inhibit
The external PDM inhibit is wired to the control/interface PWB.
A
Controller: External PDM Inhibit
alarm indicates that an external PDM inhibit command is
present. The alarm could be caused by an short circuit in the external wiring path to the control/
interface PWB or a fault in the switching circuitry on the control/interface PWB. Troubleshoot as
follows:
1. If the control/interface PWB’s shorting jumper E2 is in the
INT
position (shorting pins 2
and 3), verify the dc voltage between J6-4 and ground on the control/interface PWB is
approximately 15 V. This signifies there is no external PDM inhibit command.
2. If the control/interface PWB’s shorting jumper E2 is in the
EXT
position (shorting pins 1
and 2), verify the dc voltage between J6-3 and J6-4 on the control/interface PWB is 0 V. This
signifies there is no external PDM inhibit command.
are met, suspect the control/interface PWB and if
necessary, replace it (see
“Control/interface PWB replacement” on page 1-60
).
Controller: Interlock Open
A
Controller: Interlock Open
alarm indicates an external interlock is open. The transmitter’s RF
output will be inhibited.
The external interlock input is wired to the control/interface PWB by the end user and triggered by
the conditions that they set (e.g., the state of the door to the transmitter room).
1. Gain access to the control/exciter panel (A11) (see
) by opening the
control cabinet’s front door. The door is not latched and just swings open to the left.
2. Connect a digital multimeter (set to measure dc) between J6-2 of the control/interface PWB
and ground.
3. If 15 V is present on J6-2, the external interlock circuit is intact and the probable cause of the
alarm is a defective monitoring circuit. Suspect the control/interface PWB and if necessary,
replace it (see
“Control/interface PWB replacement” on page 1-60
).
4. If 15 V is not present on J6-2, measure the voltage between J6-5 (external 15 V) of the
control/interface PWB and ground, then between J6-1 (+15 V) and ground.
Summary of Contents for NX15
Page 2: ......
Page 4: ......
Page 8: ...NX25 NX15 Troubleshooting Manual Page viii Issue 5 0 2016 05 06...
Page 78: ...NX25 NX15 Troubleshooting Manual Responding to alarms Page 1 70 Issue 5 0 2016 05 06...
Page 96: ...NX25 NX15 Troubleshooting Manual Detailed Circuit Descriptions Page 2 18 Issue 5 0 2016 05 06...
Page 104: ...NX25 NX15 Troubleshooting Manual Parts Lists Page 3 8 Issue 5 0 2016 05 06...
Page 216: ...NX25 NX15 Troubleshooting Manual Wiring connector lists Page 4 12 Issue 5 0 2016 05 06...
Page 222: ...NX25 NX15 Troubleshooting Manual Reading Electrical Schematics Page 5 6 Issue 5 0 2016 05 06...
Page 250: ...Issue 5 0 2016 05 06 MD 1 Figure MD 1 NX15 NX25 Transmitter Front View...
Page 251: ...Issue 5 0 2016 05 06 MD 2 Figure MD 2 NX15 NX25 Transmitter Rear View...
Page 254: ...Issue 5 0 2016 05 06 MD 5 Figure MD 5 NAE96C 01 Control Exciter Panel...
Page 257: ...Issue 5 0 2016 05 06 MD 8 Figure MD 8 NAPI106 Remote Interface PWB...
Page 261: ...Issue 5 0 2016 05 06 MD 12 Figure MD 12 NAPI98 RF Drive Distribution PWB...
Page 263: ...Issue 5 0 2016 05 06 MD 14 Figure MD 14 NAX243A B Distribution Assembly...
Page 265: ...Issue 5 0 2016 05 06 MD 16 Figure MD 16 NAPA34A Modulator Power Amplifier PWB Front View...
Page 267: ...Issue 5 0 2016 05 06 MD 18 Figure MD 18 Fan Tray Assembly 207 8133...
Page 268: ...Issue 5 0 2016 05 06 MD 19 Figure MD 19 Voltage Probe 207 6111...
Page 269: ...Issue 5 0 2016 05 06 MD 20 Figure MD 20 Current Probe 207 6213 04...
Page 270: ...Issue 5 0 2016 05 06 MD 21 Figure MD 21 NAFP106B 02 Directional Coupler A1 DETAIL...
Page 273: ......