NX25/NX15 Troubleshooting Manual
Responding to alarms
Page 1-14
Issue 5.0 2016-05-06
Controller: Internal
Watchdog Reset
This alarm will only be seen in transmitter logs, and indicates that
the controller was reset by its internal watchdog. If this alarm
persists, replace the control/interface PWB (see
).
Controller: Interlock
Open
This alarm indicates that the external interlock input wired to the
control/interface PWB is open. An alarm will be triggered by user-
set conditions (e.g., the state of the door to the transmitter room).
When this alarm occurs, the transmitter immediately inhibits the
PDM and the transmitter's output power drops to 0 W. If this
condition persists for more than 10 seconds, the transmitter will
inhibit the RF power modules, fans and B+ power supply. The
transmitter will automatically recover when the condition is
cleared. With the transmitter set to RF Off, disconnect the
interlock circuit from the transmitter. Measure the impedance of
the interlock circuit. If the impedance measures open circuit (high
impedance) the interlock is open, and it will be necessary to locate
the external device that is causing this condition. If the impedance
does not measure open circuit, verify the interlock circuitry has
been properly configured. If the interlock circuitry is properly
configured, make a temporary jumper and use it to short out the
interlock circuit. If the alarm disappears, the transmitter is
operating as expected and it will be necessary to locate the
external device that is causing this condition. If the alarm persists,
replace the control PWB. See
“Controller: Interlock Open” on
Controller: Jumped to
Bootloader
This alarm is only visible in the transmitter logs, and indicates the
controller was reset due to performing a firmware upgrade. If this
alarm is occurring when a firmware upgrade is not being
performed, replace the control/interface PWB
(see
interface PWB replacement” on page 1-60
).
Controller: Low Battery
This alarm occurs if the voltage of the backup battery has fallen
below an acceptable level. Replace the battery (BT1) on the
control/interface PWB while ac power is on. If the alarm persists
after replacing the battery, replace the control/interface PWB (see
“Control/interface PWB replacement” on page 1-60
).
Alarm (with Prefix)
Description and Troubleshooting Action
Summary of Contents for NX15
Page 2: ......
Page 4: ......
Page 8: ...NX25 NX15 Troubleshooting Manual Page viii Issue 5 0 2016 05 06...
Page 78: ...NX25 NX15 Troubleshooting Manual Responding to alarms Page 1 70 Issue 5 0 2016 05 06...
Page 96: ...NX25 NX15 Troubleshooting Manual Detailed Circuit Descriptions Page 2 18 Issue 5 0 2016 05 06...
Page 104: ...NX25 NX15 Troubleshooting Manual Parts Lists Page 3 8 Issue 5 0 2016 05 06...
Page 216: ...NX25 NX15 Troubleshooting Manual Wiring connector lists Page 4 12 Issue 5 0 2016 05 06...
Page 222: ...NX25 NX15 Troubleshooting Manual Reading Electrical Schematics Page 5 6 Issue 5 0 2016 05 06...
Page 250: ...Issue 5 0 2016 05 06 MD 1 Figure MD 1 NX15 NX25 Transmitter Front View...
Page 251: ...Issue 5 0 2016 05 06 MD 2 Figure MD 2 NX15 NX25 Transmitter Rear View...
Page 254: ...Issue 5 0 2016 05 06 MD 5 Figure MD 5 NAE96C 01 Control Exciter Panel...
Page 257: ...Issue 5 0 2016 05 06 MD 8 Figure MD 8 NAPI106 Remote Interface PWB...
Page 261: ...Issue 5 0 2016 05 06 MD 12 Figure MD 12 NAPI98 RF Drive Distribution PWB...
Page 263: ...Issue 5 0 2016 05 06 MD 14 Figure MD 14 NAX243A B Distribution Assembly...
Page 265: ...Issue 5 0 2016 05 06 MD 16 Figure MD 16 NAPA34A Modulator Power Amplifier PWB Front View...
Page 267: ...Issue 5 0 2016 05 06 MD 18 Figure MD 18 Fan Tray Assembly 207 8133...
Page 268: ...Issue 5 0 2016 05 06 MD 19 Figure MD 19 Voltage Probe 207 6111...
Page 269: ...Issue 5 0 2016 05 06 MD 20 Figure MD 20 Current Probe 207 6213 04...
Page 270: ...Issue 5 0 2016 05 06 MD 21 Figure MD 21 NAFP106B 02 Directional Coupler A1 DETAIL...
Page 273: ......