2-WIRE UNIVERSAL TEMPERATURE TRANSMITTER

(HART communication, intrinsically safe)

MODEL

B3HU

INSTRUCTION MANUAL

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 

contents of the package you received as outlined below.

If you have any problems or questions with the product, 

please contact M-System’s Sales Office or representatives.

 PACKAGE INCLUDES:

  Signal conditioner ......................................................... (1)

  Shortcircuit bar ............................................................ (1)

  Terminal block with CJC sensor .................................. (1)

  CD including the configuration software .................... (1)

  I/O range and tag name label sheet ............................ (1)

 MODEL NO.

Confirm Model No. marking on the product to be exactly 

what you ordered.

 INSTRUCTION MANUAL

This manual describes necessary points of caution when 

you use this product, including installation, connection and 

basic maintenance procedures.

When using this product in potentially explosive atmos-

phere or hazardous (classified) location, you have to follow 

the safety procedure to install it.  Please refer to “SAFE IN-

STALLATION MANUAL” for each type of certification.

 POINTS OF CAUTION

The following are general precautions when using this unit.  

The safety features and precautions specific to the hazard-

ous locations are explained in “Safe Installation Manual” 

for each certification.

 CONFORMITY WITH EC DIRECTIVES

• Functional  insulation  is  maintained  between  the  input 

and output.

• The equipment must be mounted inside a panel.

• The  actual  installation  environments  such  as  panel  con-

figurations, connected devices, connected wires, may affect 

the protection level of this unit when it is integrated in a 

panel system.  The user may have to review the CE require-

ments in regard to the whole system and employ additional 

protective measures to ensure the CE conformity.

 SAFETY PRECAUTION

• Before you remove the unit or mount it, turn off the power 

supply and input signal for safety.

 ENVIRONMENT

• Indoor use

• When heavy dust or metal particles are present in the air, 

install the unit inside proper housing with sufficient ven-

tilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental  (non-hazardous  location)  temperature 

must be within -40 to +85°C (-40 to +185°F) with relative 

humidity within 0 to 95% RH in order to ensure adequate 

life span and operation.

• Be sure that the ventilation slits are not covered with ca-

bles, etc.

 WIRING

• Do  not  install  cables  (input  and  output)  close  to  noise 

sources (relay drive cable, high frequency line, etc.).

• Do  not  bind  these  cables  together  with  those  in  which 

noises are present.  Do not install them in the same duct.

 AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 

satisfying complete performance described in the data 

sheet.

COMPONENT IDENTIFICATION

Body

Specifications
(side)

Safety Specifications
(for hazardous locations)

 HOW TO SEPARATE THE TERMINAL BLOCKS

When you need to separate the terminal blocks from the 

transmitter body for wiring, insert a minus driver between 

the terminal block and the housing body, pull up the driver 

and pull out the terminal block.

 RTD/RESISTANCE SHORTCIRCUIT BAR

For a RTD/resistance input with 2- or 3-wire connection, 

short across the terminals 1 and 2 with the shortcircuit bar 

included in the product package.  Remove it for other in-

puts/connection.

Terminal Block

Terminal No.

2 3

1

Shortcircuit Bar

 CJC SENSOR TERMINAL BLOCK 

For a thermocouple input, replace the Terminal  Block (4 – 5 

– 6) with the one connected with  the CJC Sensor included 

in the package.  Be careful not to separate the Sensor from 

the terminal block.  If you did, connect the CJC leg marked 

with a white dot to the terminal 5 and the other leg to the 

terminal 6.

The CJC Sensor is calibrated to a particular unit and not 

interchangeable with another.  Match the Serial No. of the 

unit and the sensor.

CJC Sensor Terminal Block

White Dot

Serial No.

For a thermocouple input, replace the Terminal 
Block (4 – 5 – 6) with the one connected with 
the CJC Sensor included in the package.
Be careful not to separate the Sensor from the
terminal block.  If you did, connect the CJC leg
marked with a white dot to the terminal 5 and 
the other leg to the terminal 6.
The CJC Sensor is calibrated to a particular 
unit and not interchangeable with another.
Match the Serial No. of the unit and the sensor.