background image

B3HU

P. 2 / 3

EM-7502-A Rev.3

Close across the terminals 1 & 2 for a resistance or RTD input.
Limited to 250 – 1100

Ω

 for HART communication.

A safety barrier must be installed for the intrinsic safety.
The safety barrier must meet the Ex-data of this unit and must be approved for the hazardous location.

*

1.

*

2.

*

3.

1

4

2

3

3

2

1

POT

DC mV

A

A

B

B

RTD & Resistance

4-wire

T/C

3-wire

2-wire

A

B

B

A

B

7

8

*

1

*

1

+

+

+

+

*

2

*

3

+

LOAD

OUTPUT

24VDC

4 – 20mADC

Hazardous Area

Safe Area

Safety Barrier

CJC

5

6

*

4

*

4. Replace the Terminal Block (4 – 5 – 6) with the one connected with the CJC Sensor, included in the package.

 WIRING INSTRUCTIONS

  • Applicable wire size
   

Solid:  

0.2 to 2.5 mm

2

 (0.55 to 1.75 dia.)

   

Stranded:  0.2 to 2.5 mm

2

 

 

 

Tinning wire ends may cause contact failure   

 

 

and therefore is not recommended.

   

Ferruled:  0.2 to 1.5 mm

2

 (0.55 to 1.35 dia.)

 

 

 

 

The following Phoenix Contact terminals are  

   

 recommended:

 

 

 

 

AI 0.25-8YE 

0.2 to 0.25 mm

2

 

 

 

 

AI 0.34-8TQ 

0.25 to 0.34 mm

2

 

 

 

 

AI 0.5-8WH  

0.34 to 0.5 mm

2

 

 

 

 

AI 0.75-8GY 

0.5 to 0.75 mm

2

 

 

 

 

AI 1.0-8RD   

0.75 to 1.0 mm

2

 

 

 

 

AI 1.5-8BK   

1.0 to 1.5 mm

2

  • Expose wire conductors by 8 mm (0.31”).

8 mm

8 mm

4 mm dia.

max.

4 mm dia.

max.

Wire exposure

Recommended
ferruled wire

DIN Rail

35mm wide

Spring Loaded

DIN Rail Adaptor

INSTALLATION

 DIN RAIL MOUNTING

Set the unit so that its DIN rail adaptor is at the bottom.  
Position the upper hook at the rear side of the unit on the 
DIN rail and push in the lower.  When removing the unit, 
push down the DIN rail adaptor utilizing a minus screw-
driver and pull.

TERMINAL CONNECTIONS

Connect the unit as in the diagram below.  For use in a hazardous location, refer to “Installation Diagram” in the “Safe Instal-
lation Manual.”