B3HU
P. 3 / 3
EM-7502-A Rev.3
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive
remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this
warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original
sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
ADJUSTMENT PROCEDURE
■
INPUT RANGE LABEL
Blank I/O range labels are included in the product package.
Write in the configured ranges and put the label on the side
as shown below.
■
USING THE HART COMMUNICATION
Refer to the HART Setup Manual (EM-7502-B) included in
the attached CD.
For operating an HHC (Hand-Held Communicator), refer to
its instruction manual.
■
USING THE PC CONFIGURATOR
Detailed programming is available by using the PC Con-
figurator Software (model: B3HUCON) installed on a Win-
dows PC via a HART modem connected to the PC.
The PC Configurator Software and its Users Manual are
included in the attached CD.
CHECKING
Warning! Whenever you need to measure voltage across
the terminals or apply a simulated input signal to the terminals,
make sure that there is no danger of explosion in the atmos-
phere.
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Input: Check that the input voltage is within 0 – 100% of
full-scale.
If the thermocouple/RTD or its extension wires are bro-
ken, the output goes over 100% (below 0% with down-
scale) due to the burnout function. Check leadwires in
such a case.
3) Output: Check that the load is within the permissible
limit including wiring resistance.
Supply Voltage (V) – 12 (V)
Load Resistance (Ω) = ––––––––––––––––––––––––
0.024 (A)
(including
leadwire
resistance)
10 11 12
4
5
6
1
2
3
7
8
9
106 (4.17)
110.5 (4.35)
62 (2.44)
[5 (.20)]
DIN RAIL
35mm wide
• When mounting, no extra space is needed between units.
18 (.71)
7
(.28)
CJC SENSOR
*
(model: CJM
)
*
Used only with a thermocouple input
INPUT
OUTPUT
I/O Range Label (included in the product package)
EXTERNAL DIMENSIONS
mm (inch)